GE L30 Instruction Manual

Ur series line current differential system
Hide thumbs Also See for L30:
Table of Contents

Advertisement

GE
Digital Energy
GE Digital Energy
650 Markland Street
Markham, Ontario
Canada L6C 0M1
Tel: +1 905 927 7070 Fax: +1 905 927 5098
Internet:
http://www.GEDigitalEnergy.com
*1601-9050-Z3*
L30 Line Current Differential
UR Series Instruction Manual
Manual P/N: 1601-9050-Z3 (GEK-119520B)
IND.CONT. EQ.
System
L30 revision: 7.1x
831776A2.CDR
E83849
LISTED
52TL
GE Multilin's Quality Management
System is registered to ISO
9001:2008
QMI # 005094
UL # A3775

Advertisement

Table of Contents
loading

Summary of Contents for GE L30

  • Page 1 Digital Energy L30 Line Current Differential System UR Series Instruction Manual L30 revision: 7.1x Manual P/N: 1601-9050-Z3 (GEK-119520B) 831776A2.CDR E83849 GE Digital Energy LISTED 650 Markland Street IND.CONT. EQ. 52TL Markham, Ontario GE Multilin's Quality Management Canada L6C 0M1 System is registered to ISO...
  • Page 2 The contents of this manual are the property of GE Multilin Inc. This documentation is furnished on license and may not be reproduced in whole or in part without the permission of GE Multilin. The content of this manual is for informational use only and is subject to change without notice.
  • Page 3 1.3 ENERVISTA UR SETUP SOFTWARE 1.3.1 PC REQUIREMENTS ..................1-6 1.3.2 INSTALLATION....................1-6 1.3.3 CONFIGURING THE L30 FOR SOFTWARE ACCESS........1-7 1.3.4 USING THE QUICK CONNECT FEATURE............. 1-10 1.3.5 CONNECTING TO THE L30 RELAY ............... 1-15 1.3.6 SETTING UP CYBERSENTRY AND CHANGING DEFAULT PASSWORD ... 1-16 1.4 UR HARDWARE...
  • Page 4 5.2 PRODUCT SETUP 5.2.1 SECURITY......................5-8 5.2.2 DISPLAY PROPERTIES ..................5-24 5.2.3 CLEAR RELAY RECORDS ................5-26 5.2.4 COMMUNICATIONS ..................5-27 5.2.5 MODBUS USER MAP ..................5-57 5.2.6 REAL TIME CLOCK ..................5-58 5.2.7 FAULT REPORTS ....................5-63 5.2.8 OSCILLOGRAPHY ...................5-65 L30 Line Current Differential System GE Multilin...
  • Page 5 5.8.7 REMOTE DOUBLE-POINT STATUS INPUTS ..........5-243 5.8.8 REMOTE OUTPUTS..................5-243 5.8.9 DIRECT INPUTS AND OUTPUTS ..............5-244 5.8.10 RESETTING....................5-247 5.8.11 IEC 61850 GOOSE ANALOGS..............5-247 5.8.12 IEC 61850 GOOSE INTEGERS..............5-248 GE Multilin L30 Line Current Differential System...
  • Page 6 6.5 PRODUCT INFORMATION 6.5.1 MODEL INFORMATION ...................6-25 6.5.2 FIRMWARE REVISIONS..................6-25 7. COMMANDS AND 7.1 COMMANDS TARGETS 7.1.1 COMMANDS MENU ...................7-1 7.1.2 VIRTUAL INPUTS ....................7-1 7.1.3 CLEAR RECORDS .....................7-2 7.1.4 SET DATE AND TIME ..................7-2 L30 Line Current Differential System GE Multilin...
  • Page 7 COMPENSATION METHOD 1 ................9-7 9.3.3 COMPENSATION METHOD 2 ................9-8 9.3.4 COMPENSATION METHOD 3 ................9-8 9.4 INSTANTANEOUS ELEMENTS 9.4.1 INSTANTANEOUS ELEMENT ERROR DURING L30 SYNCHRONIZATION. 9-10 10. COMMISSIONING 10.1 TESTING 10.1.1 CHANNEL TESTING ..................10-1 GE Multilin L30 Line Current Differential System...
  • Page 8 C.2.3 GGIO2: DIGITAL CONTROL VALUES.............. C-3 C.2.4 GGIO3: DIGITAL STATUS AND ANALOG VALUES FROM GOOSE DATA ..C-3 C.2.5 GGIO4: GENERIC ANALOG MEASURED VALUES......... C-3 C.2.6 MMXU: ANALOG MEASURED VALUES ............C-4 viii L30 Line Current Differential System GE Multilin...
  • Page 9 F.1 RADIUS SERVER CONFIGURATION F.1.1 RADIUS SERVER CONFIGURATION............... F-1 G. MISCELLANEOUS G.1 CHANGE NOTES G.1.1 REVISION HISTORY ..................G-1 G.1.2 CHANGES TO THE L30 MANUAL ..............G-1 G.2 ABBREVIATIONS G.2.1 STANDARD ABBREVIATIONS ................ G-5 GE Multilin L30 Line Current Differential System...
  • Page 10 TABLE OF CONTENTS G.3 WARRANTY G.3.1 GE MULTILIN WARRANTY................G-7 L30 Line Current Differential System GE Multilin...
  • Page 11: Cautions And Warnings

    1.1 IMPORTANT PROCEDURES 1 GETTING STARTED 1.1IMPORTANT PROCEDURES Use this chapter for initial setup of your new L30 Line Current Differential System. 1.1.1 CAUTIONS AND WARNINGS Before attempting to install or use the device, review all safety indicators in this document to help prevent injury, equipment damage, or downtime.
  • Page 12: Inspection Procedure

    • GE EnerVista™ CD (includes the EnerVista UR Setup software and manuals in PDF format) • Mounting screws If there is any noticeable physical damage, or any of the contents listed are missing, please contact GE Digital Energy immediately as follows.
  • Page 13: Introduction To The Ur

    1.2UR OVERVIEW 1.2.1 INTRODUCTION TO THE UR The GE Universal Relay (UR) series is a new generation of digital, modular, and multifunction equipment that is easily incorporated into automation systems, at both the station and enterprise levels. 1.2.2 HARDWARE ARCHITECTURE...
  • Page 14 The UR-series devices operate in a cyclic scan fashion. The device reads the inputs into an input status table, solves the logic program (FlexLogic equation), and then sets each output to the appropriate state in an output status table. Any result- ing task execution is priority interrupt-driven. Figure 1–3: UR-SERIES SCAN OPERATION L30 Line Current Differential System GE Multilin...
  • Page 15: Software Architecture

    Employing OOD/OOP in the software architecture of the L30 achieves the same features as the hardware architecture: modularity, scalability, and flexibility. The application software for any UR-series device (for example, feeder protection, transformer protection, distance protection) is constructed by combining objects from the various functional classes.
  • Page 16: Pc Requirements

    Ethernet port of the same type as one of the UR CPU ports or a LAN connection to the UR • Internet access or a DVD drive The following qualified modems have been tested to be compliant with the L30 and the EnerVista UR Setup software: • US Robotics external 56K FaxModem 5686 •...
  • Page 17: Configuring The L30 For Software Access

    To configure the L30 for remote access via the rear Ethernet port, see the Configuring Ethernet Communications sec- tion. • To configure the L30 for local access with a computer through either the front RS232 port or rear Ethernet port, see the Using the Quick Connect Feature section. GE Multilin...
  • Page 18 CONFIGURING SERIAL COMMUNICATIONS A computer with an RS232 port and a serial cable is required. To use the RS485 port at the back of the relay, a GE Multilin F485 converter (or compatible RS232-to-RS485 converter) is required. See the F485 instruction manual for details.
  • Page 19 MODBUS PROTOCOL 21. Click the Read Order Code button to connect to the L30 device and upload the order code. If an communications error occurs, ensure that the three EnerVista UR Setup values entered in the previous steps correspond to the relay setting values.
  • Page 20: Using The Quick Connect Feature

    USING QUICK CONNECT VIA THE REAR ETHERNET PORTS To use the Quick Connect feature to access the L30 from a computer through Ethernet, first assign an IP address to the relay from the front panel keyboard. Press the MENU key until the SETTINGS menu displays.
  • Page 21 Right-click the Local Area Connection icon and select Properties. Select the Internet Protocol (TCP/IP) item from the list, and click the Properties button. Click the “Use the following IP address” box. GE Multilin L30 Line Current Differential System 1-11...
  • Page 22 1.3 ENERVISTA UR SETUP SOFTWARE 1 GETTING STARTED Enter an IP address with the first three numbers the same as the IP address of the L30 relay and the last number dif- ferent (in this example, 1.1.1.2). Enter a subnet mask equal to the one set in the L30 (in this example, 255.0.0.0).
  • Page 23 Ensure that the “Use a proxy server for your LAN” box is not checked. If this computer is used to connect to the Internet, re-enable any proxy server settings after the computer has been discon- nected from the L30 relay. Start the Internet Explorer software.
  • Page 24 Click the Quick Connect button to open the Quick Connect dialog box. Select the Ethernet interface and enter the IP address assigned to the L30, then click the Connect button. The EnerV- ista UR Setup software creates a site named “Quick Connect” with a corresponding device also named “Quick Con- nect”...
  • Page 25: Connecting To The L30 Relay

    The EnerVista UR Setup software has several quick action buttons to provide instant access to several functions that are often performed when using L30 relays. From the online window, users can select the relay to interrogate from a pull-down window, then click the button for the action they want to perform. The following quick action functions are available: •...
  • Page 26: Setting Up Cybersentry And Changing Default Password

    . Be sure to disable this bypass setting after SETTINGS > PRODUCT SETUP > SECURITY > SUPERVISORY commissioning the device. You can change the password for any role either from the front panel or through EnerVista. 1-16 L30 Line Current Differential System GE Multilin...
  • Page 27 It is strongly recommended that the password for the Administrator be changed from the default. Changing the passwords for the other three roles is optional. Figure 1–11: CHANGING THE DEFAULT PASSWORD GE Multilin L30 Line Current Differential System 1-17...
  • Page 28: Mounting And Wiring

    This device (catalog number F485) connects to the computer using a straight-through serial cable. A shielded twisted-pair (20, 22, or 24 AWG) connects the F485 converter to the L30 rear communications port. The converter terminals (+, –, GND) are connected to the L30 communication module (+, –, COM) terminals. See the CPU communica- tions ports section in chapter 3 for details.
  • Page 29: Faceplate Keypad

    To put the relay in the “Programmed” state, press either of the VALUE keys once and then press ENTER. The face- plate Trouble LED turns off and the In Service LED turns on. GE Multilin L30 Line Current Differential System 1-19...
  • Page 30: Relay Passwords

    For more information, see the CyberSentry content in the Security section of the next chapter. 1.5.6 FLEXLOGIC CUSTOMIZATION FlexLogic equation editing is required for setting user-defined logic for customizing the relay operations. See the FlexLogic section in Chapter 5. 1-20 L30 Line Current Differential System GE Multilin...
  • Page 31: Commissioning

    The L30 performs a number of continual self-tests and takes the necessary action in case of any major errors (see the Relay Self-tests section in chapter 7). However, it is recommended that L30 maintenance be scheduled with other system maintenance.
  • Page 32 1.5 USING THE RELAY 1 GETTING STARTED 1-22 L30 Line Current Differential System GE Multilin...
  • Page 33: Overview

    The L30 is intended to provide complete protection for transmission lines of any voltage level. Both three phase and single phase tripping schemes are available. Models of the L30 are available for application on both two and three terminal lines.
  • Page 34 Non-volatile selector switch Virtual outputs (96) Direct inputs (8 per pilot channel) Open pole detector VT fuse failure Disconnect switches Oscillography DNP 3.0 or IEC 60870-5-104 protocol Setting groups (6) Event recorder Stub bus L30 Line Current Differential System GE Multilin...
  • Page 35: Features

    Zero-sequence removal for application on lines with tapped transformers connected in a grounded wye on the line side • GE phaselets approach based on the Discrete Fourier Transform with 64 samples per cycle and transmitting two time- stamped phaselets per cycle •...
  • Page 36: Security

    Clearing fault reports • Changing the date and time • Clearing the breaker arcing current • Clearing the data logger • Clearing the user-programmable pushbutton states The following operations are under setting password supervision: L30 Line Current Differential System GE Multilin...
  • Page 37 When entering a settings or command password via EnerVista or any serial interface, the user must enter the correspond- ing connection password. If the connection is to the back of the L30, the remote password must be used. If the connection is to the RS232 port of the faceplate, the local password applies.
  • Page 38 User Programmable |--------------- LEDs User Programmable |--------------- self test |--------------- Control Pushbuttons User programmable |--------------- Pushbuttons |--------------- Flex states User definable dis- |--------------- plays |--------------- Direct I/O |--------------- Tele-protection |--------------- Installation |------------ System Setup L30 Line Current Differential System GE Multilin...
  • Page 39 Actual Values |------------ Front Panel Labels Designer |------------ Status |------------ Metereing |------------ Transducer I/O |------------ Records |------------ Product Info Maintenance |------------ Modbus Analyzer |------------ Change Front Panel |------------ Update Firmware |------------ Retrieve File GE Multilin L30 Line Current Differential System...
  • Page 40: Ordering

    2.1.4 ORDERING a) OVERVIEW The L30 is available as a 19-inch rack horizontal mount or reduced-size (¾) vertical unit and consists of the following mod- ules: power supply, CPU, CT/VT, contact input and output, transducer input and output, and inter-relay communications.
  • Page 41 2 PRODUCT DESCRIPTION 2.1 INTRODUCTION Table 2–4: L30 ORDER CODES (HORIZONTAL UNITS) * - F - W/X Full Size Horizontal Mount BASE UNIT Base Unit IEEE 1588 and CyberSentry Lvl 1 IEEE 1588 and CyberSentry Lvl 1 and IEC 61850...
  • Page 42 RS422, 2 Channels, 2 Clock Inputs RS422, 2 Channels The order codes for the reduced size vertical mount units are shown below. Table 2–5: L30 ORDER CODES (REDUCED SIZE VERTICAL UNITS) * - F Reduced Size Vertical Mount BASE UNIT...
  • Page 43 RS422, 2 Channels c) ORDER CODES WITH PROCESS BUS MODULES The order codes for the horizontal mount units with the process bus module are shown below. Table 2–6: L30 ORDER CODES (HORIZONTAL UNITS WITH PROCESS BUS) * - F - W/X...
  • Page 44 2.1 INTRODUCTION 2 PRODUCT DESCRIPTION Table 2–6: L30 ORDER CODES (HORIZONTAL UNITS WITH PROCESS BUS) * - F - W/X Full Size Horizontal Mount BASE UNIT Base Unit IEEE 1588 and PRP IEEE 1588, PRP, IEC 61850 IEEE 1588, PRP, and PMU...
  • Page 45 2 PRODUCT DESCRIPTION 2.1 INTRODUCTION The order codes for the reduced size vertical mount units with the process bus module are shown below. Table 2–7: L30 ORDER CODES (REDUCED SIZE VERTICAL UNITS WITH PROCESS BUS) * - F Reduced Size Vertical Mount...
  • Page 46 2.1 INTRODUCTION 2 PRODUCT DESCRIPTION Table 2–7: L30 ORDER CODES (REDUCED SIZE VERTICAL UNITS WITH PROCESS BUS) * - F Reduced Size Vertical Mount POWER SUPPLY 125 / 250 V AC/DC power supply 24 to 48 V (DC only) power supply...
  • Page 47: Replacement Modules

