Set SW1 to
Performs this Action
F
Displays general status messages.
ICU fields are Read Only and cannot be changed.
0
Displays general status messages. Users can Read, Write,
and Update ICU configuration.
1
Displays most recent card swipe for 1 second
2
Displays most recent card swipe for 7 seconds
3
Tests and displays information about manual inputs for 1
second
4
Tests and displays information about manual inputs for 2
seconds
5
Activates output change display tests for manually
activated outputs and displays information for 2 seconds
6
Activates and tests all onboard outputs and other
outputs attached to an iSTAR eX through readers and R/8
boards for 1 second
7
Activates and tests all onboard outputs only on an iSTAR
eX, one by one. Test results are indicated by the LED
associated with each output.
8
Tests and displays diagnostic information about Ethernet #1
and Ethernet #2 ports.
Table 7-8: Rotary Switch SW1 Diagnostic Tests for iSTAR eX
iSTAR eX Installation and Configuration Guide
STAR eX Diagnostic Tests
Notes
ICU Block on
ICU Block off
Fast Mode on
Slow Mode on
Slow Mode Input Test
Fast Mode Input Test
Slow Mode Output Test
Fast Mode Output test.
LCD does not display all info
Displays results on LED
Ethernet Port and CF Slot
Test