Using Fpwin Gr/Fpwin Pro - Panasonic FP0R User Manual

Hide thumbs Also See for FP0R:
Table of Contents

Advertisement

Procedure 2
<For error code is 1 to 9>
- Condition
There is a syntax error in the program.
- Operation 1
Change to PROG. mode and clear the error.
- Operation 2
Execute a total-check function using FPWIN GR to determine the location of the syntax error.
Or execute a check or compile using FPWIN Pro to determine the location of the syntax error.
<For error code is 20 or higher>
- Condition
A self-diagnostic error other than a syntax error has occurred.
- Operation
Use the programming tool in PROG. mode to clear the error.

Using FPWIN GR/FPWIN Pro

Click on the "Clear Error" button in the "Status display dialog box". Error code 43 and higher can be
cleared.
• In the PROG. mode, the power supply can be turned off and then on again to clear the error, but all of
the contents of the operation memory except hold type data are cleared.
• An error can also be cleared by executing a self-diagnostic error set instruction F148 (ERR).
Key Point:
When an operation error (error code 45) occurs, the address at which the error occurred is stored in
special data registers DT90017 and DT90018. If this happens, click on the "Operation Err" button in the
"Status display dialog box" and confirm the address at which the error occurred before cancelling the
error.
11-4