    Replacement modules can be ordered separately. When ordering a replacement CPU module or faceplate, provide the serial number of your existing unit. Not all replacement modules may be applicable to the L30 relay. Only the modules specified in the order codes are available as replacement modules.
  • Page 48 Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, LASER Channel 1 - G.703; Channel 2 - 1300 nm, single-mode LASER G.703, 1 Channel G.703, 2 Channels RS422, 1 Channel RS422, 2 Channels 2-16 L30 Line Current Differential System GE Multilin...
  • Page 49: Inter-Relay Communications

    (DTT) signal to all of the other L30 relays on the protected line. If a slave L30 relay issues a trip from one of its backup functions, it can send a transfer trip signal to its master and other slave relays if such option is designated.
  • Page 50: Channel Monitor

    2.2.2 CHANNEL MONITOR The L30 has logic to detect that the communications channel is deteriorating or has failed completely. This can provide an alarm indication and disable the current differential protection. Note that a failure of the communications from the master to a slave does not prevent the master from performing the current differential algorithm;...
  • Page 51: Loopback Test

    The L30 includes provision for sending and receiving a single-pole direct transfer trip (DTT) signal from current differential protection between the L30 relays at the line terminals using the pilot communications channel. The user may also initiate an additional eight pilot signals with an L30 communications channel to create trip, block, or signaling logic. A FlexLogic operand, an external contact closure, or a signal over the LAN communication channels can be assigned for that logic.
  • Page 52: Protection And Control Functions

    Current differential protection: The current differential algorithms used in the L30 Line Current Differential System are based on the Fourier transform phaselet approach and an adaptive statistical restraint. The L30 uses per-phase differential at 64 kbps with two phaselets per cycle. A detailed description of the current differential algorithms is found in chapter 8.
  • Page 53: Other Functions

    PFLL Status Frequency Deviation Phase and Frequency Master Locked Loop (PFLL) Clock Phase Deviation PHASELETS TO REMOTE Communications Remote Relay PHASELETS FROM REMOTE Interface Direct Transfer Trip 831732A3.CDR Figure 2–4: L30 BLOCK DIAGRAM GE Multilin L30 Line Current Differential System 2-21...
  • Page 54: Protection Elements

    Operate time: <20 ms at 3 × pickup at 60 Hz range of 0.1<V<0.9 VT Nominal in a Timer accuracy: ±3% of operate time or ±1/4 cycle fixed linear relationship (whichever is greater) 2-22 L30 Line Current Differential System GE Multilin...
  • Page 55 Time Dial = 0 to 600.00 in steps of 0.01 above 2 × CT rating: ±2.5% of reading Curve timing accuracy at <0.90 x pickup: ±3.5% of operate time or ±1/2 cycle (whichever is greater) from pickup to operate GE Multilin L30 Line Current Differential System 2-23...
  • Page 56: User-Programmable Elements

    LEDs on Test sequence 2: all LEDs off, one LED at a time on for 1 s Test sequence 3: all LEDs on, one LED at a time off for 1 s 2-24 L30 Line Current Differential System GE Multilin...
  • Page 57: Monitoring

    Relay accuracy: ±1.5% (V > 10 V, I > 0.1 pu) Worst-case accuracy: user data %error user data %error user data Line%error METHOD see chapter 8 %error RELAY ACCURACY + (1.5%) %error GE Multilin L30 Line Current Differential System 2-25...
  • Page 58: Metering

    Current withstand: 20 ms at 250 times rated 1 sec. at 100 times rated continuous 4xInom Short circuit rating:150000 RMS sym- metrical amperes, 250 V maximum (pri- mary current to external CT) 2-26 L30 Line Current Differential System GE Multilin...
  • Page 59: Power Supply

    Make and carry for 0.2 s: 30 A as per ANSI C37.90 Carry continuous: Break (DC inductive, L/R = 40 ms): VOLTAGE CURRENT 24 V 48 V 0.5 A 125 V 0.3 A 250 V 0.2 A GE Multilin L30 Line Current Differential System 2-27...
  • Page 60 Note: values for 24 V and 48 V are the same due to a required 95% voltage drop across the load impedance. Operate time: < 0.6 ms Internal Limiting Resistor: 100 Ω, 2 W 2-28 L30 Line Current Differential System GE Multilin...
  • Page 61: Communication Protocols

    –30 dBm 29 dB Singlemode 1550 nm Laser, +5 dBm –30 dBm 35 dB Singlemode These power budgets are calculated from the manu- facturer’s worst-case transmitter power and worst NOTE case receiver sensitivity. GE Multilin L30 Line Current Differential System 2-29...
  • Page 62: Environmental

    – Overvoltage category: 20°C Ingress protection: IP20 front, IP10 back HUMIDITY Noise: 0 dB Humidity: operating up to 95% (non-condensing) at 55°C (as per IEC60068-2-30 variant 1, 6 days). 2-30 L30 Line Current Differential System GE Multilin...
  • Page 63: Type Tests

    Safety IEC 60255-27 Insulation: class 1, Pollution degree: 2, Over voltage cat II 2.4.12 PRODUCTION TESTS THERMAL Products go through an environmental test based upon an Accepted Quality Level (AQL) sampling process. GE Multilin L30 Line Current Differential System 2-31...
  • Page 64: Approvals

    To avoid deterioration of electrolytic capacitors, power up units that are stored in a de-energized state once per year, for one hour continuously. 2-32 L30 Line Current Differential System GE Multilin...
  • Page 65: Panel Cutout

    HORIZONTAL UNITS The L30 Line Current Differential System is available as a 19-inch rack horizontal mount unit with a removable faceplate. The faceplate can be specified as either standard or enhanced at the time of ordering. The enhanced faceplate contains additional user-programmable pushbuttons and LED indicators.
  • Page 66 VERTICAL UNITS The L30 Line Current Differential System is available as a reduced size (¾) vertical mount unit, with a removable faceplate. The faceplate can be specified as either standard or enhanced at the time of ordering. The enhanced faceplate contains additional user-programmable pushbuttons and LED indicators.
  • Page 67 3 HARDWARE 3.1 DESCRIPTION Figure 3–4: L30 VERTICAL DIMENSIONS (ENHANCED PANEL) GE Multilin L30 Line Current Differential System...
  • Page 68 3.1 DESCRIPTION 3 HARDWARE Figure 3–5: L30 VERTICAL MOUNTING AND DIMENSIONS (STANDARD PANEL) For side mounting L30 devices with the enhanced front panel, see the following documents available on the UR DVD and the GE Digital Energy website: • GEK-113180: UR-Series UR-V Side-Mounting Front Panel Assembly Instructions •...
  • Page 69 3 HARDWARE 3.1 DESCRIPTION Figure 3–6: L30 VERTICAL SIDE MOUNTING INSTALLATION (STANDARD PANEL) GE Multilin L30 Line Current Differential System...
  • Page 70 3.1 DESCRIPTION 3 HARDWARE Figure 3–7: L30 VERTICAL SIDE MOUNTING REAR DIMENSIONS (STANDARD PANEL) L30 Line Current Differential System GE Multilin...
  • Page 71: Rear Terminal Layout

    (nearest to CPU module) which is indicated by an arrow marker on the terminal block. See the following figure for an example of rear terminal assignments. Figure 3–9: EXAMPLE OF MODULES IN F AND H SLOTS GE Multilin L30 Line Current Differential System...
  • Page 72: Typical Wiring

    3.2 WIRING 3 HARDWARE 3.2WIRING 3.2.1 TYPICAL WIRING Figure 3–10: TYPICAL WIRING DIAGRAM (T MODULE SHOWN FOR CPU) L30 Line Current Differential System GE Multilin...
  • Page 73: Dielectric Strength

    (see the Self-test errors section in chapter 7) or control power is lost, the relay is de-energize. For high reliability systems, the L30 has a redundant option in which two L30 power supplies are placed in parallel on the bus.
  • Page 74: Ct And Vt Modules

    CT connections for both ABC and ACB phase rotations are identical as shown in the Typical wiring diagram. The exact placement of a zero-sequence core balance CT to detect ground fault current is shown as follows. Twisted-pair cabling on the zero-sequence CT is recommended. 3-10 L30 Line Current Differential System GE Multilin...
  • Page 75 NOTE Current inputs Voltage inputs 8F, 8G, 8L, and 8M modules (4 CTs and 4 VTs) Current inputs 8H, 8J, 8N, and 8R modules (8 CTs) 842766A3.CDR Figure 3–13: CT/VT MODULE WIRING GE Multilin L30 Line Current Differential System 3-11...
  • Page 76: Process Bus Modules

    3.2.5 PROCESS BUS MODULES The L30 can be ordered with a process bus interface module. This module is designed to interface with the GE Multilin HardFiber system, allowing bidirectional IEC 61850 fiber optic communications with up to eight HardFiber merging units, known as Bricks.
  • Page 77 Logic operand driving the contact output should be given a reset delay of 10 ms to prevent damage of the output contact (in situations when the element initiating the contact output is bouncing, at val- ues in the region of the pickup value). GE Multilin L30 Line Current Differential System 3-13...
  • Page 78 ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs 3-14 L30 Line Current Differential System GE Multilin...
  • Page 79 ~5a, ~5c 2 Inputs 2 Outputs Solid-State Solid-State ~6a, ~6c 2 Inputs 2 Outputs Not Used Not Used ~7a, ~7c 2 Inputs 2 Outputs Solid-State Solid-State ~8a, ~8c 2 Inputs Not Used GE Multilin L30 Line Current Differential System 3-15...
  • Page 80 3.2 WIRING 3 HARDWARE Figure 3–15: CONTACT INPUT AND OUTPUT MODULE WIRING (1 of 2) 3-16 L30 Line Current Differential System GE Multilin...
  • Page 81 3 HARDWARE 3.2 WIRING Figure 3–16: CONTACT INPUT AND OUTPUT MODULE WIRING (2 of 2) For proper functionality, observe the polarity shown in the figures for all contact input and output con- nections. GE Multilin L30 Line Current Differential System 3-17...
  • Page 82 Wherever a tilde “~” symbol appears, substitute with the slot position of the module. NOTE There is no provision in the relay to detect a DC ground fault on 48 V DC control power external output. We recommend using an external DC supply. 3-18 L30 Line Current Differential System GE Multilin...
  • Page 83 = OFF CONTACT INPUT 1 AUTO-BURNISH = OFF CONTACT INPUT 2 AUTO-BURNISH = ON CONTACT INPUT 1 AUTO-BURNISH = ON CONTACT INPUT 2 AUTO-BURNISH = ON 842751A1.CDR Figure 3–19: AUTO-BURNISH DIP SWITCHES GE Multilin L30 Line Current Differential System 3-19...
  • Page 84 3.2 WIRING 3 HARDWARE The auto-burnish circuitry has an internal fuse for safety purposes. During regular maintenance, check the auto- burnish functionality using an oscilloscope. NOTE 3-20 L30 Line Current Differential System GE Multilin...
  • Page 85: Transducer Inputs And Outputs

    (5A, 5C, 5D, 5E, and 5F) and channel arrangements that can be ordered for the relay. Wherever a tilde “~” symbol appears, substitute with the slot position of the module. NOTE Figure 3–20: TRANSDUCER INPUT/OUTPUT MODULE WIRING The following figure show how to connect RTDs. GE Multilin L30 Line Current Differential System 3-21...
  • Page 86 3.2 WIRING 3 HARDWARE Figure 3–21: RTD CONNECTIONS 3-22 L30 Line Current Differential System GE Multilin...
  • Page 87: Rs232 Faceplate Port

    3.2.8 RS232 FACEPLATE PORT A 9-pin RS232C serial port is located on the L30 faceplate for programming with a computer. All that is required to use this interface is a computer running the EnerVista UR Setup software provided with the relay. Cabling for the RS232 port is shown in the following figure for both 9-pin and 25-pin connectors.
  • Page 88 This common voltage is implied to be a power supply common. Some systems allow the shield (drain wire) to be used as common wire and to connect directly to the L30 COM terminal (#3); others function cor- rectly only if the common wire is connected to the L30 COM terminal, but insulated from the shield.
  • Page 89: Irig-B

    IRIG-B is a standard time code format that allows stamping of events to be synchronized among connected devices. The IRIG-B code allows time accuracies of up to 100 ns. Using the IRIG-B input, the L30 operates an internal oscillator with 1 µs resolution and accuracy.
  • Page 90 20 to 25 degree error in the synchrophasor angle measurement. The IEEE 1588 Precision Time NOTE Protocol can also be used to achieve accurate time synchronization for synchrophasor calculation. 3-26 L30 Line Current Differential System GE Multilin...
  • Page 91: Description

    RS422, 1 channel RS422, 2 channels, 2 clock inputs RS422, 2 channels All of the fiber modules use ST type connectors. For two-terminal applications, each L30 relay requires at least one com- munications channel. GE Multilin L30 Line Current Differential System...
  • Page 92: Fiber: Led And Eled Transmitters

    3.3.3 FIBER-LASER TRANSMITTERS The following figure shows the configuration for the 72, 73, 7D, and 7K fiber-laser module. Figure 3–27: LASER FIBER MODULES Observing any fiber transmitter output can injure the eye. 3-28 L30 Line Current Differential System GE Multilin...
  • Page 93 3 HARDWARE 3.3 PILOT CHANNEL COMMUNICATIONS When using a laser Interface, attenuators can be necessary to ensure that you do not exceed the maximum optical input power to the receiver. GE Multilin L30 Line Current Differential System 3-29...
  • Page 94: G.703 Interface

    Remove the module cover screw. Remove the top cover by sliding it towards the rear and then lift it upwards. Set the timing selection switches (channel 1, channel 2) to the desired timing modes. 3-30 L30 Line Current Differential System GE Multilin...
  • Page 95 Loop Timing Mode: The system clock is derived from the received line signal. Therefore, the G.703 timing selection should be in loop timing mode for connections to higher order systems. For connection to a higher order system (UR- GE Multilin L30 Line Current Differential System 3-31...
  • Page 96 G.703 line side of the interface while the other lies on the differential Manchester side of the interface. DMR = Differential Manchester Receiver DMX = Differential Manchester Transmitter G7X = G.703 Transmitter G7R = G.703 Receiver 842775A1.CDR Figure 3–32: G.703 DUAL LOOPBACK MODE 3-32 L30 Line Current Differential System GE Multilin...
  • Page 97: Rs422 Interface

