CHAPTER 5: SETTINGS

5.3.13 Control pushbuttons

SETTINGS  PRODUCT SETUP  CONTROL PUSHBUTTONS  CONTROL PUSHBUTTON 1(7)
 CONTROL
 PUSHBUTTON 1
There are three standard control pushbuttons, labeled USER 1, USER 2, and USER 3, on the standard and enhanced front
panels. These are user-programmable and can be used for various applications such as performing an LED test, switching
setting groups, and invoking and scrolling though user-programmable displays.
Firmware revisions 3.2x and older use these three pushbuttons for manual breaker control. This functionality has been
retained—if the breaker control feature is configured to use the three pushbuttons, they cannot be used as user-
programmable control pushbuttons.
The location of the control pushbuttons are shown in the following figures.
An additional four control pushbuttons are included on the standard faceplate when the L60 is ordered with the 12 user-
programmable pushbutton option.
Control pushbuttons are not typically used for critical operations and are not protected by the control password. However,
by supervising their output operands, the user can dynamically enable or disable control pushbuttons for security reasons.
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
CONTROL PUSHBUTTN 1 ID
CTRL PB 1
CONTROL PUSHBUTTON 1
FUNCTION: Disabled
CONTROL PUSHBUTTON 1
EVENTS: Disabled
Figure 5-43: Control pushbuttons (enhanced faceplate)
Figure 5-44: Control pushbuttons (standard faceplate)
Range: up to 20 alphanumeric characters
Range: Disabled, Enabled
Range: Disabled, Enabled