OR Output of Alarms

5-8-1

Integrated Alarm

You can use an integrated alarm to output an OR of alarms 1 to 4, the HB alarm, the HS alarm, and the
input error. Set the Integrated Alarm Assignment parameter (alma) and then assign the integrated
alarm (alm) to an auxiliary output or a control output.
Parameters
Parameter
Control Output
Assignment
Auxiliary
Output 1 to 4
Assignment
Integrated
Alarm
Assignment
E5@C-T Digital Temperature Controllers User's Manual (H185)
No. 1
Value
display
ALM: Integrated alarm (The Integrated
out1 to
Alarm Assignment parameter must be
out2
set separately.)
ALM: Integrated alarm (The Integrated
sub1 to
Alarm Assignment parameter must be
sub4
set separately.)
Set the sum of the following values for
the alarms and errors to include in the
OR output. 0 to 255
Alarm 1: +1
Alarm 2: +2
Alarm 3: +4
alma
Alarm 4: +8
HB alarm: +16
HS alarm: +32
Input error: +64
Not used.: +128
(Default: 49 (i.e., an OR of alarm 1, the
HB alarm, and the HS alarm))
5 Advanced Operations
No. 2
Level
display
Advanced
alm
Function Setting
Level
Advanced
alm
Function Setting
Level
Advanced
0 to 255
Function Setting
Level
5
5 - 23