t-pr
This parameter specifies the segment setting method when a program is set.
There are two methods: Step Time, in which the arrival time and arrival SP are set, and
Rate of Rise Programming, in which the segment type is set (to ramp, soak, or step) and the
Function
values are set.
The setting method that you select does not affect the program patterns that you can create.
time: Step time
Setting
pr: Rate of rise programming
Related Sections
See
See
5-15 Program-related Functions (page 5-53)
pru
This parameter sets the time unit for the denominator of the Segment Slope parameter.
Example:
Function
h: Hours
Setting
m: Minutes
Related Sections
See
See
5-15 Program-related Functions (page 5-53)
Related Parameters
Step Time/Rate of Rise Programming (Initial Setting Level): Page 6-59
E5@C-T Digital Temperature Controllers User's Manual (H185)
Step Time/Rate of Rise
Programming
Setting range
Time Unit of Ramp Rate
If the Segment Ramp Rate parameter is set to 100 and the Time Unit of Ramp
Rate parameter is set to M (minutes), the program SP will change at a rate of
100 per minute toward the segment SP.
Setting range
Unit
Default
time: Step time
---
The Step Time/Rate of Rise Programming
parameter must be set to Rate of Rise
Programming.
Unit
Default
m: Minutes
---