Setting Communication Parameters
Confirm that the model of the programming tool is FP0.
Usable communication port
COM port (RS232C port)
COM port (RS232C port) settings
Dialog box of PLC system register setting
No. 412 Communication mode
Select "General communication".
No. 413 Communication Format setting
Char. Bit: 7 bits/8 bits
Parity: None/Odd/Even
Stop bit: 1 bit/2 bits
Terminator: End code: CR/CR+LF/None/ETX
Header: STX not exist/STX
Specify the value to match the connected external device.
-
No. 414 Baud rate setting
Select one of the values from "300, 600, 1200, 2400, 4800, 9600 and 19200 bps".
No. 415 Unit number
The unit number can be set within a range of 1 to 99.
No. 417 Starting address for data received
No. 417 Buffer capacity setting for data received
For the general-purpose serial communication, setting "Receive buffer" is required.
To change this area, specify the starting address using system register No.417 and the volume (number
of words) using No.418. The receive buffer layout is shown below.
Starting address for data received
Buffer capacity setting for data received
C10,C14,C16: DT0 to DT1659
C32
: DT0 to DT6143
T32
: DT0 to DT16383
(Default: Tool port: DT4096 COM(RS232C) port: DT0)
C10, C14, C16: 0 to 1660 words (Default: 1660 words)
C32: 0 to 6144 words (Default: 6144 words)
T32: 0 to 16384 words (Default: 16384 words)