    The send timing outputs from the multiplexer (data module 1), connects to the clock inputs of the UR–RS422 interface in the usual fashion. In addition, GE Multilin L30 Line Current Differential System 3-33...
  • Page 98 Figure 3–35: TIMING CONFIGURATION FOR RS422 TWO-CHANNEL, THREE-TERMINAL APPLICATION Data module 1 provides timing to the L30 RS422 interface via the ST(A) and ST(B) outputs. Data module 1 also provides timing to data module 2 TT(A) and TT(B) inputs via the ST(A) and AT(B) outputs. The data module pin numbers have been omitted in the figure above since they vary by manufacturer.
  • Page 99: Two-Channel Two-Clock Rs422 Interface

    74 modules are used in two-terminal with a redundant channel or three-terminal configurations where channel 1 is employed via the RS422 interface (possibly with a multiplexer) and channel 2 via direct fiber. GE Multilin L30 Line Current Differential System 3-35...
  • Page 100: G.703 And Fiber Interface

    The frame is 256 bits and is repeated at a frame rate of 8000 Hz, with a resultant bit rate of 2048 kbps. The specifications for the module are as follows:. 3-36 L30 Line Current Differential System GE Multilin...
  • Page 101 5.60. For customers using firmware release 5.60 and higher, the module can be identified with "Rev D" printed on the module and is to be used on all ends of L30 communi- cation for two and three terminal applications.
  • Page 102 Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously. When the clips have locked into position, the module is fully inserted. Figure 3–40: IEEE C37.94 TIMING SELECTION SWITCH SETTING 3-38 L30 Line Current Differential System GE Multilin...
  • Page 103 Solid yellow — FPGA is receiving a "yellow bit" and remains yellow for each "yellow bit" • Solid red — FPGA is not receiving a valid packet or the packet received is invalid GE Multilin L30 Line Current Differential System 3-39...
  • Page 104: C37.94Sm Interface

    5.60. For customers using firmware release 5.60 and higher, the module can be identified with "Rev D" printed on the module and is to be used on all ends of L30 communi- cation for two and three terminal applications.
  • Page 105 Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously. When the clips have locked into position, the module is fully inserted. GE Multilin L30 Line Current Differential System 3-41...
  • Page 106 Modules shipped since January 2012 have status LEDs that indicate the status of the DIP switches, as shown in the follow- ing figure. Figure 3–43: STATUS LEDS The clock configuration LED status is as follows: • Flashing green — loop timing mode while receiving a valid data packet 3-42 L30 Line Current Differential System GE Multilin...
  • Page 107 Solid yellow — FPGA is receiving a "yellow bit" and remains yellow for each "yellow bit" • Solid red — FPGA is not receiving a valid packet or the packet received is invalid GE Multilin L30 Line Current Differential System 3-43...
  • Page 108 3.3 PILOT CHANNEL COMMUNICATIONS 3 HARDWARE 3-44 L30 Line Current Differential System GE Multilin...
  • Page 109: Introduction

    In online mode, you can communicate with the device in real-time. The EnerVista UR Setup software is provided with every L30 relay and runs on Microsoft Windows XP, 7, and Server 2008. This chapter provides a summary of the basic EnerVista UR Setup software interface features. The EnerVista UR Setup Help File provides details for getting started and using the EnerVista UR Setup software interface.
  • Page 110 Site List window are automatically sent to the online communicating device. g) FIRMWARE UPGRADES The firmware of a L30 device can be upgraded, locally or remotely, via the EnerVista UR Setup software. The correspond- ing instructions are provided by the EnerVista UR Setup Help file under the topic “Upgrading Firmware”.
  • Page 111: Enervista Ur Setup Main Window

    Device data view windows, with common tool bar Settings file data view windows, with common tool bar Workspace area with data view tabs Status bar 10. Quick action hot links 842786A2.CDR Figure 4–1: ENERVISTA UR SETUP SOFTWARE MAIN WINDOW GE Multilin L30 Line Current Differential System...
  • Page 112: Settings Templates

    Select the Template Mode > Edit Template option to place the device in template editing mode. Enter the template password then click OK. Open the relevant settings windows that contain settings to be specified as viewable. L30 Line Current Differential System GE Multilin...
  • Page 113 The following procedure describes how to add password protection to a settings file template. Select a settings file from the offline window on the left of the EnerVista UR Setup main screen. Selecting the Template Mode > Password Protect Template option. GE Multilin L30 Line Current Differential System...
  • Page 114 Template Mode > View In Template Mode command. The template specifies that only the Pickup Curve Phase time overcurrent settings window without template applied. settings be available. 842858A1.CDR Figure 4–4: APPLYING TEMPLATES VIA THE VIEW IN TEMPLATE MODE COMMAND L30 Line Current Differential System GE Multilin...
  • Page 115 Select an installed device or settings file from the tree menu on the left of the EnerVista UR Setup main screen. Select the Template Mode > Remove Settings Template option. Enter the template password and click OK to continue. GE Multilin L30 Line Current Differential System...
  • Page 116: Securing And Locking Flexlogic Equations

    Click on Save to save and apply changes to the settings template. Select the Template Mode > View In Template Mode option to view the template. Apply a password to the template then click OK to secure the FlexLogic equation. L30 Line Current Differential System GE Multilin...
  • Page 117 FlexLogic entries in a settings file have been secured, use the following procedure to lock the settings file to a specific serial number. Select the settings file in the offline window. Right-click on the file and select the Edit Settings File Properties item. GE Multilin L30 Line Current Differential System...
  • Page 118: Settings File Traceability

    When a settings file is transferred to a L30 device, the date, time, and serial number of the L30 are sent back to EnerVista UR Setup and added to the settings file on the local PC. This infor- mation can be compared with the L30 actual values at any later date to determine if security has been compromised.
  • Page 119 4.2 EXTENDED ENERVISTA UR SETUP FEATURES The transfer date of a setting file written to a L30 is logged in the relay and can be viewed via EnerVista UR Setup or the front panel display. Likewise, the transfer date of a setting file saved to a local PC is logged in EnerVista UR Setup.
  • Page 120 ONLINE DEVICE TRACEABILITY INFORMATION The L30 serial number and file transfer date are available for an online device through the actual values. Select the Actual Values > Product Info > Model Information menu item within the EnerVista UR Setup online window as shown in the example below.
  • Page 121: Faceplate

    The following figure shows the horizontal arrange- ment of the faceplate panels. Figure 4–16: UR-SERIES STANDARD HORIZONTAL FACEPLATE PANELS GE Multilin L30 Line Current Differential System 4-13...
  • Page 122: Led Indicators

    The status indicators in the first column are described below. • IN SERVICE: This LED indicates that control power is applied, all monitored inputs, outputs, and internal systems are OK, and that the device has been programmed. 4-14 L30 Line Current Differential System GE Multilin...
  • Page 123 Support for applying a customized label beside every LED is provided. Default labels are shipped in the label pack- age of every L30, together with custom templates. The default labels can be replaced by user-printed labels. User customization of LED operation is of maximum benefit in installations where languages other than English are used to communicate with operators.
  • Page 124 User customization of LED operation is of maximum benefit in installations where languages other than English are used to communicate with operators. Refer to the User-programmable LEDs section in chapter 5 for the settings used to program the operation of the LEDs on these panels. 4-16 L30 Line Current Differential System GE Multilin...
  • Page 125: Custom Labeling Of Leds

    EnerVista UR Setup software is installed and operational • The L30 settings have been saved to a settings file • The L30 front panel label cutout sheet (GE Multilin part number 1006-0047) has been downloaded from http://www.gedigitalenergy.com/products/support/ur/URLEDenhanced.doc and printed •...
  • Page 126 Enter the text to appear next to each LED and above each user-programmable pushbuttons in the fields provided. Feed the L30 front panel label cutout sheet into a printer and press the Print button in the front panel report window.
  • Page 127 4.3 FACEPLATE INTERFACE Bend the tab at the center of the tool tail as shown below. The following procedure describes how to remove the LED labels from the L30 enhanced front panel and insert the custom labels. Use the knife to lift the LED label and slide the label tool underneath. Make sure the bent tabs are pointing away from the relay.
  • Page 128 Slide the new LED label inside the pocket until the text is properly aligned with the LEDs, as shown below. The following procedure describes how to remove the user-programmable pushbutton labels from the L30 enhanced front panel and insert the custom labels.
  • Page 129 Slide the label tool under the user-programmable pushbutton label until the tabs snap out as shown below. This attaches the label tool to the user-programmable pushbutton label. Remove the tool and attached user-programmable pushbutton label as shown below. GE Multilin L30 Line Current Differential System 4-21...
  • Page 130: Display

    INTRODUCTION The L30 can interface with associated circuit breakers. In many cases the application monitors the state of the breaker, that can be presented on faceplate LEDs, along with a breaker trouble indication. Breaker operations can be manually initiated from faceplate keypad or automatically initiated from a FlexLogic operand.
  • Page 131: Menus

    Press the MENU key to select a header display page (top-level menu). The header title appears momentarily followed by a header display page menu item. Each press of the MENU key advances through the following main heading pages: • Actual values • Settings GE Multilin L30 Line Current Differential System 4-23...
  • Page 132 Pressing the MESSAGE DOWN key displays the second setting sub-header associ-  PROPERTIES ated with the Product Setup header.  Press the MESSAGE RIGHT key once more to display the first setting for Display FLASH MESSAGE Properties. TIME: 1.0 s 4-24 L30 Line Current Differential System GE Multilin...
  • Page 133: Changing Settings

    ENTERING ALPHANUMERIC TEXT Text settings have data values which are fixed in length, but user-defined in character. They can be upper case letters, lower case letters, numerals, and a selection of special characters. GE Multilin L30 Line Current Differential System 4-25...
  • Page 134 The information in this section refers to password security. For information on how to set or change CyberSentry pass- words, see the Settings > Product Setup > Security > CyberSentry section in the next chapter. 4-26 L30 Line Current Differential System GE Multilin...
  • Page 135 By default, when an incorrect Command or Setting password has been entered via the faceplate interface three times within three minutes, the FlexLogic™ operand is set to “On” and the L30 does not allow settings or LOCAL ACCESS DENIED command level access via the faceplate interface for the next five minutes.
  • Page 136 4 HUMAN INTERFACES By default, when an incorrect Command or Setting password has been entered via any external communications interface three times within three minutes, the FlexLogic™ operand is set to and the L30 does not REMOTE ACCESS DENIED “ ”...
  • Page 137: Settings Menu

    See page 5-84.  SYSTEM SETUP   POWER SYSTEM See page 5-85.   SIGNAL SOURCES See page 5-86.   87L POWER SYSTEM See page 5-89.   BREAKERS See page 5-95.  GE Multilin L30 Line Current Differential System...
  • Page 138  DIGITAL ELEMENTS See page 5-218.   DIGITAL COUNTERS See page 5-221.   MONITORING See page 5-223.  ELEMENTS  SETTINGS  CONTACT INPUTS See page 5-234.  INPUTS / OUTPUTS  L30 Line Current Differential System GE Multilin...
  • Page 139 See page 5-255.  FORCE CONTACT See page 5-256.  INPUTS  FORCE CONTACT See page 5-257.  OUTPUTS  CHANNEL TESTS See page 5-258.   PMU See page 5-258.  TEST VALUES GE Multilin L30 Line Current Differential System...
  • Page 140: Introduction To Elements

    In more complex elements, a set of settings may be provided to define the range of the measured parameters which will cause the element to pickup. L30 Line Current Differential System GE Multilin...
  • Page 141: Introduction To Ac Sources

    Sources, in the context of L30 series relays, refer to the logical grouping of current and voltage signals such that one source contains all the signals required to measure the load or fault in a particular power apparatus. A given source may contain all or some of the following signals: three-phase currents, single-phase ground current, three-phase voltages and an auxiliary voltages from a single-phase VT for checking for synchronism.
  • Page 142 CTs through which any portion of the current for the element being protected could flow. Auxiliary CTs are required to perform ratio matching if the ratios of the primary CTs to be summed are not identical. In the L30 relay, provisions have been included for all the current signals to be brought to the device where grouping, CT ratio correction, and summation are applied internally via configuration settings.
  • Page 143 Upon startup, the CPU configures the settings required to characterize the current and voltage inputs, and will display them in the appropriate section in the sequence of the banks (as described above) as follows for a maximum configuration: F1, F5, L1, L5, S1, and S5. GE Multilin L30 Line Current Differential System...
  • Page 144: Security

    To reset the unit after a lost password: Email GE customer service at multilin.tech@ge.com with the serial number and using a recognizable corporate email account. Customer service provides a code to reset the relay to the factory defaults.
  • Page 145 When entering a settings or command password via EnerVista or any serial interface, the user must enter the correspond- ing connection password. If the connection is to the back of the L30, the remote password must be used. If the connection is to the RS232 port of the faceplate, the local password must be used.
  • Page 146 When lockout occurs, the LOCAL ACCESS DENIED FlexLogic operands are set to “On”. These operands are returned to the “Off” state upon REMOTE ACCESS DENIED expiration of the lockout. 5-10 L30 Line Current Differential System GE Multilin...
  • Page 147 INVALID ATTEMPTS BEFORE LOCKOUT The L30 provides a means to raise an alarm upon failed password entry. Should password verification fail while accessing a password-protected level of the relay (either settings or commands), the FlexLogic operand is UNAUTHORIZED ACCESS asserted.
  • Page 148 It is disabled by default to allow the administrator direct access to the EnerVista software immediately after installation. When security is disabled, all users have administrator access. GE recommends enabling the EnerVista security before placing the device in service.
  • Page 149 Enter a username in the User field. The username must be 4 to 20 characters in length. Select the user access rights by enabling the check box of one or more of the fields. GE Multilin L30 Line Current Differential System 5-13...
  • Page 150 Deletes the user account when exiting the user management window Actual Values Allows the user to read actual values Settings Allows the user to read setting values Commands Allows the user to execute commands 5-14 L30 Line Current Differential System GE Multilin...
  • Page 151  screen. SETTINGS PRODUCT SETUP SECURITY SUPERVISORY Note that other protocols (DNP, 101, 103, 104, EGD) are not encrypted, and they are good communications options for SCADA systems when CyberSentry is enabled. GE Multilin L30 Line Current Differential System 5-15...
  • Page 152 5.2 PRODUCT SETUP 5 SETTINGS CYBERSENTRY SETTINGS THROUGH ENERVISTA CyberSentry security settings are configured under Device > Settings > Product Setup > Security. Figure 5–2: CYBERSENTRY SECURITY PANEL 5-16 L30 Line Current Differential System GE Multilin...
  • Page 153 Authentication method used by RADIUS EAP-TTLS EAP-TTLS EAP-TTLS Administrator Authentication server. Currently fixed to EAP-TTLS. Method Timeout Timeout in seconds between re- 9999 Administrator transmission requests Retries Number of retries before giving up 9999 Administrator GE Multilin L30 Line Current Differential System 5-17...
  • Page 154 Change Text The specified role password-protected. All RADIUS users are following following Me1# and Administrator, password-protected. password password except for section for section for Supervisor, where requirements requireme it is only itself 5-18 L30 Line Current Differential System GE Multilin...
  • Page 155 This role can also be disabled, but only through a Supervisor authentication. When this role is disabled its permissions are assigned to the Administrator role. GE Multilin L30 Line Current Differential System 5-19...
  • Page 156 LOAD FACTORY DEFAULTS: This setting is used to reset all the settings, communication and security passwords. An Administrator role is used to change this setting and a Supervisor role (if not disabled) approves it. 5-20 L30 Line Current Differential System GE Multilin...
  • Page 157 Administrator if the Supervisor role is disabled. The Supervisor role enables this setting for the relay to start accepting setting changes or command changes or firmware upgrade. After all the setting changes are applied or com- mands executed, the Supervisor disables to lock setting changes. GE Multilin L30 Line Current Differential System 5-21...
  • Page 158 RADIUS server. Once both the RADIUS server and the parameters for connecting UR to the server have been configured, you can choose server authentication on the login screen of EnerVista. 5-22 L30 Line Current Differential System GE Multilin...
  • Page 159 Username — 255 chars maximum, but in the security log it is truncated to 20 characters IP address — Device IP address Role — 16 bit unsigned, of type format F617 ENUMERATION ROLE None Administrator Supervisor Engineer Operator Factory GE Multilin L30 Line Current Differential System 5-23...
  • Page 160: Display Properties

