GE L60 Instruction Manual page 484

Line phase comparison system
Hide thumbs Also See for L60:
Table of Contents

Advertisement

CONTROL ELEMENTS
5
5.7.9.8 Thermal overload protection (ANSI 49)
SETTINGS  CONTROL ELEMENTS  MONITORING ELEMENTS  THERMAL OVERLOAD PROTECTION 
THERMAL PROTECTION 1(2)
 THERMAL
 PROTECTION 1
5-316
Figure 5-181: Open pole detector logic (Sheet 2 of 2)
THERMAL PROTECTION 1
FUNCTION: Disabled
THERMAL PROTECTION 1
SOURCE: SRC1
THERMAL PROTECTION 1
BASE CURR: 0.80 pu
THERMAL PROTECTION 1
k FACTOR: 1.10
THERM PROT 1 TRIP
TIME CONST: 45 min
THERM PROT 1 RESET
TIME CONST: 45 min
THERM PROT 1 MINIM
RESET TIME: 20 min
THERM PROT 1 RESET:
Off
THERM PROT 1 BLOCK:
Off
THERMAL PROTECTION 1
TARGET: Self-reset
THERMAL PROTECTION 1
EVENTS: Disabled
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: 0.20 to 3.00 pu in steps of 0.01
Range: 1.00 to 1.20 in steps of 0.05
Range: 0 to 1000 min. in steps of 1
Range: 0 to 1000 min. in steps of 1
Range: 0 to 1000 min. in steps of 1
Range: FlexLogic operand
Range: FlexLogic operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS