CHAPTER 5: SETTINGS
— The trip bus output is reset when the operand assigned to this setting is asserted. Note that the
TRIP BUS 1 RESET
operand is pre-wired to the reset gate of the latch, As such, a reset command from the front panel interface or via
communications resets the trip bus output.

5.7.3 Setting groups

SETTINGS  CONTROL ELEMENTS  SETTING GROUPS
 SETTING GROUPS
The setting groups menu controls the activation and deactivation of up to six possible groups of settings in the
settings menu. The active setting group can be indicated on the front display of the UR by configuring User-
ELEMENTS
Programmable LEDs to display the state of the
— When Enabled, allows setting groups other than group 1 (the default active group) to be
SETTING GROUPS FUNCTION
activated. The default setting group is forced active while the
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
Figure 5-158: Trip bus logic
SETTING GROUPS
FUNCTION: Enabled
SETTING GROUPS BLK:
Off
GROUP 2 ACTIVATE ON:
Off
GROUP 6 ACTIVATE ON:
Off
GROUP 1 NAME:
GROUP 6 NAME:
SETTING GROUP
EVENTS: Disabled
FlexLogic operands.
SETTING GROUP ACT
SETTING GROUPS FUNCTION
Range: Disabled, Enabled
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: up to 16 alphanumeric characters
Range: up to 16 alphanumeric characters
Range: Disabled, Enabled
setting is Disabled.
CONTROL ELEMENTS
RESET OP
5
GROUPED
5-275