    DEFAULT MESSAGE TIMEOUT: If the keypad is inactive for a period of time, the relay automatically reverts to a default message. The inactivity time is modified via this setting to ensure messages remain on the screen long enough during programming or reading of actual values. 5-24 L30 Line Current Differential System GE Multilin...
  • Page 161 Some customers prefer very low currents to display as zero, while others prefer the current be displayed even when the value reflects noise rather than the actual signal. The L30 applies a cut- off value to the magnitudes and angles of the measured currents.
  • Page 162: Clear Relay Records

    Selected records can be cleared from user-programmable conditions with FlexLogic operands. Assigning user-programma- ble pushbuttons to clear specific records are typical applications for these commands. Since the L30 responds to rising edges of the configured FlexLogic operands, they must be asserted for at least 50 ms to take effect.
  • Page 163: Communications

    ETHERNET NETWORK TOPOLOGY The L30 has three Ethernet ports. Each Ethernet port must belong to a different network or subnetwork. Configure the IP address and subnet to ensure that each port meets this requirement. Two subnets are different when the bitwise AND oper- ation performed between their respective IP address and mask produces a different result.
  • Page 164 EnerVista, and access to the public network shared on the same LAN. No redundancy is provided. Figure 5–4: NETWORK CONFIGURATION FOR SINGLE LAN Public Network SCADA EnerVista Software LAN1 ML3000 IP1/ MAC1 859708A2.vsd 5-28 L30 Line Current Differential System GE Multilin...
  • Page 165 LAN3, to which port 3 (P3) is connected. There is no redundancy. Figure 5–6: MULTIPLE LANS, NO REDUNDANCY Public Network SCADA EnerVista Software LAN1 LAN2 LAN3 ML3000 ML3000 ML3000 IP1/ IP2/ IP3/ MAC2 MAC3 MAC1 859710A2.vsd GE Multilin L30 Line Current Differential System 5-29...
  • Page 166 Port 3 is in standby mode and does not actively communicate on the Ethernet network but monitors its link to the Mul- tilink switch. If port 2 detects a problem with the link, communications is switched to Port 3. Port 3 is, in effect, acting as 5-30 L30 Line Current Differential System GE Multilin...
  • Page 167 Under normal circumstances both frames reach the destination and one of them is sent up the OSI stack to the destination application, while the second one is discarded. If an error occurs in one of the networks and GE Multilin L30 Line Current Differential System 5-31...
  • Page 168 The default route is used as the last choice when no other route towards a given destination is found. Range: Standard IPV4 unicast address format  IPV4 DEFAULT ROUTE GATEWAY ADDRESS  127.0.0.1 5-32 L30 Line Current Differential System GE Multilin...
  • Page 169 (RtGwy & Prt1Mask) == (Prt1IP & Prt1Mask) || (RtGwy & Prt2Mask) == (Prt2IP & Prt2Mask) || (RtGwy & Prt3Mask) == (Prt3IP & Prt3Mask) where & is the bitwise-AND operator == is the equality operator || is the logical OR operator GE Multilin L30 Line Current Differential System 5-33...
  • Page 170 PRT2 SUBNET IP MASK = 255.255.255.0 IPV4 DEFAULT ROUTE: GATEWAY ADDRESS = 10.1.1.1 STATIC NETWORK ROUTE 1: RT1 DESTINATION = 10.1.3.0/24; RT1 NET MASK = 255.255.255.0; and RT1 GATE- WAY = 10.1.2.1 5-34 L30 Line Current Differential System GE Multilin...
  • Page 171 This allows the EnerVista UR Setup software to be used on the port. The UR operates as a Modbus slave device only. When using Modbus protocol on the RS232 port, the L30 responds regardless of the pro- MODBUS SLAVE ADDRESS grammed.
  • Page 172 DNP POWER DEFAULT MESSAGE DEADBAND: 30000 Range: 0 to 100000000 in steps of 1 DNP ENERGY DEFAULT MESSAGE DEADBAND: 30000 Range: 0 to 100000000 in steps of 1 DNP PF DEFAULT MESSAGE DEADBAND: 30000 5-36 L30 Line Current Differential System GE Multilin...
  • Page 173 TIMEOUT: 120 s The L30 supports the Distributed Network Protocol (DNP) version 3.0. The L30 can be used as a DNP slave device con- nected to multiple DNP masters (usually an RTU or a SCADA master station). Since the L30 maintains two sets of DNP data change buffers and connection information, two DNP masters can actively communicate with the L30 at one time.
  • Page 174 DNP analog input points that are voltages will be returned with values 1000 times smaller (for example, a value of 72000 V on the L30 will be returned as 72). These settings are useful when analog input values must be adjusted to fit within cer- tain ranges in DNP masters.
  • Page 175 (for circuit breakers) or raise/lower (for tap changers) using a single control point. That is, the DNP master can operate a single point for both trip and close, or raise and lower, operations. The L30 can be configured to sup- port paired control points, with each paired control point operating two virtual inputs.
  • Page 176 60870-5-104 point lists must be in one continuous block, any points assigned after the first “Off” point are ignored. NOTE Changes to the DNP / IEC 60870-5-104 point lists will not take effect until the L30 is restarted. NOTE k) IEC 61850 PROTOCOL ...
  • Page 177 The L30 supports the Manufacturing Message Specification (MMS) protocol as specified by IEC 61850. MMS is supported over two protocol stacks: TCP/IP over Ethernet. The L30 operates as an IEC 61850 server. The Remote inputs and outputs section in this chapter describe the peer-to-peer GSSE/GOOSE message scheme.
  • Page 178 DESTINATION MAC address; the least significant bit of the first byte must be set. In L30 releases previous to 5.0x, the destination Ethernet MAC address was determined automatically by taking the sending MAC address (that is, the unique, local MAC address of the L30) and setting the multicast bit.
  • Page 179 The L30 has the ability of detecting if a data item in one of the GOOSE datasets is erroneously oscillating. This can be caused by events such as errors in logic programming, inputs improperly being asserted and de-asserted, or failed station components.
  • Page 180 Configure the transmission dataset. Configure the GOOSE service settings. Configure the data. The general steps required for reception configuration are: Configure the reception dataset. Configure the GOOSE service settings. Configure the data. 5-44 L30 Line Current Differential System GE Multilin...
  • Page 181 MMXU1 HZ DEADBAND change greater than 45 mHz, from the previous MMXU1.MX.mag.f value, in the source frequency. The L30 must be rebooted (control power removed and re-applied) before these settings take effect. The following procedure illustrates the reception configuration. Configure the reception dataset by making the following changes in the ...
  • Page 182 IEC61850 GOOSE ANALOG INPUT 1 UNITS The GOOSE analog input 1 can now be used as a FlexAnalog value in a FlexElement or in other settings. The L30 must be rebooted (control power removed and re-applied) before these settings take effect.
  • Page 183 DNA and UserSt bit pairs that are included in GSSE messages. To set up a L30 to receive a configurable GOOSE dataset that contains two IEC 61850 single point status indications, the following dataset items can be selected (for example, for configurable GOOSE dataset 1): “GGIO3.ST.Ind1.stVal” and “GGIO3.ST.Ind2.stVal”.
  • Page 184 CPU resources. When server scanning is disabled, there is no updating of the IEC 61850 logical node status values in the L30. Clients are still able to connect to the server (L30 relay), but most data values are not updated. This set- ting does not affect GOOSE/GSSE operation.
  • Page 185 (_) character, and the first character in the prefix must be a letter. This conforms to the IEC 61850 standard. Changes to the logical node prefixes will not take effect until the L30 is restarted. The main menu for the IEC 61850 MMXU deadbands is shown below.
  • Page 186 The GGIO2 control configuration settings are used to set the control model for each input. The available choices are “0” (status only), “1” (direct control), and “2” (SBO with normal security). The GGIO2 control points are used to control the L30 virtual inputs.
  • Page 187 GGIO1 (binary status values). The settings allow the selection of FlexInteger values for each GGIO5 integer value point. It is intended that clients use GGIO5 to access generic integer values from the L30. Additional settings are provided to allow the selection of the number of integer values available in GGIO5 (1 to 16), and to assign FlexInteger values to the GGIO5 integer inputs.
  • Page 188 ITEM 64 attributes supported by the L30. Changes to the dataset will only take effect when the L30 is restarted. It is recommended to use reporting service from logical node LLN0 if a user needs some (but not all) data from already existing GGIO1, GGIO4, and MMXU4 points and their quantity is not greater than 64 minus the number items in this dataset.
  • Page 189 XCBR operating counter status attribute (OpCnt) increments with every operation. Frequent breaker operation can result in very large OpCnt values over time. This setting allows the OpCnt to be reset to “0” for XCBR1. GE Multilin L30 Line Current Differential System 5-53...
  • Page 190 Since GSSE/GOOSE messages are multicast Ethernet by specification, they are not usually be forwarded by net- work routers. However, GOOSE messages may be forwarded by routers if the router has been configured for VLAN functionality. NOTE 5-54 L30 Line Current Differential System GE Multilin...
  • Page 191 Menu”. Web pages are available showing DNP and IEC 60870-5-104 points lists, Modbus registers, event records, fault reports, and so on. First connect the UR and a computer to an Ethernet network, then enter the IP address of the L30 into the “Address”...
  • Page 192 ENABLED: No The L30 supports the IEC 60870-5-104 protocol. The L30 can be used as an IEC 60870-5-104 slave device connected to a maximum of two masters (usually either an RTU or a SCADA master station). Since the L30 maintains two sets of IEC 60870-5-104 data change buffers, no more than two masters should actively communicate with the L30 at one time.
  • Page 193: Modbus User Map

    “1”. An address value of “0” in the initial register means “none” and values of “0” display for all registers. Different values can be entered as required in any of the register positions. ADDRESS GE Multilin L30 Line Current Differential System 5-57...
  • Page 194: Real Time Clock

    Precision Time Protocol (PTP), IRIG-B, or SNTP, its accuracy approaches that of the synchroniz- ing time delivered to the relay. When the L30/L90 channel asymmetry function is used, the relay’s real time clock must be synchronized to an external time source using PTP or IRIG-B, typically from a global positioning system (GPS) receiver.
  • Page 195 Each network device implementing PP measures the processing delay it introduces in each time message and compensates for this delay in the time it transmits. As a result, the time delivered to end-devices such as the UR are GE Multilin L30 Line Current Differential System 5-59...
  • Page 196 A setting can be chosen that will reduce worst-case error to half of the range between minimum and maximum uncompensated delay, if these values are known. 5-60 L30 Line Current Differential System GE Multilin...
  • Page 197 L30 clock is closely synchronized with the SNTP/NTP server. It takes up to two minutes for the L30 to signal an SNTP self-test error if the server is offline.
  • Page 198 DAYLIGHT SAVINGS TIME (DST) Note that when IRIG-B time synchronization is active, the local time in the IRIG-B signal contains any daylight savings time offset and so the DST settings are ignored. 5-62 L30 Line Current Differential System GE Multilin...
  • Page 199: Fault Reports

    MESSAGE Z0 ANGLE: 75° The L30 relay supports one fault report and an associated fault locator. The signal source and trigger condition, as well as the characteristics of the line or feeder, are entered in this menu. The fault report stores data, in non-volatile memory, pertinent to an event when triggered. The captured data contained in the FaultReport.txt file includes:...
  • Page 200 It should be kept in mind that grounding points in vicinity of the installation impact the system zero-sequence impedance (grounded loads, reactors, zig-zag transformers, shunt capacitor banks, etc.). 5-64 L30 Line Current Differential System GE Multilin...
  • Page 201: Oscillography

    Reducing the sampling rate allows longer records to be stored. This setting has no effect on the internal sampling rate of the relay which is always 64 samples per cycle; that is, it has no effect on the fundamental calculations of the device. GE Multilin L30 Line Current Differential System 5-65...
  • Page 202 IB signal on terminal 2 of the CT/VT module in slot F. If there are no CT/VT modules and analog input modules, no analog traces will appear in the file; only the digital traces will appear. 5-66 L30 Line Current Differential System GE Multilin...
  • Page 203: Data Logger

    436380 s 254460 s 3600000 ms 2727.5 235645200 s 340.9 29455200 s 26182800 s Changing any setting affecting data logger operation will clear any data that is currently in the log. NOTE GE Multilin L30 Line Current Differential System 5-67...
  • Page 204: User-Programmable Leds

    LED TEST    PATH: SETTINGS PRODUCT SETUP USER-PROGRAMMABLE LEDS LED TEST Range: Disabled, Enabled.  LED TEST LED TEST FUNCTION:  Disabled Range: FlexLogic operand LED TEST CONTROL: MESSAGE 5-68 L30 Line Current Differential System GE Multilin...
  • Page 205 (one LED on at a time) control input rising edge of the Wait 1 second control input rising edge STAGE 3 of the control (one LED off at a time) input 842011A1.CDR Figure 5–9: LED TEST SEQUENCE GE Multilin L30 Line Current Differential System 5-69...
  • Page 206 LED column 2: user-programmable LEDs 1 through 12 • LED column 3: user-programmable LEDs 13 through 24 • LED column 4: user-programmable LEDs 25 through 36 • LED column 5: user-programmable LEDs 37 through 48 5-70 L30 Line Current Differential System GE Multilin...
  • Page 207: User-Programmable Self-Tests

    Range: Disabled, Enabled. SFP MODULE FAIL MESSAGE FUNCTION: Disabled All major self-test alarms are reported automatically with their corresponding FlexLogic operands, events, and targets. Most of the minor alarms can be disabled if desired. GE Multilin L30 Line Current Differential System 5-71...
  • Page 208: Control Pushbuttons

