Setting the Autotuning Starting and Ending Points
Setting the Autotuning Starting Point (Fixed SP) (Adjustment Level)
1
Press the M Key several times in the Adjustment Level to
select the Fixed SP parameter.
2
Press the U or D Key to set 100.
The default is 0.
Refer to 4-1-1 Moving to the Initial Setting Level for the procedure to enter the Adjustment Level.
Setting the Autotuning Ending Point (All PID AT Upper Limit SP) (Initial
Setting Level)
1
Press the M Key several times in the Initial Setting Level to
display the All PID AT Upper Limit SP parameter.
2
Press the U or D Key to set 600.
The default is 0.
Refer to 4-1-1 Moving to the Initial Setting Level for the procedure to enter the Initial Setting Level.
Changing to Fixed SP Operation
Changing the SP Mode to Fixed SP (Adjustment Level)
(The Reset Operation parameter must be set to stop control.)
1
Press the M Key several times in the Adjustment Level to
select the SP Mode parameter.
2
Press the U or D Key to set fsp (fixed SP).
The default is psp (program SP).
Refer to 4-1-1 Moving to the Initial Setting Level for the procedure to enter the Adjustment Level.
E5@C-T Digital Temperature Controllers User's Manual (H185)
5 Advanced Operations
Adjustment Level
fsp
Fixed SP
0
fsp
100
Initial Setting Level
tspu
All PID AT
Upper Limit SP
0
tspu
600
Adjustment Level
spmd
SP Mode
psp
spmd
fsp
5 - 51