Siemens SPC4000 Installation & Configuration Manual page 55

Intrusion
Hide thumbs Also See for SPC4000:
Table of Contents

Advertisement

Timer
EXTERNAL BELL TIME
INTERNAL BELL TIME
EXTERNAL BELL DELAY
STROBE TIME
CHIME TIME
DIALLER DELAY
SOAK DAYS
DOUBLE KNOCK
MAINS SIGNAL DELAY
KEYPAD TIMEOUT
WIRELESS FAILED TO SET
(FTS)*
WIRELESS LOST*
ENGINEER ACCESS TIME
ENTRY TIME
EXIT TIME
BELL ON FULLSET
STROBE ON FULLSET
FINAL EXIT TIME
TECH DELAY
FAIL TO SET
Siemens Building Technologies
Fire Safety & Security Products
Description
Duration that external sounders will sound when alarm is activated
(Note: minimum bell time is 90 seconds)
Duration that Internal sounders will sound when alarm is Activated
Causes a delayed activation of the external bell
Duration that the strobe output is active when an alarm is Activated
Number of seconds that a chime output will activate, when a zone with
CHIME attribute opens
The dialler delay initiates a pre-defined delay period (0 -30 seconds)
before the system dials out to an Alarm Receiving Centre. This is
specifically designed to reduce unwarranted responses from Alarm
Receiving Centres and the constabulary. In the event of a subsequent
zone being tripped, the dialler delay period is ignored and the dialler
dials out immediately.
The number of days a zone remains under soak test before it
automatically returns to normal operation
The maximum delay between activations of zones with the double
attribute, which causes an alarm
The time after a Mains fault has been detected before an alert is
activated by the system
The number of seconds that an RKD will wait for key entry before it
leaves the current menu
The number of minutes without supervision that will prevent arming
*Wireless features and devices will be available with a later market
package.
The number of minutes without a supervision signal being received by
the SPC Controller before it reports the sensor as being lost
* Wireless features and devices will be available with a later market
package.
The time period engineer access is permitted; this timer starts as soon
as the user selects ALLOW ENGINEER in the GRANT ACCESS user
menu option
The time period allowed for the user to UNSET the alarm, having
opened an entry/exit zone of an armed system
The time period allowed for the user to exit the building after having set
the system
Activates the external bell momentarily to indicate a full set condition
Activates the strobe on the external bell momentarily to indicate a full
set condition
The number of seconds arming is delayed after a zone programmed
with the final exit attribute is closed
The number of seconds before attributes for tech zones are activated
The number of seconds before the system notifies user of a Fail to Set
status following attempt to set alarm
Tab. 9
Timers
NOTE
Default times are dependent upon the Engineer configuration.
* The default times denoted may or may not be allowable and is dependent on the configuration by the
Engineer.
Engineer Programming Via the Keypad
*Default
15
15
0
15
2
30
14 Days
10 Seconds
0 Minutes
30 Seconds
0 Minutes
720 Minutes
0 Minutes
45 Seconds
45 Seconds
0 Seconds
0 Seconds
7 Seconds
0 Seconds
10 Seconds
55
09.2008