Panasonic FP0R User Manual page 336

Hide thumbs Also See for FP0R:
Table of Contents

Advertisement

Error
Name
code
Intelligent
E41
unit error
I/O unit
E42
verify error
15-74
Opera-
tion
Description and steps to take
status
An abnormality in an intelligent unit.
FPΣ, FP-X:
Check the contents of special data register
"DT90006" and locate the abnormal FP
intelligent unit (application cassette for FP-X).
FP2,FP2SH,and FP10SH:
Check the contents of special data registers
DT90006,DT90007 and locate the abnormal
intelligent unit. Then check the unit referring
to its manual..
Selection of operation status using system
register22:
Selec-
-to continue operation, set 1
table
-to stop operation, set 0
FP3:
Check the contents of special data registers
DT9006,DT9007 and locate the abnormal
intelligent unit. Then check the unit referring
to its manual..
Selection of operation status using system
register22:
-to continue operation, set 1
-to stop operation, set 0
Verification is possible in FPWIN GR/Pro at
"I/O error" in the status display function.
I/O unit(Expansion unit) wiring condition has
changed compared to that at time of power-
up.
⇒ Check the contents of special data register
(FP0: DT9010,
FPΣ, FP-X: DT90010,DT90011) and locate
the erroneous expansion unit.
It checks whether an expansion connector is
in agreement.
Selec-
⇒ Check the contents of special data register
table
(FP2,FP2SH,and
FP10SH:DT90010,DT90011,FP3
DT9010,DT9011)
Selection of operation status using system
register23:
-to continue operation, set 1
-to stop operation, set 0
Verification is possible in FPWIN GR/Pro at
"I/O error" in the status display function.
A
A
A
A
A
A
A
A
A
A
A: Available
A
A

Advertisement

Table of Contents
loading

Table of Contents