Bell Test; Walk Test; Zone Monitor - Siemens SPC4000 Installation & Configuration Manual

Intrusion
Hide thumbs Also See for SPC4000:
Table of Contents

Advertisement

Engineer Programming Via the Keypad

10.12.1 Bell Test

10.12.2 Walk Test

10.12.3 Zone Monitor

78
Siemens Building Technologies
Fire Safety & Security Products
To perform a bell test:
1.
Scroll to the BELL TEST programming option.
2.
Press SELECT.
A walk test is a test performed on the SPC to ensure the sensors are operating
correctly.
To perform a walk test:
1.
Scroll to the WALK TEST programming option.
2.
Press SELECT.
The display indicates the total number of zones on the system with the text
'TO TEST XX' (where XX is the TOTAL number of zones).
Panic zones, Fire zones, Fire Exit zones and Holdup zones are included in
the walk test as activation of these zone types do not generate an alarm.
3.
Locate the sensor on the first zone and activate it (open the door or window).
The Keypad buzzer sounds continuously for approximately two seconds
indicating that the zone activation has been detected; the number of zones
remaining for test (displayed on the Keypad) decreases.
4.
Continue until all zones have been tested. If a zone activation is not
acknowledged by the system, check the wiring of the sensor and/or replace
with another sensor if necessary.
NOTE
Alarm zones programmed as Panic, Fire, Fire Exit, or Holdup type zones are all included in the walk
test in Full Engineer mode.
The Zone Monitor option displays status information on each of the zones on the
system.
To view zone status information:
1.
Scroll to the ZONE MONITOR programming option.
2.
Press SELECT.
3.
Scroll to a preferred zone and press SELECT.
The status of the zone and its associated resistance value is displayed.
4.
Press NEXT to locate the zone (e.g. CONTROLLER 1 = first zone on
Controller).
Refer to the table below for correlating status information (valid for Dual EOL
resistors).
09.2008

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents