Omron E5AC-T User Manual page 413

E5xc-t series digital temperature controllers programmable type
Hide thumbs Also See for E5AC-T:
Table of Contents

Advertisement

A Appendices
Parameters
Characters
s-hc
Standard or
Heating/Cooling
cp
Control Period
(Heating)
c-cp
Control Period
(Cooling)
orev
Direct/Reverse
Operation
alt1
Alarm 1Type
alh1
Alarm 1 Hysteresis
alt2
Alarm 2 Type
alh2
Alarm 2 Hysteresis
alt3
Alarm 3 Type
alh3
Alarm 3 Hysteresis
A - 24
Setting (monitor) value
Standard or heating/cooling
0.1, 0.2, 0.5, or 1 to 99
0.1, 0.2, 0.5, or 1 to 99
Reverse operation, direct operation
0: Alarm function OFF
1: Upper and lower-limit alarm
2: Upper-limit alarm
3: Lower-limit alarm
4: Upper and lower-limit range alarm
5: Upper- and lower-limit alarm with standby
sequence
6: Upper-limit alarm with standby sequence
7: Lower-limit alarm with standby sequence
8: Absolute-value upper-limit alarm
9: Absolute-value lower-limit alarm
10: Absolute-value upper-limit alarm with standby
sequence
11: Absolute-value lower-limit alarm with standby
sequence
12: LBA (Loop Burnout Alarm) (A Standard Model
must be used.)
13: PV change rate alarm
14: SP absolute-value upper-limit alarm
15: SP absolute-value lower-limit alarm
16: MV absolute-value upper-limit alarm
17: MV absolute-value lower-limit alarm
Temperature input: 0.1 to 999.9 for all alarms except
for MV absolute-value upper-limit or MV lower-limit
alarms
Analog input: 0.01 to 99.99 for all alarms except for
MV absolute-value upper-limit or MV lower-limit
alarms
0.01 to 99.99 for MV absolute-value upper-limit or
MV lower-limit alarms
Same as Alarm 1 Type except that 12 (LBA) cannot
be set.
Temperature input: 0.1 to 999.9 for all alarms except
for MV absolute-value upper-limit or MV lower-limit
alarms
Analog input: 0.01 to 99.99 for all alarms except for
MV absolute-value upper-limit or MV lower-limit
alarms
0.01 to 99.99 for MV absolute-value upper-limit or
MV lower-limit alarms
Same as Alarm 1 Type except that 12 (LBA) cannot
be set.
Temperature input: 0.1 to 999.9 for all alarms except
for MV absolute-value upper-limit or MV lower-limit
alarms
Analog input: 0.01 to 99.99 for all alarms except for
MV absolute-value upper-limit or MV lower-limit
alarms
0.01 to 99.99 for MV absolute-value upper-limit or
MV lower-limit alarms
Display
stnd, h-c
Standard
0.1, 0.2, 0.5, 1
Relay
to 99
output: 20
Voltage
output (for
driving
SSR): 2
0.1, 0.2, 0.5, 1
Relay
to 99
output: 20
Voltage
output (for
driving
SSR): 2
or-r, or-d
Reverse
operation
2
0.2
0.02
0.50
2
0.2
0.02
0.50
2
0.2
0.02
0.50
E5@C-T Digital Temperature Controllers User's Manual (H185)
Default
Unit
None
Seconds
Seconds
None
None
°C or °F
%FS
%
None
°C or °F
%FS
%
None
°C or °F
%FS
%