Omron E5AC-T User Manual page 183

E5xc-t series digital temperature controllers programmable type
Hide thumbs Also See for E5AC-T:
Table of Contents

Advertisement

5 Advanced Operations
Setting Example
In this example, the SP Mode parameter in the Adjustment Level is set to mask (mask (hide)).
Operating Procedure
Moving to Parameter Mask Mode (Advanced Function Setting Level)
1
Press the M Key several times in the Advanced Function
Setting Level to display the Parameter Mask Setting
parameter.
2
Press the U or D Key to set on (move to Parameter Mask
Mode).
The default is off.
Refer to 4-1-6 Moving to the Advanced Function Setting Level for the procedure to enter the
Advanced Function Setting Level.
Hiding the SP Mode Parameter (Adjustment Level)
1
Press the M Key several times in the Adjustment Level to
select the SP Mode parameter.
2
Press the U or D Key to set mask (mask (hide)).
The default is disp.
3
Press the O Key for at least 1 second to end Parameter Mask
Mode.
Refer to 4-1-3 Moving to the Adjustment Level for the procedure to enter the Adjustment Level.
Enabling Parameter Masks (Protect Level)
1
Press the M Key several times in the Protect Level to display
the Parameter Mask Enable parameter.
2
Press the U or D Key to set on (enable).
The default is on.
*The SP Mode parameter is masked (i.e., hidden).
Refer to 4-1-5 Moving to the Protect Level for the procedure to enter the Protect Level.
5 - 22
Advanced Function Setting
Level
pmst
pmst
Adjustment Level
spmd
disp
spmd
mask
Protect Level
pmsk
pmsk
E5@C-T Digital Temperature Controllers User's Manual (H185)
Parameter Mask
Settings
off
on
SP Mode
Parameter Mask
Enable
on
on