TRANSDUCER INPUTS/OUTPUTS
See the following table for reference temperature values for each RTD type.
Table 5-42: RTD temperature vs. resistance
Temperature
°C
°F
–50
–58
–40
–40
–30
–22
–20
–4
–10
14
0
32
10
50
20
68
30
86
40
104
50
122
60
140
70
158
80
176
90
194
100
212
5
110
230
120
248
130
266
140
284
150
302
160
320
170
338
180
356
190
374
200
392
210
410
220
428
230
446
240
464
250
482
5.9.3 DCmA outputs
SETTINGS TRANSDUCER I/O DCMA OUTPUTS DCMA OUTPUT H1(W8)
DCMA OUTPUT H1
5-352
Resistance (in ohms)
100 Ω Pt
120 Ω Ni
100 Ω Ni
(DIN 43760)
80.31
86.17
71.81
84.27
92.76
77.30
88.22
99.41
82.84
92.16
106.15
88.45
96.09
113.00
94.17
100.00
120.00
100.00
103.90
127.17
105.97
107.79
134.52
112.10
111.67
142.06
118.38
115.54
149.79
124.82
119.39
157.74
131.45
123.24
165.90
138.25
127.07
174.25
145.20
130.89
182.84
152.37
134.70
191.64
159.70
138.50
200.64
167.20
142.29
209.85
174.87
146.06
219.29
182.75
149.82
228.96
190.80
153.58
238.85
199.04
157.32
248.95
207.45
161.04
259.30
216.08
164.76
269.91
224.92
168.47
280.77
233.97
172.46
291.96
243.30
175.84
303.46
252.88
179.51
315.31
262.76
183.17
327.54
272.94
186.82
340.14
283.45
190.45
353.14
294.28
194.08
366.53
305.44
DCMA OUTPUT H1
SOURCE: Off
DCMA OUTPUT H1
RANGE: –1 to 1 mA
DCMA OUTPUT H1
MIN VAL: 0.000 pu
DCMA OUTPUT H1
MAX VAL: 1.000 pu
10 Ω Cu
7.10
7.49
7.88
8.26
8.65
9.04
9.42
9.81
10.19
10.58
10.97
11.35
11.74
12.12
12.51
12.90
13.28
13.67
14.06
14.44
14.83
15.22
15.61
16.00
16.39
16.78
17.17
17.56
17.95
18.34
18.73
Range: Off, any analog actual value parameter
Range: –1 to 1 mA, 0 to 1 mA, 4 to 20 mA
Range: –90.000 to 90.000 pu in steps of 0.001
Range: –90.000 to 90.000 pu in steps of 0.001
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS