Omron E5AC-T User Manual page 319

E5xc-t series digital temperature controllers programmable type
Hide thumbs Also See for E5AC-T:
Table of Contents

Advertisement

6 Parameters
sl-h
sl-l
• These parameters set the upper and lower limits of the set points. A set point can be set
within the range defined by the upper and lower limit set values in the SP Upper Limit and
SP Lower Limit parameters. If these parameters are reset, any set point that is outside of
Function
the new range will be forcibly changed to either the upper limit or the lower limit.
• When the temperature input type and temperature unit have been changed, the set point
upper limit and set point lower limit are forcibly changed to the upper and lower limits of
the sensor.
• For a temperature input, the decimal point position depends on the currently selected
sensor, and for an analog input it depends on the Decimal Point parameter setting.
Set Point Upper
Setting
Limit
Set Point Lower
Limit
Related Parameters
See
See
Input Type (Initial Setting Level): Page 6-56
Temperature Unit (Initial Setting Level): Page 6-57
t-u
• This parameter sets the time unit for the program.
• This parameter sets the time unit for the following parameters. Always set this time unit
before setting the following parameters.
Function
• Segment Times
• Time Signal ON Times and Time Signal OFF Times
h-m: hours and minutes
Setting
m-s: minutes and seconds
6 - 58
SP Upper Limit
SP Lower Limit
Parameter name
Temperature
input
Analog input
Temperature
input
Analog input
Program Time Unit
Setting range
Setting range
SP lower limit + 1 to Input setting
range upper limit
SP lower limit + 1 to scaling upper
limit
Input setting range lower limit to
SP upper limit - 1
Scaling lower limit to SP upper
limit - 1
Unit
Default
h-m: hours and
---
minutes
E5@C-T Digital Temperature Controllers User's Manual (H185)
Unit
Default
EU
1300
EU
100
−200
EU
EU
0