Panasonic FP0R User Manual page 268

Hide thumbs Also See for FP0R:
Table of Contents

Advertisement

No.
Name
High-speed
counter
operation
400
mode
settings (X0
to X2)
High-speed
counter
operation
400
mode
settings (X3
to X5)
High-speed
counter/
401
pulse output
settings
(X6 to X7)
Note1) If the operation mode is set to Two-phase, incremental/decremental, or incremental/decremental
control, the setting for CH1 or CH3 is invalid in system register 400 and the setting for CH5 is
invalid in system register 401.
Note2) If reset input settings overlap, the CH1 setting takes precedence in system register 400 and the
CH3 setting takes precedence in system register 401.
Note3) If system register 400 to 403 have been set simultaneously for the same input relay, the follwing
precedence order is effective: [High-speed counter]→[Pulse catch]→[Interrupt input].
<Example>
When the high-speed counter is being used in the addition input mode, even if input X0 is
specified as an interrupt input or as pulse catch input, those settings are invalid, and X0
functions as counter input for the high-speed counter.
15-6
Default value
CH0:
Do not set input
CH0
X0 as high-speed
counter
CH1:
Do not set input
CH1
X1 as high-speed
counter
CH2:
Do not set input
CH2
X3 as high-speed
counter
CH3:
Does not set
CH3
input X4 as high-
speed counter
CH4:
Do not set input
CH4
X6 as high-speed
counter
CH5:
Do not set input
CH5
X7 as high-speed
counter
Descriptions
Do not set input X0 as high-speed counter.
Two-phase input (X0, X1)
Two-phase input (X0, X1), Reset input (X2)
Incremental input (X0)
Incremental input (X0), Reset input (X2)
Decremental input (X0)
Decremental input (X0), Reset input (X2)
Individual input (X0, X1)
Individual input (X0, X1), Reset input (X2)
Incremental/decremental control input (X0, X1)
Incremental/decremental control input (X0, X1),
Reset input (X2)
Do not set input X1 as high-speed counter.
Incremental input (X1)
Incremental inptu (X1), Reset input (X2)
Decremental input (X1)
Decremental input (X1), Reset input (X2)
Do not set input X3 as high-speed counter.
Two-phase input (X3, X4)
Two-phase input (X3, X4), Reset input (X5)
Incremental input (X3)
Incremental input (X3), Reset input (X5)
Decremental input (X5)
Decremental input (X5), Reset input (X5)
Individual input (X3, X4)
Individual input (X3, X4), Reset input (X5)
Incremental/decremental control (X3, X4)
Incremental/decremental control (X3, X4),
Reset input (X5)
Does not set input X4 as high-speed counter.
Incremental input (X4)
Incremental input (X4), Reset input (X5)
Decremental input (X4)
Decremental input (X4), Reset input (X5)
Do not set input X6 as high-speed counter.
Incremental input (X6)
Decremental input (X6)
Two-phase input (X6, X7)
Individual input (X6, X7)
Incremental/decremental control input (X6, X7)
Do not set input X7 as high-speed counter.
Incremental input (X7)
Decremental input (X7)
FP0R