    The location of the control pushbuttons are shown in the following figures. Control pushbuttons 842813A1.CDR Figure 5–10: CONTROL PUSHBUTTONS (ENHANCED FACEPLATE) An additional four control pushbuttons are included on the standard faceplate when the L30 is ordered with the twelve user- programmable pushbutton option. STATUS EVENT CAUSE...
  • Page 209 SYSTEM SETUP/ BREAKERS/BREAKER 1/ BREAKER 1 PUSHBUTTON CONTROL Enabled=1 TIMER FLEXLOGIC OPERAND SYSTEM SETUP/ BREAKERS/BREAKER 2/ CONTROL PUSHBTN 1 ON 100 msec BREAKER 2 PUSHBUTTON CONTROL 842010A2.CDR Enabled=1 Figure 5–12: CONTROL PUSHBUTTON LOGIC GE Multilin L30 Line Current Differential System 5-73...
  • Page 210: User-Programmable Pushbuttons

    FlexLogic equations, protection elements, and control elements. Typical applications include breaker control, autorecloser blocking, and setting groups changes. The user-programmable pushbuttons are under the control level of password protection. The user-configurable pushbuttons for the enhanced faceplate are shown below. 5-74 L30 Line Current Differential System GE Multilin...
  • Page 211 The pulse duration of the remote set, remote reset, or local pushbutton must be at least 50 ms to operate the push- button. This allows the user-programmable pushbuttons to properly operate during power cycling events and vari- ous system disturbances that may cause transient assertion of the operating signals. NOTE GE Multilin L30 Line Current Differential System 5-75...
  • Page 212 PUSHBTN 1 RESET • PUSHBTN 1 LOCAL: This setting assigns the FlexLogic operand serving to inhibit pushbutton operation from the front panel pushbuttons. This locking functionality is not applicable to pushbutton autoreset. 5-76 L30 Line Current Differential System GE Multilin...
  • Page 213 “Normal” if the setting is “High Priority” or “Normal”. PUSHBTN 1 MESSAGE • PUSHBUTTON 1 EVENTS: If this setting is enabled, each pushbutton state change will be logged as an event into event recorder. GE Multilin L30 Line Current Differential System 5-77...
  • Page 214 Off = 0 SETTING SETTING Autoreset Delay Autoreset Function = Enabled = Disabled SETTING Drop-Out Timer TIMER FLEXLOGIC OPERAND 200 ms PUSHBUTTON 1 ON 842021A3.CDR Figure 5–15: USER-PROGRAMMABLE PUSHBUTTON LOGIC (Sheet 1 of 2) 5-78 L30 Line Current Differential System GE Multilin...
  • Page 215 User-programmable pushbuttons require a type HP or HQ faceplate. If an HP or HQ type faceplate was ordered separately, the relay order code must be changed to indicate the correct faceplate option. This can be done via EnerVista UR Setup with the Maintenance > Enable Pushbutton command. NOTE GE Multilin L30 Line Current Differential System 5-79...
  • Page 216: Flex State Parameters

    • USER-PROGRAMMABLE CONTROL INPUT: The user-definable displays also respond to the INVOKE AND SCROLL setting. Any FlexLogic operand (in particular, the user-programmable pushbutton operands), can be used to navigate the programmed displays. 5-80 L30 Line Current Differential System GE Multilin...
  • Page 217 (setting, actual value, or command) which has a Modbus address, to view the hexadecimal form of the Modbus address, then manually convert it to decimal form before entering it (EnerVista UR Setup usage conveniently facilitates this conversion). GE Multilin L30 Line Current Differential System 5-81...
  • Page 218: Installation

    "Programmed" state. UNIT NOT PROGRAMMED setting allows the user to uniquely identify a relay. This name will appear on generated reports. RELAY NAME 5-82 L30 Line Current Differential System GE Multilin...
  • Page 219: Remote Resources Configuration

    Bricks. Remote resources settings configure the point-to-point connection between specific fiber optic ports on the L30 process card and specific Brick. The relay is then configured to measure spe- cific currents, voltages and contact inputs from those Bricks, and to control specific outputs.
  • Page 220: Ac Inputs

    1000:1 CT before summation. If a protection element is set up to act on SRC 1 currents, then a pickup level of 1 pu will operate on 1000 A primary. The same rule applies for current sums from CTs with different secondary taps (5 A and 1 A). 5-84 L30 Line Current Differential System GE Multilin...
  • Page 221: Power System

    ABC or ACB. CT and VT inputs on the relay, labeled as A, B, and C, must be con- nected to system phases A, B, and C for correct operation. GE Multilin L30 Line Current Differential System 5-85...
  • Page 222: Signal Sources

    FREQUENCY TRACKING frequency applications. NOTE The frequency tracking feature functions only when the L30 is in the “Programmed” mode. If the L30 is “Not Pro- grammed”, then metering values are available but can exhibit significant errors. NOTE The nominal system frequency should be selected as 50 Hz or 60 Hz only. The FREQUENCY AND PHASE REFERENCE setting, used as a reference for calculating all angles, must be identical for all terminals.
  • Page 223 0.02 pu; thus by default the disturbance detector responds to a change of 0.04 pu. The metering sensitivity setting ( PROD-   ) controls the sensitivity of the disturbance detector UCT SETUP DISPLAY PROPERTIES CURRENT CUT-OFF LEVEL accordingly. GE Multilin L30 Line Current Differential System 5-87...
  • Page 224 Figure 5–19: EXAMPLE USE OF SOURCES Y LV D HV SRC 1 SRC 2 SRC 3 Phase CT F1+F5 None Ground CT None None Phase VT None None Aux VT None None 5-88 L30 Line Current Differential System GE Multilin...
  • Page 225: L Power System

    See page 5-94.  TRANSFORMER Any changes to the L30 power system settings change the protection system configuration. As such, the 87L pro- tection at all L30 protection system terminals must be temporarily disabled to allow the relays to acknowledge the NOTE new settings.
  • Page 226 Charging current compensation calculations should be performed for an arrangement where the VTs are con- nected to the line side of the circuit; otherwise, opening the breaker at one end of the line will cause a calcula- NOTE tion error. 5-90 L30 Line Current Differential System GE Multilin...
  • Page 227 LOCAL (TERMINAL 1 and TERMINAL 2) ID NUMBER: In installations using multiplexers or modems for communica- tion, it is desirable to ensure the data used by the relays protecting a given line comes from the correct relays. The L30 performs this check by reading the ID number contained in the messages sent by transmitting relays and comparing this ID to the programmed correct ID numbers by the receiving relays.
  • Page 228 • BLOCK GPS TIME REF: This setting signals to the L30 that the time reference is not valid. The time reference may be not accurate due to problems with the GPS receiver. The user must to be aware of the case when a GPS satellite receiver loses its satellite signal and reverts to its own calibrated crystal oscillator.
  • Page 229 5 SETTINGS 5.4 SYSTEM SETUP Figure 5–21: CHANNEL ASYMMETRY COMPENSATION LOGIC GE Multilin L30 Line Current Differential System 5-93...
  • Page 230 “None”). Only one in-zone transformer is allowed for both two-terminal and three-terminal applications. Enabling in- zone transformer functionality forces the L30 to automatically remove the zero-sequence component from all terminals currents. It also disables ground differential 87LG functionality and zero-sequence current removal functionality defined by the setting.
  • Page 231: Breakers

    Range: 0.000 to 65.535 s in steps of 0.001 MANUAL CLOSE RECAL1 MESSAGE TIME: 0.000 s Range: FlexLogic operand BREAKER 1 OUT OF SV: MESSAGE Range: Disabled, Enabled BREAKER 1 EVENTS: MESSAGE Disabled GE Multilin L30 Line Current Differential System 5-95...
  • Page 232 1. The number of breaker control elements is dependent on the number of CT/VT modules specified with the L30. The follow- ing settings are available for each breaker control element.
  • Page 233 5 SETTINGS 5.4 SYSTEM SETUP Figure 5–23: DUAL BREAKER CONTROL SCHEME LOGIC (Sheet 1 of 2) IEC 61850 functionality is permitted when the L30 is in “Programmed” mode and not in the local control mode. NOTE GE Multilin L30 Line Current Differential System...
  • Page 234 Note that IEC 61850 commands are event-driven and dwell time for these is one protection pass only. If you want to main- tain the close/open command for a certain time, do so either on the contact outputs using the "Seal-in" setting or in Flex- Logic. 5-98 L30 Line Current Differential System GE Multilin...
  • Page 235: Disconnect Switches

    For greater security in determination of the switch pole position, both the 89/a and 89/b auxiliary contacts are used with reporting of the discrepancy between them. The number of available disconnect switches depends on the number of the CT/VT modules ordered with the L30. •...
  • Page 236 SWITCH 1 ALARM DELAY: This setting specifies the delay interval during which a disagreement of status among the three-pole position tracking operands will not declare a pole disagreement. This allows for non-simultaneous operation of the poles. IEC 61850 functionality is permitted when the L30 is in “Programmed” mode and not in the local control mode. NOTE 5-100...
  • Page 237 5 SETTINGS 5.4 SYSTEM SETUP Figure 5–25: DISCONNECT SWITCH SCHEME LOGIC GE Multilin L30 Line Current Differential System 5-101...
  • Page 238: Flexcurves

    15.0 0.48 0.88 15.5 0.50 0.90 16.0 0.52 0.91 16.5 0.54 0.92 17.0 0.56 0.93 17.5 0.58 0.94 18.0 0.60 0.95 18.5 0.62 0.96 19.0 0.64 0.97 19.5 0.66 0.98 10.0 20.0 5-102 L30 Line Current Differential System GE Multilin...
  • Page 239 The multiplier and adder settings only affect the curve portion of the characteristic and not the MRT and HCT set- tings. The HCT settings override the MRT settings for multiples of pickup greater than the HCT ratio. NOTE GE Multilin L30 Line Current Differential System 5-103...
  • Page 240 EnerVista UR Setup software generates an error message and discards the proposed changes. NOTE e) STANDARD RECLOSER CURVES The standard recloser curves available for the L30 are displayed in the following graphs. 5-104 L30 Line Current Differential System...
  • Page 241 842723A1.CDR Figure 5–29: RECLOSER CURVES GE101 TO GE106 GE142 GE138 GE120 GE113 0.05 7 8 9 10 12 CURRENT (multiple of pickup) 842725A1.CDR Figure 5–30: RECLOSER CURVES GE113, GE120, GE138 AND GE142 GE Multilin L30 Line Current Differential System 5-105...
  • Page 242 Figure 5–31: RECLOSER CURVES GE134, GE137, GE140, GE151 AND GE201 GE152 GE141 GE131 GE200 7 8 9 10 12 CURRENT (multiple of pickup) 842728A1.CDR Figure 5–32: RECLOSER CURVES GE131, GE141, GE152, AND GE200 5-106 L30 Line Current Differential System GE Multilin...
  • Page 243 Figure 5–33: RECLOSER CURVES GE133, GE161, GE162, GE163, GE164 AND GE165 GE132 GE139 GE136 GE116 0.05 GE117 GE118 0.02 0.01 7 8 9 10 12 CURRENT (multiple of pickup) 842726A1.CDR Figure 5–34: RECLOSER CURVES GE116, GE117, GE118, GE132, GE136, AND GE139 GE Multilin L30 Line Current Differential System 5-107...
  • Page 244 Figure 5–35: RECLOSER CURVES GE107, GE111, GE112, GE114, GE115, GE121, AND GE122 GE202 GE135 GE119 7 8 9 10 12 CURRENT (multiple of pickup) 842727A1.CDR Figure 5–36: RECLOSER CURVES GE119, GE135, AND GE202 5-108 L30 Line Current Differential System GE Multilin...
  • Page 245: Phasor Measurement Unit

