GE L60 Instruction Manual page 323

Line phase comparison system
Hide thumbs Also See for L60:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
Operand type
Operand syntax
ELEMENT:
TRIP 3-POLE
Trip output
TRIP 1-POLE
TRIP PHASE A
TRIP PHASE B
TRIP PHASE C
TRIP AR INIT 3-POLE
TRIP FORCE 3-POLE
TRIP OUTPUT OP
TRIP Z2PH TMR INIT
TRIP Z2GR TMR INIT
ELEMENT:
TRIP BUS 1 PKP
Trip bus
TRIP BUS 1 OP
TRIP BUS 2 to 6
ELEMENT:
WATTMETRIC 1 PKP
Wattmetric zero-
WATTMETRIC 1 OP
sequence directional
WATTMETRIC 2
FIXED OPERANDS
Off
On
INPUTS/OUTPUTS:
Cont Ip 1 On
Contact inputs
Cont Ip 2 On
Cont Ip 1 Off
Cont Ip 2 Off
Cont Ip 96 On
Cont Ip 96 Off
INPUTS/OUTPUTS:
Cont Op 1
Contact outputs,
Cont Op 2
current
(from detector on
Cont Op 64
form-A output only)
INPUTS/OUTPUTS:
Cont Op 1 VOn
Contact outputs,
Cont Op 2
voltage
(from detector on
Cont Op 64
form-A output only)
Cont Op 1
Cont Op 2
Cont Op 64
INPUTS/OUTPUTS:
DIRECT INPUT 1 On
Direct inputs
DIRECT INPUT 32 On
INPUTS/OUTPUTS:
RxG DPS 1 BAD
RxGOOSE DPS
RxG DPS 1 INTERM
RxG DPS 1 OFF
RxG DPS 1 ON
RxG DPS 2 to 5
INPUTS/OUTPUTS:
RxG Bool 1 On
RxGOOSE Booleans
RxG Bool 2 On
RxG Bool 3 On
RxG Bool 32 On
INPUTS/OUTPUTS:
Virt Ip 1 On
Virtual inputs
Virt Ip 2 On
Virt Ip 3 On
Virt Ip 64 On
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
Operand description
Trip all three breaker poles
A single-pole trip-and-reclose operation is initiated
Trip breaker pole A, initiate phase A breaker fail and reclose
Trip breaker pole B, initiate phase B breaker fail and reclose
Trip breaker pole C, initiate phase C breaker fail and reclose
Initiate a three-pole reclose
Three-pole trip must be initiated
Any trip is initiated by the trip output
Phase distance zone 2 timer is initiated by the trip output
Ground distance zone 2 timer is initiated by the trip output
Asserted when the trip bus 1 element picks up
Asserted when the trip bus 1 element operates
Same set of operands as shown for TRIP BUS 1
Wattmetric directional element 1 has picked up
Wattmetric directional element 1 has operated
Same set of operands as per WATTMETRIC 1
Logic = 0. Does nothing and can be used as a delimiter in an equation list;
used as 'Disable' by other features.
Logic = 1. Can be used as a test setting.
(does not appear unless ordered)
(does not appear unless ordered)
(does not appear unless ordered)
(does not appear unless ordered)
(does not appear unless ordered)
(does not appear unless ordered)
IOn
(does not appear unless ordered)
IOn
(does not appear unless ordered)
IOn
(does not appear unless ordered)
(does not appear unless ordered)
VOn
(does not appear unless ordered)
VOn
(does not appear unless ordered)
VOff
(does not appear unless ordered)
VOff
(does not appear unless ordered)
VOff
(does not appear unless ordered)
Flag is set, logic=1
Flag is set, logic=1
Asserted while the RxGOOSE double-point status input is in the bad state
Asserted while the RxGOOSE double-point status input is in the intermediate
state
Asserted while the RxGOOSE double-point status input is off
Asserted while the RxGOOSE double-point status input is on
Same set of operands as per RxG DPS 1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
FLEXLOGIC
5
5-155