A-6-10 Communications Setting Level - Omron E5AC-T User Manual

E5xc-t series digital temperature controllers programmable type
Hide thumbs Also See for E5AC-T:
Table of Contents

Advertisement

A Appendices

A-6-10 Communications Setting Level

Parameters
Protocol Setting
Communications Unit No.
Communications Baud Rate
Communications Data Length
Communications Stop Bits
Communications Parity
Send Data Wait Time
Highest Communications Unit No.
Area
First Address Upper Word
First Address Lower Word
Receive Data Wait Time
Communications Node Number
Upload Settings 1 to 23
Download Settings 1 to 43
Copy
A - 32
Characters
Setting (monitor) value
psel
CWF: CompoWay/F
MOD: Modbus
CMP: Component communications
FINS: Host Link (FINS)
MCP4: MC Protocol (Type 4)
u-no
0 to 99
bps
9.6, 19.2, 38.4, or 57.6
len
7, 8
sbit
1, 2
prty
NONE: None
EVEN: Even
ODD: Odd
sdwt
0 to 99
maxu
0 to 99
area
0 to 25
adrh
0 to 99
adrl
0 to 9999
rwat
100 to 9999
unit
0 to 99
up1
to
23
0 to 179
dn1
to
43
30 to 179
copy
OFF, ALL, or 1 to 31
Display
cwf
mod
cmp
fins
mcp4
9.6, 19.2,
38.4, 57.6
none, eVen,
odd
E5@C-T Digital Temperature Controllers User's Manual (H185)
Default
Unit
CompoWay/
None
F
1
None
9.6
kbps
7
Bit
2
Bit
Even
None
20
ms
0
None
0
None
0
None
0
None
1000
ms
0
None
None
None
OFF
None

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5ec-tE5cc-t

Table of Contents