5.2 PRODUCT SETUP
Refer to the Control of setting groups example in the Control elements section of this chapter for group activation.
PATH: SETTINGS
PRODUCT SETUP
USER-PROGRAMMABLE
SELF TESTS
All major self-test alarms are reported automatically with their corresponding FlexLogic™ operands, events, and targets.
5
Most of the minor alarms can be disabled if desired.
When in the "Disabled" mode, minor alarms will not assert a FlexLogic™ operand, write to the event recorder, or display
target messages. Moreover, they will not trigger the
mode, minor alarms continue to function along with other major and minor alarms. Refer to the Relay self-tests section in
chapter 7 for additional information on major and minor self-test alarms.
To enable the Ethernet switch failure function, ensure that the
menu.
NOTE
PATH: SETTINGS
PRODUCT SETUP
CONTROL
PUSHBUTTON 1
There are three standard control pushbuttons, labeled USER 1, USER 2, and USER 3, on the standard and enhanced front
panels. These are user-programmable and can be used for various applications such as performing an LED test, switching
setting groups, and invoking and scrolling though user-programmable displays.
Firmware revisions 3.2x and older use these three pushbuttons for manual breaker control. This functionality has been
retained – if the breaker control feature is configured to use the three pushbuttons, they cannot be used as user-program-
mable control pushbuttons.
5-50
USER-PROGRAMMABLE SELF TESTS
REMOTE DEVICE OFF
FUNCTION: Enabled
PRI. ETHERNET FAIL
MESSAGE
FUNCTION: Disabled
SEC. ETHERNET FAIL
MESSAGE
FUNCTION: Disabled
BATTERY FAIL
MESSAGE
FUNCTION: Enabled
SNTP FAIL
MESSAGE
FUNCTION: Enabled
IRIG-B FAIL
MESSAGE
FUNCTION: Enabled
ETHERNET SWITCH FAIL
MESSAGE
FUNCTION: Disabled
ANY MINOR ALARM

CONTROL PUSHBUTTONS

CONTROL PUSHBUTTON 1
FUNCTION: Disabled
CONTROL PUSHBUTTON 1
MESSAGE
EVENTS: Disabled
L90 Line Current Differential System

5.2.12 USER-PROGRAMMABLE SELF-TESTS

Range: Disabled, Enabled. Valid for units that contain a
CPU with Ethernet capability.
Range: Disabled, Enabled. Valid for units that contain a
CPU with a primary fiber port.
Range: Disabled, Enabled. Valid for units that contain a
CPU with a redundant fiber port.
Range: Disabled, Enabled.
Range: Disabled, Enabled. Valid for units that contain a
CPU with Ethernet capability.
Range: Disabled, Enabled.
Range: Disabled, Enabled. Valid for units that contain a
switch module.
or
messages. When in the "Enabled"
ANY SELF-TEST
ETHERNET SWITCH FAIL FUNCTION
5.2.13 CONTROL PUSHBUTTONS
CONTROL PUSHBUTTON 1(7)
Range: Disabled, Enabled
Range: Disabled, Enabled
5 SETTINGS