Advertisement

CONTROL ELEMENTS
5

5.7.11 Autoreclose (ANSI 79)

SETTINGS  CONTROL ELEMENTS  AUTORECLOSE  AUTORECLOSE
 AUTORECLOSE
5-324
Figure 5-185: POTT scheme logic
AR FUNCTION:
Disabled
AR MODE:
Mode 1 (1 & 3 Pole)
Mode 1 Activation:
Off
Mode 2 Activation:
Off
Mode 3 Activation:
Off
Mode 4 Activation:
Off
AR MAX NUMBER OF
SHOTS: 2
AR INITIATE MODE:
Protection AND CB
Range: Disabled, Enabled
Range: Mode 1(1 & 3 Pole), Mode 2 (1 Pole), Mode 3 (3
Pole-A), Mode 4 (3 Pole-B)
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: 1, 2, 3, 4
Range: Protection AND CB, Protection Only
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL