Engineer Programming Via the Keypad
74
Siemens Building Technologies
Fire Safety & Security Products
To program the zone outputs from the Keypad:
1.
Scroll to either the CONTROLLER or
EXPANDER setting and press SELECT.
If programming Expanders, scroll to the
Expander to be programmed.
2.
Scroll to the output to be programmed and
press SELECT.
3.
If the output activations are recorded in
the system event log (ie., Enabled, items
recorded / Disabled, items) the following
programming options are available:
Names: used to help identify the
–
output; enter a specific and descriptive
name
Output Type: determines the output
–
type; see 0, for a description of output
types
Output Mode: determines the style of
–
the output: Continuous, Momentary, or
Pulsed
Polarity: determines whether the
–
output is activated on a positive or
negative polarity
Log: determines if system log is
–
enabled or disabled
4.
Press BACK to exit the Outputs menu.
For the Output test procedure, see Section
10.12.4, Output Test.
...CONTROLLER...
BACK
SELECT
...OUTPUT1...
BACK
SELECT
Ext. Bell
BACK
ENTER
...OUTPUT TYPE...
BACK
SELECT
...SYSTEM...
BACK
ENTER
...OUTPUT MODE...
BACK
SELECT
...CONTINOUS...
BACK
SELECT
...POLARITY...
BACK
SELECT
...POSITIVE...
BACK
SELECT
...LOG...
BACK
SELECT
...ENABLED...
BACK
SELECT
09.2008