Output Diagnostics
You can also use the iSTAR Web Page Diagnostic Utility to view reader
diagnostic information. For information about this utility, see "Diagnostic
Screens" on
page
6-10.
The iSTAR eX provides three types of output tests:
Output Change Display (slow) – tests a specific output that is activated
manually by the technician
Output Change Display (fast) – activates and tests every output on the
system. (Onboard outputs, reader outputs and R/8 outputs)
Output Test Mode – activates and tests onboard outputs one by one.
Do not activate outputs on a live system!
Output Change Display (Slow Mode)
The manual output test is an end-to-end test that displays information about
outputs activated manually by a technician. The outputs you are testing can
be attached to iSTAR eX through readers and R/8 boards. Information
displays on the LED for two seconds.
To activate the output change display test, set rotary switch SW1 to the
position shown in Table 7.3.
Table 7.3: Manual Output Test Switch Settings
Switch
Position
Function
SW1-5
Activate output change display for two seconds (slow mode)
Output Change Display (Fast Mode)
The output change display test is an end-to-end test that automatically
activates all outputs attached to iSTAR eX. The outputs you are testing can be
attached to iSTAR eX through readers and R/8 boards. Output information
iSTAR eX Installation and Configuration Guide
iSTAR eX Diagnostic Tests
7–5