    See page 5–129.  CONFIGURATION The L30 is provided with an optional phasor measurement unit feature. This feature is specified as a soft- ware option at the time of ordering. The number of phasor measurement units available is also dependent on this option.
  • Page 246 Precise time input to the relay from the international time standard, via either IRIG-B or PTP, is vital for correct syn- chrophasor measurement and reporting. For IRIG-B, a DC level shift IRIG-B receiver must be used for the phasor measurement unit to output proper synchrophasor values. NOTE 5-110 L30 Line Current Differential System GE Multilin...
  • Page 247 — d1, d2, d3, and so on. The number of descriptions are equal to the number of bits configured in the 16 bit digital status word. GE Multilin L30 Line Current Differential System 5-111...
  • Page 248 From each PMU the user selects the phasor information of interest that is mapped into the selected aggregator datset(s). For version 7.0 only FCDA data is supported. Figure 5–40: DATA SET CREATED FROM USER SELECTED INTERNAL ITEMS 5-112 L30 Line Current Differential System GE Multilin...
  • Page 249 CONFIGURATION EXAMPLE: CFG-2 BASED CONFIGURATION (USING IEC61850-90-5) The L30 is expected to send the CFG-2 file (IEEE C37.118 config. file) upon request from the upstream synchrophasor devices (e.g., P30) without stopping R-SV multicasting, see figure below. The primary domain controller (PDC) does not need to use a stop/start data stream command if the UR protocol is set to IEC61850-90-5 prior to requesting the configura- tion via CFG-2 (IEEE C37.118 config.
  • Page 250 Range: 1 to 65534 in steps of 1 PMU 1 IDCODE: MESSAGE Range: 32-character ASCII string truncated to 16 PMU 1 STN: MESSAGE characters if mapped into C37.118 Default: GE-UR-PMU GE-UR-PMU Range: Available signal sources PMU 1 SIGNAL SOURCE: MESSAGE SRC 1...
  • Page 251 • PMU 1 SIGNAL SOURCE: This setting specifies one of the available L30 signal sources for processing in the PMU. Note that any combination of voltages and currents can be configured as a source. The current channels could be con- figured as sums of physically connected currents.
  • Page 252 For a system frequency of 60 Hz (50 Hz), the L30 generates a reporting mismatch message if the selected rate is not set as 10 Hz, 12 Hz, 15 Hz, 20 Hz, 30 Hz, 60 Hz, or 120 Hz (or 10 Hz, 25 Hz, 50 Hz or 100 Hz when the system frequency is 50 Hz) when entered via the keypad or software;...
  • Page 253 As per IEC 61850-6 standard specification, the PMU LD Name is the concatenated combination (to total 64 charac- ters) of IED Name (specified in IEC 61850 Server Settings) appended with PMU X LDINST string. NOTE GE Multilin L30 Line Current Differential System 5-117...
  • Page 254 VTs, CTs, and cabling. The setting values are effectively added to the measured angles. Therefore, enter a positive correction of the secondary signal lags the true signal; and negative value if the secondary signal leads the true signal. 5-118 L30 Line Current Differential System GE Multilin...
  • Page 255 When receiving synchrophasor data at multiple locations, with possibly different reference nodes, it can be more beneficial to allow the central locations to perform the compensation of sequence voltages. This setting applies to PMU data only. The L30 calculates symmetrical voltages independently for protection and control purposes without applying this correction.
  • Page 256 DPO TIME: 1.00 s Range: FlexLogic operand PMU 1 FREQ TRIG BLK: MESSAGE Range: Self-Reset, Latched, Disabled PMU 1 FREQ TRIGGER MESSAGE TARGET: Self-Reset Range: Enabled, Disabled PMU 1 FREQ TRIGGER MESSAGE EVENTS: Disabled 5-120 L30 Line Current Differential System GE Multilin...
  • Page 257 L30 standards. This element requires the frequency is above the minimum measurable value. If the frequency is below this value, such as when the circuit is de-energized, the trigger drops out.
  • Page 258 This element responds to elevated current. The trigger responds to the phase current signal of the phasor measurement unit (PMU) source. All current channel (A, B, and C) are processed independently and could trigger the recorder. 5-122 L30 Line Current Differential System GE Multilin...
  • Page 259 1 pu is a product of 1 pu voltage and 1 pu current, or the product of nominal secondary voltage, the VT ratio and the nominal primary current. For the three-phase power, 1 pu is three times that for a single-phase power. The comparator applies a 3% hysteresis. GE Multilin L30 Line Current Differential System 5-123...
  • Page 260 DPO TIME: 1.00 s Range: FlexLogic operand PMU 1 df/dt TRG BLK: MESSAGE Range: Self-Reset, Latched, Disabled PMU 1 df/dt TRIGGER MESSAGE TARGET: Self-Reset Range: Enabled, Disabled PMU 1 df/dt TRIGGER MESSAGE EVENTS: Disabled 5-124 L30 Line Current Differential System GE Multilin...
  • Page 261 PMU 1 df/dt TRIGGER DPO TIME: This setting could be used to extend the trigger after the situation returned to nor- mal. This setting is of particular importance when using the recorder in the forced mode (recording as long as the trig- gering condition is asserted). GE Multilin L30 Line Current Differential System 5-125...
  • Page 262 5.4 SYSTEM SETUP 5 SETTINGS Figure 5–48: RATE OF CHANGE OF FREQUENCY TRIGGER SCHEME LOGIC 5-126 L30 Line Current Differential System GE Multilin...
  • Page 263 Default: 4712  CONFIGURATION TCP PORT: 4712 Range: 1 to 65534 PMU AGGREGATOR 1 MESSAGE Default: 4713 UDP PORT: 4713 Range: Disabled, Enabled PMU AGGREGATOR 1 MESSAGE Default: Disabled PDC CONTROL: Disabled GE Multilin L30 Line Current Differential System 5-127...
  • Page 264 AGTR2 PDC CNTRL 3 Phasor data concentrator asserts control bit 3 as received via the network. ↓ as above AGTR1 PDC CNTRL 16 Phasor data concentrator asserts control bit 16, as received via the network. 5-128 L30 Line Current Differential System GE Multilin...
  • Page 265 R-SV frames. If remote client control is disabled, a negative response is pro- vided to the client in response to a write attempt. A FlexLogic operand (SvEna) is provided for each Aggregator that GE Multilin L30 Line Current Differential System 5-129...
  • Page 266 The range is 0 to 2. Shaded settings in the table are not supported in firmware 7.0. ENUMERATION AUTHENTICATION ENCRYPTION NOTE 5-130 L30 Line Current Differential System GE Multilin...
  • Page 267: Introduction To Flexlogic

    Figure 5–50: UR ARCHITECTURE OVERVIEW The states of all digital signals used in the L30 are represented by flags (or FlexLogic operands, which are described later in this section). A digital “1” is represented by a 'set' flag. Any external contact change-of-state can be used to block an ele- ment from operating, as an input to a control feature in a FlexLogic equation, or to operate a contact output.
  • Page 268 Some types of operands are present in the relay in multiple instances; e.g. contact and remote inputs. These types of oper- ands are grouped together (for presentation purposes only) on the faceplate display. The characteristics of the different types of operands are listed in the table below. Table 5–13: L30 FLEXLOGIC OPERAND TYPES OPERAND TYPE STATE...
  • Page 269 Exceeded maximum CRC error threshold on channel 2 87L DIFF CH2 CRCFAIL 87L DIFF CH1 ID FAIL The ID check for a peer L30 on channel 1 has failed 87L DIFF CH2 ID FAIL The ID check for a peer L30 on channel 2 has failed...
  • Page 270 5.5 FLEXLOGIC 5 SETTINGS Table 5–14: L30 FLEXLOGIC OPERANDS (Sheet 2 of 7) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT BKR FAIL 1 RETRIPA Breaker failure 1 re-trip phase A (only for 1-pole schemes) Breaker failure BKR FAIL 1 RETRIPB...
  • Page 271 5 SETTINGS 5.5 FLEXLOGIC Table 5–14: L30 FLEXLOGIC OPERANDS (Sheet 3 of 7) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT LATCH 1 ON Non-volatile latch 1 is ON (Logic = 1) Non-volatile latches LATCH 1 OFF Non-volatile latch 1 is OFF (Logic = 0)
  • Page 272 5.5 FLEXLOGIC 5 SETTINGS Table 5–14: L30 FLEXLOGIC OPERANDS (Sheet 4 of 7) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT: PHASE TOC1 PKP At least one phase of phase time overcurrent 1 has picked up Phase time PHASE TOC1 OP...
  • Page 273 5 SETTINGS 5.5 FLEXLOGIC Table 5–14: L30 FLEXLOGIC OPERANDS (Sheet 5 of 7) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT: SRC1 VT FF OP Source 1 VT fuse failure detector has operated VTFF (Voltage SRC1 VT FF DPO Source 1 VT fuse failure detector has dropped out...
  • Page 274 5.5 FLEXLOGIC 5 SETTINGS Table 5–14: L30 FLEXLOGIC OPERANDS (Sheet 6 of 7) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION INPUTS/OUTPUTS: Cont Ip 1 (will not appear unless ordered) Contact inputs Cont Ip 2 (will not appear unless ordered) ↓ ↓...
  • Page 275 5 SETTINGS 5.5 FLEXLOGIC Table 5–14: L30 FLEXLOGIC OPERANDS (Sheet 7 of 7) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION PASSWORD ACCESS LOC SETG OFF Asserted when local setting access is disabled SECURITY ACCESS LOC SETG ON Asserted when local setting access is enabled...
  • Page 276: Flexlogic Rules

    A timer operator (for example, "TIMER 1") or virtual output assignment (for example, " = Virt Op 1") may only be used once. If this rule is broken, a syntax error will be declared. 5-140 L30 Line Current Differential System GE Multilin...
  • Page 277: Flexlogic Evaluation

    (i.e. Virtual Output 3). The final output must also be assigned to a virtual output as virtual output 4, which will be programmed in the contact output section to oper- ate relay H1 (that is, contact output H1). GE Multilin L30 Line Current Differential System 5-141...
  • Page 278 Until accustomed to using FlexLogic, it is suggested that a worksheet with a series of cells marked with the arbitrary parameter numbers be prepared, as shown below. 5-142 L30 Line Current Differential System GE Multilin...
  • Page 279 99: The final output of the equation is virtual output 4 which is parameter “= Virt Op 4". 98: The operator preceding the output is timer 2, which is operand “TIMER 2". Note that the settings required for the timer are established in the timer programming section. GE Multilin L30 Line Current Differential System 5-143...
  • Page 280 It is now possible to check that the selection of parameters will produce the required logic by converting the set of parame- ters into a logic diagram. The result of this process is shown below, which is compared to the logic for virtual output 4 dia- gram as a check. 5-144 L30 Line Current Differential System GE Multilin...
  • Page 281 In the expression above, the virtual output 4 input to the four-input OR is listed before it is created. This is typical of a form of feedback, in this case, used to create a seal-in effect with the latch, and is correct. GE Multilin L30 Line Current Differential System 5-145...
  • Page 282: Flexlogic Equation Editor

    TIMER 1 PICKUP DELAY: Sets the time delay to pickup. If a pickup delay is not required, set this function to "0". • TIMER 1 DROPOUT DELAY: Sets the time delay to dropout. If a dropout delay is not required, set this function to "0". 5-146 L30 Line Current Differential System GE Multilin...
  • Page 283: Flexelements

    The element can be programmed to respond either to a signal level or to a rate-of-change (delta) over a pre-defined period of time. The output operand is asserted when the operating signal is higher than a threshold or lower than a threshold as per user's choice. GE Multilin L30 Line Current Differential System 5-147...
  • Page 284 The FLEXELEMENT 1 DIRECTION following figure explains the application of the FLEXELEMENT 1 DIRECTION FLEXELEMENT 1 PICKUP FLEXELEMENT 1 HYS- settings. TERESIS 5-148 L30 Line Current Differential System GE Multilin...
  • Page 285 DIRECTION = Under; FLEXELEMENT INPUT MODE = Signed; FlexElement 1 OpSig FLEXELEMENT 1 PKP FLEXELEMENT DIRECTION = Under; FLEXELEMENT INPUT MODE = Absolute; FlexElement 1 OpSig 842706A2.CDR Figure 5–60: FLEXELEMENT INPUT MODE SETTING GE Multilin L30 Line Current Differential System 5-149...
  • Page 286 “Delta”. FLEXELEMENT 1 COMP MODE This setting specifies the pickup delay of the element. The setting FLEXELEMENT 1 PKP DELAY FLEXELEMENT 1 RST DELAY specifies the reset delay of the element. 5-150 L30 Line Current Differential System GE Multilin...
  • Page 287: Non-Volatile Latches

    LATCH N LATCH N LATCH N TYPE RESET Reset Dominant Previous Previous State State Dominant Previous Previous State State Figure 5–61: NON-VOLATILE LATCH OPERATION TABLE (N = 1 to 16) AND LOGIC GE Multilin L30 Line Current Differential System 5-151...
  • Page 288: Overview

      PATH: SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) LINE DIFFERENTIAL ELEMENTS  LINE DIFFERENTIAL  CURRENT See page 5-153.  ELEMENTS  DIFFERENTIAL  STUB BUS MESSAGE See page 5-157.  5-152 L30 Line Current Differential System GE Multilin...
  • Page 289 This CURRENT DIFF SIGNAL SOURCE 1 CURRENT DIFF SIGNAL SOURCE 4 source is mandatory and is assigned with the   menu. SYSTEM SETUP SIGNAL SOURCES SOURCE 1 GE Multilin L30 Line Current Differential System 5-153...
  • Page 290 If set to “Per phase”, the L30 performs inrush inhibit individually in each phase. – If set to “2-out-of-3”, the L30 checks second harmonic level in all three phases individually. If any two phases establish an inhibiting condition, then the remaining phase is restrained automatically.
  • Page 291 DTT on a per three-phase basis. For the current differential element to function properly, it is imperative that all L30 devices on the protected line have exactly identical firmware revisions. For example, revision 5.62 in only compatible with 5.62, not 5.61 or 5.63.
  • Page 292 5.6 GROUPED ELEMENTS 5 SETTINGS Figure 5–62: CURRENT DIFFERENTIAL SCHEME LOGIC 5-156 L30 Line Current Differential System GE Multilin...
  • Page 293 The assigned current element should be mapped to appropriate output contact(s) to trip the stub bus breakers. It should be blocked unless disconnect is open. To prevent 87L tripping from remote L30 relays still protecting the line, the auxiliary contact of line disconnect switch (logic “1” when line switch is open) should be assigned to block the local 87L function by using the setting.
  • Page 294: Phase Current

     PHASE IOC3 MESSAGE See page 5-166.   PHASE IOC4 MESSAGE See page 5-166.   PHASE MESSAGE See page 5–167.  DIRECTIONAL 1  PHASE MESSAGE See page 5–167.  DIRECTIONAL 2 5-158 L30 Line Current Differential System GE Multilin...
  • Page 295 5.6 GROUPED ELEMENTS b) INVERSE TIME OVERCURRENT CHARACTERISTICS The inverse time overcurrent curves used by the time overcurrent elements are the IEEE, IEC, GE Type IAC, and I t stan- dard curve shapes. This allows for simplified coordination with downstream devices.
  • Page 296 4.827 38.634 22.819 14.593 11.675 10.130 9.153 8.470 7.960 7.562 7.241 51.512 30.426 19.458 15.567 13.507 12.204 11.294 10.614 10.083 9.654 10.0 64.390 38.032 24.322 19.458 16.883 15.255 14.117 13.267 12.604 12.068 5-160 L30 Line Current Differential System GE Multilin...
  • Page 297 1.835 1.067 0.668 0.526 0.451 0.404 0.371 0.346 0.327 0.311 0.80 2.446 1.423 0.890 0.702 0.602 0.538 0.494 0.461 0.435 0.415 1.00 3.058 1.778 1.113 0.877 0.752 0.673 0.618 0.576 0.544 0.518 GE Multilin L30 Line Current Differential System 5-161...
  • Page 298 = characteristic constant, and T = reset time in seconds (assuming energy capacity is 100% RESET is “Timed”) RESET Table 5–23: GE TYPE IAC INVERSE TIME CURVE CONSTANTS IAC CURVE SHAPE IAC Extreme Inverse 0.0040 0.6379 0.6200 1.7872 0.2461...
  • Page 299 = Reset Time in seconds (assuming energy capacity is 100% and RESET: Timed) RESET RECLOSER CURVES: The L30 uses the FlexCurve feature to facilitate programming of 41 recloser curves. Please refer to the FlexCurve section in this chapter for additional details. GE Multilin...
  • Page 300 (see the figure below); the pickup level is calculated as ‘Mvr’ times the setting. If the voltage restraint PHASE TOC1 PICKUP feature is disabled, the pickup level always remains at the setting value. 5-164 L30 Line Current Differential System GE Multilin...
  • Page 301 5 SETTINGS 5.6 GROUPED ELEMENTS Phase-Phase Voltage ÷ VT Nominal Phase-phase Voltage 818784A4.CDR Figure 5–64: PHASE TIME OVERCURRENT VOLTAGE RESTRAINT CHARACTERISTIC Figure 5–65: PHASE TIME OVERCURRENT 1 SCHEME LOGIC GE Multilin L30 Line Current Differential System 5-165...
  • Page 302 The input current is the fundamental phasor magnitude. For timing curves, see the publication Instan- taneous Overcurrent Element Response to Saturated Waveforms in UR-Series Relays (GET-8400A). Figure 5–66: PHASE INSTANTANEOUS OVERCURRENT 1 SCHEME LOGIC 5-166 L30 Line Current Differential System GE Multilin...
  • Page 303 CTs and the line-line voltage from the VTs, based on the 90° or quadrature connection. If there is a requirement to supervise overcurrent elements for flows in opposite directions, such as can happen through a bus-tie breaker, two phase directional elements should be programmed with opposite element characteristic angle (ECA) settings. GE Multilin L30 Line Current Differential System 5-167...
  • Page 304 10 ms must be added to all the instantaneous protection elements under the supervi- sion of the phase directional element. If current reversal is of a concern, a longer delay – in the order of 20 ms – may be needed. 5-168 L30 Line Current Differential System GE Multilin...
  • Page 305: Neutral Current

