Omron E5AC-T User Manual page 381

E5xc-t series digital temperature controllers programmable type
Hide thumbs Also See for E5AC-T:
Table of Contents

Advertisement

7 User Calibration
str
no
7 - 8
7. When the M Key is pressed, the status changes as shown to the left.
The data to be temporarily registered is not displayed if it is not complete.
Press the U Key. The No. 2 display changes to yes. Release the key and wait
two seconds or press the M Key. This stores the temporarily registered calibration
data to non-volatile memory.
To cancel the saving of temporarily registered calibration data to non-volatile
memory, press the M Key (while no is displayed in the No. 2 display) without
pressing the U Key.
8. The calibration mode is quit by turning the power OFF.
For Controllers that have a transfer output, you can continue by calibrating the
transfer output. For detailed setting methods, refer to 7-6 Calibrating the Transfer
Output.
E5@C-T Digital Temperature Controllers User's Manual (H185)