Trip Output - GE L60 Instruction Manual

Line phase comparison system
Hide thumbs Also See for L60:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS

5.7.5 Trip output

SETTINGS  CONTROL ELEMENTS  TRIP OUTPUT
 TRIP OUTPUT
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
Figure 5-162: Selector switch logic
TRIP MODE:
Disabled
TRIP 3-POLE INPUT1:
Off
TRIP 3-POLE INPUT6:
Off
TRIP 1-POLE INPUT1:
Off
TRIP 1-POLE INPUT6:
Off
TRIP RECLOSE INPUT1:
Off
TRIP RECLOSE INPUT6:
Off
TRIP SEAL-IN DELAY:
0.000 s
Range: Disabled, 3 Pole Only, 3 Pole & 1 Pole
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: 0 to 65.535 s in steps of 0.001
CONTROL ELEMENTS
5
5-283

Advertisement

Table of Contents
loading

Table of Contents