Fire Safety SXL-EX CONTROL PANEL (For SXL-EX Firmware Revision 2.0 and higher) Operation, Installation, and Maintenance Manual Siemens Building Technologies, Ltd. Siemens Building Technologies, Inc. 2 Kenview Boulevard 8 Fernwood Road Florham Park, New Jersey 07932 Brampton, Ontario L6T 5E4 CN P/N 315-095997-6 Technical Manuals Online! - http://www.tech-man.com...
Page 2
Table of Contents Section Page Simple Zone Code ........................Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 3
Table of Contents (Cont.) Section Page Enter Password ......................... Reading the SXL-EX Display ..................... To Select Program Mode ......................To Exit Program Mode ......................Reading the SXL-EX Display ....................Enter Password ........................To Select Test Mode ........................ To Exit Test Mode ........................
Page 18
SXL-EX Operation, Installation, and Maintenance Manual (Test Level 4) Program Mode Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 19
SXL-EX Operation, Installation, and Maintenance Manual Enter Password Reading the SXL-EX Display To Select Program Mode Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 20
SXL-EX Operation, Installation, and Maintenance Manual 6. Press the key when done. Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 26
SXL-EX Operation, Installation, and Maintenance Manual TABLE 1 PROGRAM MODE LEVELS Level Sublevel Description Enable/Bypass Initiating Device Circuit Zone 1 Enable/Bypass Initiating Device Circuit Zone 2 Enable/Bypass Initiating Device Circuit Zone 3 Enable/Bypass Initiating Device Circuit Zone 4 Enable/Bypass Initiating Device Circuit Zone 5...
Page 27
SXL-EX Operation, Installation, and Maintenance Manual TABLE 2 TEST MODE LEVELS Level Sublevel Description One Person System Test with Notification Appliance Circuits Activated One Person System Test with Notification Appliance Circuits Silenced Test Main Board Alarm Relay Test NAC 1 Relay...
Page 28
SXL-EX Operation, Installation, and Maintenance Manual CHECKOUT PROCEDURE Maintenance TABLE 3 SYSTEM FAULT TROUBLESHOOTING Fault Code Display Trouble Possible Cause AC Power Fail Check AC Power Source AC Circuit Wiring Open Open F1 AC Fuse Brownout Notification Appliance Open Wire...
Page 29
SXL-EX Operation, Installation, and Maintenance Manual TABLE 4 ELECTRICAL REQUIREMENTS FOR BATTERY CALCULATIONS AND POWER MANAGEMENT Standby Alarm Current Current Main Board Current 0.110A 0.120A IDC Current (Zones 1-4): Number of IDC Zones ________ 0.009A (Standby) = _______A ________ 0.120A (Alarm) =...
Page 30
SXL-EX Operation, Installation, and Maintenance Manual MEASURE RESISTANCE BETWEEN DESIRED PROBABLE CAUSE IF TERMINAL AND TERMINAL RESULTS RESULTS DIFFER Meter connection for Field Wiring Checkout Procedure Steps 1 and 2: Positive lead connected to BL1-1 or BL2-1 and negative lead connected to BL1-2 or BL2-2.
Page 31
SXL-EX Operation, Installation, and Maintenance Manual TABLE 6 DEFAULT CONFIGURATIONS Level Sublevel Description User Factory Initiating Device Circuit Zone 1 Enabled Enabled Initiating Device Circuit Zone 2 Enabled Enabled Initiating Device Circuit Zone 3 Enabled Enabled Initiating Device Circuit Zone 4...
Page 34
IDC 8 UL Listed, Regulated, To JP3 To SXL Main Board OC 1 TB-2 and Filtered power External of SXL -V TB-3 SXL-EX Operation, Installation, and Maintenance Manual, SZE-4X Load supply. OC 2 Main External Load Board (See Note 6)
Page 35
All NACs are supervised and power limited per NFPA 70, Article 760. Each NAC must use at least 14 AWG, 300V insulation, color coded wire. NOTES: SXL-EX Operation, Installation, and Maintenance Manual, See Open Collector Electrical Rating Table and Note 6 OC 1 TB-2...