GE L60 Instruction Manual page 500

Line phase comparison system
Hide thumbs Also See for L60:
Table of Contents

Advertisement

CONTROL ELEMENTS
AR TRANSFER 1 TO 2
breaker 1 is blocked. When set to "Yes" the closing command is transferred direct to breaker 2 without waiting the transfer
time. When set to "No" the closing command is blocked by the AR BKR1 BLK signal and the scheme will be sent to lockout
by the incomplete sequence timer.
AR TRANSFER 2 TO 1
breaker 2 is blocked. When set to "Yes" the closing command is transferred direct to breaker 1 without waiting the transfer
time. When set to "No", the closing command is blocked by the AR BKR2 BLK signal and the scheme is sent to lockout by
the incomplete sequence timer.
AR BKR1 FAIL OPTION
Breaker 1 has failed to close. When set to "Continue" the closing command is transferred to breaker 2, which continues the
reclosing cycle until successful (the scheme resets) or unsuccessful (the scheme goes to Lockout). When set to "Lockout"
the scheme goes to lockout without attempting to reclose breaker 2.
AR BKR2 FAIL OPTION
Breaker 2 has failed to close. When set to "Continue" the closing command is transferred to breaker 1, which continues the
reclosing cycle until successful (the scheme resets) or unsuccessful (the scheme goes to Lockout). When set to "Lockout"
the scheme goes to lockout without attempting to reclose breaker 1.
— Set this intentional delay longer than the estimated de-ionizing time after the first single-pole trip.
AR 1-P DEAD TIME
AR BREAKER SEQUENCE
reclose breaker 2 only, "1&2" for reclose both breakers simultaneously, "1-2" for reclose breakers sequentially; Breaker 1
first, and "2-1" for reclose breakers sequentially; Breaker 2 first.
AR TRANSFER TIME
reclosed sequentially. The transfer timer is initiated by a close signal to the first breaker. The transfer timer transfers the
reclose signal from the breaker selected to close first to the second breaker. The time delay setting is based on the
5
maximum time interval between the autoreclose signal and the protection trip contact closure assuming a permanent
fault (unsuccessful reclose). Therefore, the minimum setting is equal to the maximum breaker closing time plus the
maximum line protection operating time plus a suitable margin. This setting prevents the autoreclose scheme from
transferring the close signal to the second breaker unless a successful reclose of the first breaker occurs.
— This setting is used in breaker-and-a-half applications to allow the autoreclose control function to
AR BUS FLT INIT
perform reclosing with only one breaker previously opened by bus protection. For line faults, both breakers must open for
the autoreclose reclosing cycles to take effect.
5-332
— This setting establishes how the scheme performs when the breaker closing sequence is 1-2 and
— This setting establishes how the scheme performs when the breaker closing sequence is 2-1 and
— This setting establishes how the scheme performs when the breaker closing sequence is 1-2 and
— This setting establishes how the scheme performs when the breaker closing sequence is 2-1 and
— This setting selects the breakers reclose sequence: Select "1" for reclose breaker 1 only, "2" for
— The transfer time is used only for breaker closing sequence 1-2 or 2-1, when the two breakers are
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL