Engineer Programming Via the Keypad

10.2.1 Configuring a GSM or PSTN Modem

44
Siemens Building Technologies
Fire Safety & Security Products
Before changing PIN or new SIM card, ensure all
power sources are disconnected (AC mains and
battery) or card will not be activated.
To configure a GSM modem:
1.
Enter the Engineer Programming code
(default 1111).
2.
Press SELECT for FULL ENGINEER
programming.
3.
Using the up/down arrow keys, scroll to
COMMUNICATION> MODEMS programming
option.
4.
Press SELECT.
5.
Toggle between PRIMARY and BACKUP for
correct modem slot and press SELECT.
The ENABLE MODEM option is displayed.
6.
Press SELECT and toggle between
ENABLED and DISABLED for the preferred
setting and press SELECT.
Modem is enabled/disabled and UPDATED
displays.
1.
Scroll from this modem menu to MODEM
STATUS.
2.
Press SELECT to view the status of the
modem.
The FIRMWARE VERSION option is
displayed.
3.
Press SELECT to view the version of
firmware.
4.
Select GSM/PSTN PIN to enter the PIN code
for the SIM card.
5.
Select ANSWER MODE to enter the manner
the modem answers incoming calls.
6.
Select SMS ENABLE to enable SMS text
messages to mobile phones.
FULL ENGINEER
EXIT
SELECT
...COMMUNICATION...
BACK
SELECT
...MODEMS...
BACK
SELECT
...PRIMARY...
BACK
SELECT
...ENABLED
MODEM...
BACK
SELECT
ENABLED
BACK
SELECT
UPDATED
...MODEM STATUS...
BACK
SELECT
...FIRMWARE VERSION..
BACK
SELECT
...GSM PIN...
BACK
SELECT
...ANSWER MODE...
BACK
SELECT
...SMS ENABLED...
BACK
SELECT