    MESSAGE See page 5-171.  ↓  NEUTRAL IOC4 MESSAGE See page 5-171.   NEUTRAL MESSAGE See page 5–172.  DIRECTIONAL 1  NEUTRAL MESSAGE See page 5–172.  DIRECTIONAL 2 GE Multilin L30 Line Current Differential System 5-169...
  • Page 306 NEUTRAL TOC 1 SETTING RESET: NEUTRAL TOC1 PKP NEUTRAL TOC1 NEUTRAL TOC1 DPO PICKUP SOURCE: NEUTRAL TOC1 OP SETTING NEUTRAL TOC1 BLOCK: Off = 0 827034A4.VSD Figure 5–69: NEUTRAL TIME OVERCURRENT 1 SCHEME LOGIC 5-170 L30 Line Current Differential System GE Multilin...
  • Page 307 The positive-sequence restraint must be considered when testing for pickup accuracy and response time (multiple of pickup). The operating quantity depends on how test currents are injected into the relay (single-phase injection: 0.9375xI ; three-phase pure zero-sequence injection: × injected injected Figure 5–70: NEUTRAL IOC1 SCHEME LOGIC GE Multilin L30 Line Current Differential System 5-171...
  • Page 308 × × (EQ 5.19) – The positive-sequence restraint allows for more sensitive settings by counterbalancing spurious zero-sequence currents resulting from: • System unbalances under heavy load conditions. 5-172 L30 Line Current Differential System GE Multilin...
  • Page 309 REV LA = 80° (reverse limit angle = the ± angular limit with the ECA for operation) The above bias should be taken into account when using the neutral directional overcurrent element to directionalize other protection elements. GE Multilin L30 Line Current Differential System 5-173...
  • Page 310 NEUTRAL DIR OC1 POL VOLT: Selects the polarizing voltage used by the directional unit when "Voltage," "Dual," "Dual-V," or "Dual-I" polarizing mode is set. The polarizing voltage can be programmed to be either the zero-sequence 5-174 L30 Line Current Differential System GE Multilin...
  • Page 311 NEUTRAL DIR OC1 REV PICKUP: This setting defines the pickup level for the overcurrent unit of the element in the reverse direction. When selecting this setting it must be kept in mind that the design uses a positive-sequence restraint technique for the “Calculated 3I0” mode of operation. GE Multilin L30 Line Current Differential System 5-175...
  • Page 312: Ground Current

     GROUND TOC1 See page 5-177.    GROUND TOC2 MESSAGE See page 5-177.   GROUND IOC1 MESSAGE See page 5-178.  ↓  GROUND IOC4 MESSAGE See page 5-178.  5-176 L30 Line Current Differential System GE Multilin...
  • Page 313 GROUND TOC 1 SETTING GROUND TOC1 PKP RESET: GROUND TOC1 GROUND TOC1 DPO PICKUP SOURCE: GROUND TOC1 OP SETTING GROUND TOC1 BLOCK: Off = 0 827036A4.VSD Figure 5–73: GROUND TOC1 SCHEME LOGIC GE Multilin L30 Line Current Differential System 5-177...
  • Page 314 GROUND IOC1 PICKUP Enabled = 1 SETTING DELAY: GROUND IOC1 GROUND IOC1 RESET SETTING PICKUP: DELAY: GROUND IOC1 SOURCE: PICKUP SETTING GROUND IOC1 BLOCK: 827037A5.VSD Off = 0 Figure 5–74: GROUND IOC1 SCHEME LOGIC 5-178 L30 Line Current Differential System GE Multilin...
  • Page 315: Negative Sequence Current

    For example, if the element reset characteristic is set to “Instanta- neous” and the element is blocked, the time accumulator is cleared immediately. Figure 5–75: NEGATIVE SEQUENCE TOC1 SCHEME LOGIC GE Multilin L30 Line Current Differential System 5-179...
  • Page 316 The operating quantity depends on the way the test currents are injected into the relay (single-phase injection: ⋅ 0.2917 I ; three-phase injection, opposite rotation: injected injected Figure 5–76: NEGATIVE SEQUENCE IOC1 SCHEME LOGIC 5-180 L30 Line Current Differential System GE Multilin...
  • Page 317: Breaker Failure

    Range: 0.001 to 30.000 pu in steps of 0.001 BF1 N AMP HISET MESSAGE PICKUP: 1.050 pu Range: 0.001 to 30.000 pu in steps of 0.001 BF1 PH AMP LOSET MESSAGE PICKUP: 1.050 pu GE Multilin L30 Line Current Differential System 5-181...
  • Page 318 5-182 L30 Line Current Differential System GE Multilin...
  • Page 319 BREAKER FAILURE TIMER No. 2 (±1/8 cycle) INITIATE (1/8 cycle) BREAKER FAILURE CURRENT DETECTOR PICKUP (1/8 cycle) BREAKER FAILURE OUTPUT RELAY PICKUP (1/4 cycle) FAULT cycles OCCURS 827083A6.CDR Figure 5–77: BREAKER FAILURE MAIN PATH SEQUENCE GE Multilin L30 Line Current Differential System 5-183...
  • Page 320 In microprocessor relays this time is not significant. In L30 relays, which use a Fourier transform, the calculated current magnitude will ramp-down to zero one power frequency cycle after the current is interrupted, and this lag should be included in the overall margin duration, as it occurs after current interruption.
  • Page 321 Upon operation of the breaker failure element for a single pole trip command, a three-pole trip command should be given via output operand BKR FAIL 1 TRIP OP GE Multilin L30 Line Current Differential System 5-185...
  • Page 322 5.6 GROUPED ELEMENTS 5 SETTINGS SINGLE-POLE BREAKER FAILURE, INITIATE Figure 5–79: SINGLE-POLE BREAKER FAILURE, TIMERS 5-186 L30 Line Current Differential System GE Multilin...
  • Page 323 5 SETTINGS 5.6 GROUPED ELEMENTS Figure 5–80: THREE-POLE BREAKER FAILURE, INITIATE GE Multilin L30 Line Current Differential System 5-187...
  • Page 324 5.6 GROUPED ELEMENTS 5 SETTINGS Figure 5–81: THREE-POLE BREAKER FAILURE, TIMERS 5-188 L30 Line Current Differential System GE Multilin...
  • Page 325: Voltage Elements

    ------------------ –   pickup where: T = operating time D = undervoltage delay setting (D = 0.00 operates instantaneously) V = secondary voltage applied to the relay = pickup level pickup GE Multilin L30 Line Current Differential System 5-189...
  • Page 326 The minimum voltage setting selects the operating voltage below which the element is blocked (a setting of “0” will allow a dead source to be considered a fault condition). 5-190 L30 Line Current Differential System GE Multilin...
  • Page 327 The input voltage is the phase-to-phase voltage, either measured directly from delta-connected VTs or as cal- culated from phase-to-ground (wye) connected VTs. The specific voltages to be used for each phase are shown below. GE Multilin L30 Line Current Differential System 5-191...
  • Page 328 There are three negative-sequence overvoltage elements available. The negative-sequence overvoltage element may be used to detect loss of one or two phases of the source, a reversed phase sequence of voltage, or a non-symmetrical system voltage condition. 5-192 L30 Line Current Differential System GE Multilin...
  • Page 329 AUX UV1 EVENTS: MESSAGE Disabled The L30 contains one auxiliary undervoltage element for each VT bank. This element is intended for monitoring undervolt- age conditions of the auxiliary voltage. The selects the voltage level at which the time undervoltage ele- AUX UV1 PICKUP ment starts timing.
  • Page 330 AUX OV1 EVENTS: MESSAGE Disabled The L30 contains one auxiliary overvoltage element for each VT bank. This element is intended for monitoring overvoltage conditions of the auxiliary voltage. The nominal secondary voltage of the auxiliary voltage channel entered under SYSTEM ...
  • Page 331: Supervising Elements

    0.24 pu, the current adaptive level detector setting remains at 0.24 pu and the output remains active (as well as the disturbance detector output) when the measured value remains above the current setting. GE Multilin L30 Line Current Differential System 5-195...
  • Page 332 DD EVENTS bance on the system which may result in filling the events buffer and possible loss of valuable data. NOTE Figure 5–88: DISTURBANCE DETECTOR SCHEME LOGIC 5-196 L30 Line Current Differential System GE Multilin...
  • Page 333: Overview

    If more than one operate-type operand is required, it may be assigned directly from the trip bus menu. GE Multilin L30 Line Current Differential System 5-197...
  • Page 334 TRIP BUS 1 PKP = Enabled TRIP BUS 1 BLOCK = Off SETTINGS TRIP BUS 1 LATCHING = Enabled TRIP BUS 1 RESET = Off FLEXLOGIC OPERAND RESET OP 842023A1.CDR Figure 5–90: TRIP BUS LOGIC 5-198 L30 Line Current Differential System GE Multilin...
  • Page 335: Setting Groups

    The setting groups menu controls the activation and deactivation of up to six possible groups of settings in the GROUPED settings menu. The faceplate Settings In Use LEDs indicate which active group (with a non-flashing energized ELEMENTS LED) is in service. GE Multilin L30 Line Current Differential System 5-199...
  • Page 336 OR (2) AND (3) = VIRT OP 1 (VO1) PHASE TOC1 PKP PHASE TOC2 PKP AND (3) = VIRT OP 1 (VO1) 842789A1.CDR Figure 5–91: EXAMPLE FLEXLOGIC CONTROL OF A SETTINGS GROUP 5-200 L30 Line Current Differential System GE Multilin...
  • Page 337: Selector Switch

    1 to the . If the control word is outside the range, an alarm is established SELECTOR FULL RANGE by setting the FlexLogic operand for 3 seconds. SELECTOR ALARM GE Multilin L30 Line Current Differential System 5-201...
  • Page 338 SELECTOR 1 3BIT ACK: This setting specifies an acknowledging input for the three-bit control input. The pre- selected position is applied on the rising edge of the assigned FlexLogic operand. This setting is active only under the 5-202 L30 Line Current Differential System GE Multilin...
  • Page 339 The selector position pre-selected via the stepping up control input has not been confirmed before the time out. SELECTOR 1 BIT ALARM The selector position pre-selected via the three-bit control input has not been confirmed before the time out. GE Multilin L30 Line Current Differential System 5-203...
  • Page 340 3BIT A2 POS 1 POS 2 POS 3 POS 4 POS 5 POS 6 POS 7 BIT 0 BIT 1 BIT 2 STP ALARM BIT ALARM ALARM 842737A1.CDR Figure 5–92: TIME-OUT MODE 5-204 L30 Line Current Differential System GE Multilin...
  • Page 341 Make the following changes to selector switch element in the    SETTINGS CONTROL ELEMENTS SELECTOR SWITCH menu to assign control to user programmable pushbutton 1 and contact inputs 1 through 3: SELECTOR SWITCH 1 GE Multilin L30 Line Current Differential System 5-205...
  • Page 342 SELECTOR 1 BIT ALARM 3-bit position out SELECTOR 1 ALARM SELECTOR 1 PWR ALARM SELECTOR 1 BIT 0 SELECTOR 1 BIT 1 SELECTOR 1 BIT 2 842012A2.CDR Figure 5–94: SELECTOR SWITCH LOGIC 5-206 L30 Line Current Differential System GE Multilin...
  • Page 343: Underfrequency

    For example, UNDERFREQ 1 PICKUP if the system frequency is 60 Hz and the load shedding is required at 59.5 Hz, the setting will be 59.50 Hz. Figure 5–95: UNDERFREQUENCY SCHEME LOGIC GE Multilin L30 Line Current Differential System 5-207...
  • Page 344: Synchrocheck

    ΔF. This time can be calculated by: ------------------------------- - (EQ 5.22) 360° ----------------- - × ΔF 2 ΔΦ × where: ΔΦ = phase angle difference in degrees; ΔF = frequency difference in Hz. 5-208 L30 Line Current Differential System GE Multilin...
  • Page 345 COMBINATION SOURCE Y SOURCE Z Phase VTs and Phase VTs and Phase Phase Auxiliary VT Auxiliary VT Phase VTs and Phase VT Phase Phase Auxiliary VT Phase VT Phase VT Phase Phase GE Multilin L30 Line Current Differential System 5-209...
  • Page 346 The relay will use the phase channel of a three-phase set of voltages if pro- grammed as part of that source. The relay will use the auxiliary voltage channel only if that channel is programmed as part of the Source and a three-phase set is not. 5-210 L30 Line Current Differential System GE Multilin...
  • Page 347 5 SETTINGS 5.7 CONTROL ELEMENTS Figure 5–96: SYNCHROCHECK SCHEME LOGIC GE Multilin L30 Line Current Differential System 5-211...
  • Page 348: Autoreclose

    4.000 s Range: FlexLogic operand AR1 ADD DELAY 1: MESSAGE Range: 0.00 to 655.35 s in steps of 0.01 AR1 DELAY 1: MESSAGE 0.000 s Range: FlexLogic operand AR1 ADD DELAY 2: MESSAGE 5-212 L30 Line Current Differential System GE Multilin...
  • Page 349 Scheme lockout blocks all phases of the reclosing cycle, preventing automatic reclosure, if any of the following occurs: • The maximum shot number was reached. • A ‘Block’ input is in effect (for instance; Breaker Failure, bus differential protection operated, etc.). GE Multilin L30 Line Current Differential System 5-213...
  • Page 350 ‘reclose-in-progress’ state. If all condi- tions allowing a breaker closure are not satisfied when this time expires, the scheme goes to “Lockout”. This timer must be set to a delay less than the reset timer. NOTE 5-214 L30 Line Current Differential System GE Multilin...
  • Page 351 5 SETTINGS 5.7 CONTROL ELEMENTS To sheet 2 Figure 5–97: AUTORECLOSURE SCHEME LOGIC (Sheet 1 of 2) GE Multilin L30 Line Current Differential System 5-215...
  • Page 352 5.7 CONTROL ELEMENTS 5 SETTINGS Figure 5–98: AUTORECLOSURE SCHEME LOGIC (Sheet 2 of 2) 5-216 L30 Line Current Differential System GE Multilin...
  • Page 353 5 SETTINGS 5.7 CONTROL ELEMENTS Figure 5–99: SINGLE SHOT AUTORECLOSING SEQUENCE - PERMANENT FAULT GE Multilin L30 Line Current Differential System 5-217...
  • Page 354: Digital Elements

    DIGITAL ELEMENT 1 RESET DELAY: Sets the time delay to reset. If a reset delay is not required, set to “0”. • DIGITAL ELEMENT 1 PICKUP LED: This setting enables or disabled the digital element pickup LED. When set to “Disabled”, the operation of the pickup LED is blocked. 5-218 L30 Line Current Differential System GE Multilin...
  • Page 355 In most breaker control circuits, the trip coil is connected in series with a breaker auxiliary contact which is open when the breaker is open (see diagram below). To prevent unwanted alarms in this situation, the trip circuit monitoring logic must include the breaker position. Figure 5–101: TRIP CIRCUIT EXAMPLE 1 GE Multilin L30 Line Current Differential System 5-219...
  • Page 356 In this case, it is not required to supervise the monitoring circuit with the breaker position – the setting is BLOCK selected to “Off”. In this case, the settings are as follows (EnerVista UR Setup example shown). Figure 5–102: TRIP CIRCUIT EXAMPLE 2 5-220 L30 Line Current Differential System GE Multilin...
  • Page 357: Digital Counters

