Omron E5AC-T User Manual page 364

E5xc-t series digital temperature controllers programmable type
Hide thumbs Also See for E5AC-T:
Table of Contents

Advertisement

hctm
This parameter sets the tuning method that is suitable for the cooling control characteristics.
Function
0: Same as heating control
Setting
1: Linear
2: Air cooling
3: Water cooling
• Air Cooling/Water Cooling
Control that is suitable for an application that does not have linear cooling characteristics
(such as plastic molding machines) is performed. The response is fast and the response
characteristics are stable.
• Linear
Control that is suitable for an application that has linear cooling characteristics is
performed.
Cooling
capacity
[%]
E5@C-T Digital Temperature Controllers User's Manual (H185)
Heating/Cooling Tuning Method
Setting range
Water cooling
Air cooling
100
MV (cooling) [%]
0
Cooling Characteristics
The control must be set to heating/cooling control
and 2-PID control.
Default
0
Linear
100
6 Parameters
6
6 - 103

Hide quick links: