12.5.2 Cases Where Rewriting During Run is Not Possible

When the timeout error message is indicated:

Even if the timeout error message is indicated, it is highly possible that the program in PLC has been
already rewritten. Carry out the following operations.

1. When ladder symbol mode

As a ladder editing is left, set it to the offline edit mode. Complete the program conversion in the tool
software, and then change to the online edit mode to check.

2. When boolean mode

A ladder editing is cleared.
Set it to the offline edit mode and carry out the editing operation again. After the operation, change to the
online edit mode to check.
When the timeout error occurs using the through mode in GT series programmable display
Extend the timeout time of the programmable display using the GTWIN.
(The default setting is 5 seconds.)
Select "Transfer" from "File" in the menu bar.
The "Transfer data" screen will open.
Select "Condition" to open "Communication
Setting" screen.
Change the value for "Timeout".
Click "OK" button to complete the change of
setting.
12-11