10.4.14 Entry Time
10.4.15 Exit Time
10.4.16 Fullset Bell
10.4.17 Fullset Strobe
10.4.18 Final Exit
Siemens Building Technologies
Fire Safety & Security Products
To set the entry time setting:
1.
Scroll to the ENTRY TIME programming
option.
2.
Press SELECT.
3.
Enter the preferred time (XX-XXX sec).
4.
Press SAVE to update the setting.
To set the exit time setting:
1.
Scroll to the EXIT TIME programming option.
2.
Press SELECT.
3.
Enter the preferred time (0-720 min).
4.
Press SAVE to update the setting.
To set the fullset bell setting:
1.
Scroll to the FULLSET BELL programming
option.
2.
Press SELECT.
3.
Enter the preferred time (0-10 sec).
4.
Press SAVE to update the setting.
To set the fullset strobe setting:
1.
Scroll to the FULLSET STROBE programming
option.
2.
Press SELECT.
3.
Enter the preferred time (0-10 sec).
4.
Press SAVE to update the setting.
To set the final exit time:
1.
Scroll to the FINAL EXIT programming option.
2.
Press SELECT.
3.
Enter the preferred time (1-45 sec).
4.
Press SAVE to update the setting.
Engineer Programming Via the Keypad
...ENTRY TIME...
BACK
720
BACK
...EXIT TIME...
BACK
720
BACK
...FULLSET BELL...
BACK
0
BACK
...FULLSET STROBE...
BACK
0
BACK
...FINAL EXIT...
BACK
0
BACK
SELECT
(0-10) SEC
SAVE
SELECT
(0-720) MIN
SAVE
SELECT
(0-10) SEC
SAVE
SELECT
(0-10) SEC
SAVE
SELECT
(1-45) SEC
SAVE
59
09.2008