    –2,147,483,648 counts, the counter will rollover to +2,147,483,647. • COUNTER 1 BLOCK: Selects the FlexLogic operand for blocking the counting operation. All counter operands are blocked. GE Multilin L30 Line Current Differential System 5-221...
  • Page 358 COUNTER 1 FROZEN: Off = 0 STORE DATE & TIME Date & Time SETTING COUNT1 FREEZE/RESET: Off = 0 827065A1.VSD SETTING COUNT1 FREEZE/COUNT: Off = 0 Figure 5–103: DIGITAL COUNTER SCHEME LOGIC 5-222 L30 Line Current Differential System GE Multilin...
  • Page 359: Monitoring Elements

    1000 kA2-cyc Range: FlexLogic operand BKR 1 ARC AMP BLOCK: MESSAGE Range: Self-reset, Latched, Disabled BKR 1 ARC AMP MESSAGE TARGET: Self-reset Range: Disabled, Enabled BKR 1 ARC AMP MESSAGE EVENTS: Disabled GE Multilin L30 Line Current Differential System 5-223...
  • Page 360 BKR 1 ARC AMP LIMIT: Selects the threshold value above which the output operand is set. Breaker Contacts Initiate Extinguished Part Total Area = Breaker Arcing Current (kA·cycle) Programmable 100 ms Start Delay Start Stop Integration Integration Figure 5–104: ARCING CURRENT MEASUREMENT 5-224 L30 Line Current Differential System GE Multilin...
  • Page 361 5 SETTINGS 5.7 CONTROL ELEMENTS Figure 5–105: BREAKER ARCING CURRENT SCHEME LOGIC GE Multilin L30 Line Current Differential System 5-225...
  • Page 362 CT FAIL 3I0 INPUT 2 PICKUP: This setting selects the 3I_0 pickup value for input 2 (different CT input) of the relay. • CT FAIL 3V0 INPUT: This setting selects the voltage source. 5-226 L30 Line Current Differential System GE Multilin...
  • Page 363 An additional condition is introduced to inhibit a fuse failure declaration when the monitored circuit is de-energized; positive- sequence voltage and current are both below threshold levels. setting enables and disables the fuse failure feature for Source 1 VT Fuse Fail. VT FUSE FAILURE 1 FUNCTION GE Multilin L30 Line Current Differential System 5-227...
  • Page 364 Figure 5–107: VT FUSE FAIL SCHEME LOGIC Base voltage for this element is PHASE VT SECONDARY setting in the case of WYE VTs and (PHASE VT SECONDARY)/ in case of DELTA VTs. 5-228 L30 Line Current Differential System GE Multilin...
  • Page 365 • BROKEN CONDUCTOR 1 PKP DELAY: This setting specifies the pickup time delay for this function to operate after assertion of the broken conductor pickup FlexLogic operand. GE Multilin L30 Line Current Differential System 5-229...
  • Page 366 5.7 CONTROL ELEMENTS 5 SETTINGS Figure 5–108: BROKEN CONDUCTOR DETECTION LOGIC 5-230 L30 Line Current Differential System GE Multilin...
  • Page 367 • = measured load RMS current before overload occurs. • k= IEC 255-8 k-factor applied to I , defining maximum permissible current above nominal current. • = protected element base (nominal) current. GE Multilin L30 Line Current Differential System 5-231...
  • Page 368 Δ -------------- - (EQ 5.26) – op In When current is less than the dropout level, I > 0.97 × k × I , the element starts decreasing the thermal energy: 5-232 L30 Line Current Differential System GE Multilin...
  • Page 369 30 minutes Busbar 60 minutes 20 minutes Underground cable 20 to 60 minutes 60 minutes The logic for the thermal overload protection element is shown below. Figure 5–110: THERMAL OVERLOAD PROTECTION SCHEME LOGIC GE Multilin L30 Line Current Differential System 5-233...
  • Page 370: Contact Inputs

    The DC input voltage is compared to a user-settable threshold. A new contact input state must be maintained for a user- settable debounce time in order for the L30 to validate the new contact state. In the figure below, the debounce time is set at 2.5 ms;...
  • Page 371 Event Records menu, make the following settings changes: "Breaker Closed (52b)" CONTACT INPUT H5A ID: "Enabled" CONTACT INPUT H5A EVENTS: Note that the 52b contact is closed when the breaker is open and open when the breaker is closed. GE Multilin L30 Line Current Differential System 5-235...
  • Page 372: Virtual Inputs

    FlexLogic equation, it will likely have to be lengthened NOTE in time. A FlexLogic timer with a delayed reset can perform this function. Figure 5–112: VIRTUAL INPUTS SCHEME LOGIC 5-236 L30 Line Current Differential System GE Multilin...
  • Page 373: Contact Outputs

    The most dependable protection of the initiating contact is provided by directly measuring current in the tripping circuit, and using this parameter to control resetting of the initiating relay. This scheme is often called trip seal-in. This can be realized in the L30 using the FlexLogic operand to seal-in the contact output as follows: CONT OP 1 ION “Cont Op 1"...
  • Page 374 5 SETTINGS The L30 latching output contacts are mechanically bi-stable and controlled by two separate (open and close) coils. As such they retain their position even if the relay is not powered up. The relay recognizes all latching output contact cards and pop- ulates the setting menu accordingly.
  • Page 375: Virtual Outputs

    Logic equations. Any change of state of a virtual output can be logged as an event if programmed to do so. For example, if Virtual Output 1 is the trip signal from FlexLogic and the trip relay is used to signal events, the settings would be programmed as follows: GE Multilin L30 Line Current Differential System 5-239...
  • Page 376: Remote Devices

    NOTE c) LOCAL DEVICES: DEVICE ID FOR TRANSMITTING GSSE MESSAGES In a L30 relay, the device ID that represents the IEC 61850 GOOSE application ID (GoID) name string sent as part of each GOOSE message is programmed in the ...
  • Page 377 5 SETTINGS 5.8 INPUTS AND OUTPUTS In L30 releases previous to 5.0x, these name strings were represented by the setting. RELAY NAME GE Multilin L30 Line Current Differential System 5-241...
  • Page 378: Remote Inputs

    This setting identifies the Ethernet application identification in the GOOSE message. It should match the corre- sponding settings on the sending device. setting provides for the choice of the L30 fixed (DNA/UserSt) dataset (that is, containing REMOTE DEVICE 1 DATASET DNA and UserSt bit pairs), or one of the configurable datasets.
  • Page 379: Remote Double-Point Status Inputs

    REMOTE OUTPUTS DNA BIT PAIRS REMOTE OUTPUTS DNA- 1(32) BIT PAIR Range: FlexLogic operand  REMOTE OUTPUTS DNA- 1 OPERAND:  DNA- 1 BIT PAIR Range: Disabled, Enabled DNA- 1 EVENTS: MESSAGE Disabled GE Multilin L30 Line Current Differential System 5-243...
  • Page 380: Direct Inputs And Outputs

    DIRECT INPUTS Range: Off, On  DIRECT INPUTS DIRECT INPUT 1-1  DEFAULT: Off Range: Off, On DIRECT INPUT 1-2 MESSAGE DEFAULT: Off ↓ Range: Off, On DIRECT INPUT 1-8 MESSAGE DEFAULT: Off 5-244 L30 Line Current Differential System GE Multilin...
  • Page 381 FlexLogic operand. The setting above is used to select the operand which represents a specific function (as selected by the user) to be transmitted. Direct outputs 2-1 to 2-8 are only functional on three-terminal systems. NOTE GE Multilin L30 Line Current Differential System 5-245...
  • Page 382 L90 communication channel (same for 1-2...1-8) (87L is Enabled) SETTING DIRECT OUTPUT 1-1: FLEXLOGIC OPERAND (same for 1-2...1-8) Fail DIRECT I/P 1-1 Off (Flexlogic Operand) (same for 1-2...1-8) 831024A1.CDR Figure 5–113: DIRECT INPUTS/OUTPUTS LOGIC 5-246 L30 Line Current Differential System GE Multilin...
  • Page 383: Resetting

    GOOSE ANALOG 1 PU: This setting specifies the per-unit base factor when using the GOOSE analog input FlexAna- log values in other L30 features, such as FlexElements. The base factor is applied to the GOOSE analog input FlexAn- alog quantity to normalize it to a per-unit quantity. The base units are described in the following table.
  • Page 384: Iec 61850 Goose Integers

    = maximum primary RMS value of all the sources related to the +IN and –IN inputs BASE (Max Delta Volts) The GOOSE analog input FlexAnalog values are available for use in other L30 functions that use FlexAnalog values. 5.8.12 IEC 61850 GOOSE INTEGERS ...
  • Page 385: Dcma Inputs

    –20 to +180 MW; in this case the value would be “–20” and the DCMA INPUT H1 MIN VALUE DCMA INPUT H1 MAX value “180”. Intermediate values between the min and max values are scaled linearly. VALUE GE Multilin L30 Line Current Differential System 5-249...
  • Page 386: Rtd Inputs

    1.5 pu. FlexElement operands are available to FlexLogic for further interlocking or to operate an output contact directly. Refer to the following table for reference temperature values for each RTD type. 5-250 L30 Line Current Differential System GE Multilin...
  • Page 387 168.47 280.77 233.97 16.00 172.46 291.96 243.30 16.39 175.84 303.46 252.88 16.78 179.51 315.31 262.76 17.17 183.17 327.54 272.94 17.56 186.82 340.14 283.45 17.95 190.45 353.14 294.28 18.34 194.08 366.53 305.44 18.73 GE Multilin L30 Line Current Differential System 5-251...
  • Page 388: Dcma Outputs

    – MAX VAL MIN VAL MAX VAL < 0.1 pu. The resulting characteristic is illustrated in the following figure. DRIVING SIGNAL MIN VAL MAX VAL 842739A1.CDR Figure 5–114: DCMA OUTPUT CHARACTERISTIC 5-252 L30 Line Current Differential System GE Multilin...
  • Page 389 The CT ratio is 5000:5 and the maximum load current is 4200 A. The current should be monitored from 0 A upwards, allow- ing for 50% overload. The phase current with the 50% overload margin is: GE Multilin L30 Line Current Differential System 5-253...
  • Page 390 1.27 kV – • ±0.5% of reading For example, under nominal conditions, the positive-sequence reads 230.94 kV and the worst-case error is 0.005 x 230.94 kV + 1.27 kV = 2.42 kV. 5-254 L30 Line Current Differential System GE Multilin...
  • Page 391: Test Mode

    TEST MODE FORCING: MESSAGE The L30 provides a test facility to verify the functionality of contact inputs and outputs, some communication channels and the phasor measurement unit (where applicable), using simulated conditions. The test mode is indicated on the relay face- plate by a Test Mode LED indicator.
  • Page 392: Force Contact Inputs

    Following a restart, power up, settings TEST MODE FUNCTION upload, or firmware upgrade, the test mode will remain at the last programmed value. This allows a L30 that has been placed in isolated mode to remain isolated during testing and maintenance activities. On restart, the TEST MODE FORCING setting and the force contact input and force contact output settings all revert to their default states.
  • Page 393: Force Contact Outputs

    PUSHBUTTON 1 FUNCTION input 1 to initiate the Test mode, make the following changes in the menu:   SETTINGS TESTING TEST MODE “Enabled” and “ ” TEST MODE FUNCTION: TEST MODE INITIATE: GE Multilin L30 Line Current Differential System 5-257...
  • Page 394: Channel Tests

    Range: 0.000 to 9.999 kA in steps of 0.001 PMU 1 IA TEST MESSAGE MAGNITUDE: 1.000 kA Range: –180.00 to 180.00° in steps of 0.05 PMU 1 IA TEST MESSAGE ANGLE: –10.00° 5-258 L30 Line Current Differential System GE Multilin...
  • Page 395 In test mode, the following actions take place: a. The Data Invalid / Test Mode bit (bit 15 in the STAT word) is set. b. The Sim bit in all output datasets is set. GE Multilin L30 Line Current Differential System 5-259...
  • Page 396 5.10 TESTING 5 SETTINGS 5-260 L30 Line Current Differential System GE Multilin...
  • Page 397: Actual Values Menu

    See page 6-10.  REMAINING CONNECT  PRP See page 6-10.   ACTUAL VALUES  87L DIFFERENTIAL See page 6-14.  METERING  CURRENT  SOURCE SRC 1 See page 6-15.  GE Multilin L30 Line Current Differential System...
  • Page 398  PMU RECORDS See page 6-23.   MAINTENANCE See page 6-24.   ACTUAL VALUES  MODEL INFORMATION See page 6-25.  PRODUCT INFO   FIRMWARE REVISIONS See page 6-25.  L30 Line Current Differential System GE Multilin...
  • Page 399: Contact Inputs

    The state displayed will be that of the remote point unless the remote device has been established to be “Offline” in which case the value shown is the programmed default state for the remote input. GE Multilin L30 Line Current Differential System...
  • Page 400: Remote Double-Point Status Inputs

    Range: On, Off, VOff, VOn, IOn, IOff  CONTACT OUTPUTS Cont Op 1  Range: On, Off, VOff, VOn, IOn, IOff Cont Op 2 MESSAGE ↓ Range: On, Off, VOff, VOn, IOn, IOff Cont Op xx MESSAGE L30 Line Current Differential System GE Multilin...
  • Page 401: Virtual Outputs

    The present state of the programmed remote devices is shown here. The message indicates ALL REMOTE DEVICES ONLINE whether or not all programmed remote devices are online. If the corresponding state is "No", then at least one required remote device is not online. GE Multilin L30 Line Current Differential System...
  • Page 402: Channel Tests

    Range: n/a, FAIL, OK VALIDITY OF CHANNEL MESSAGE CONFIGURATION: n/a Range: n/a, FAIL, OK PFLL MESSAGE STATUS: n/a The status information for two channels is shown here. A brief description of each actual value is below: L30 Line Current Differential System GE Multilin...
  • Page 403: Digital Counters

      PATH: ACTUAL VALUES STATUS SELECTOR SWITCHES Range: Current Position / 7  SELECTOR SWITCHES SELECTOR SWITCH 1  POSITION: 0/7 Range: Current Position / 7 SELECTOR SWITCH 2 MESSAGE POSITION: 0/7 GE Multilin L30 Line Current Differential System...
  • Page 404: Flex States

    UINT INPUT 16 MESSAGE The L30 Line Current Differential System is provided with optional IEC 61850 communications capability. This feature is specified as a software option at the time of ordering. Refer to the Ordering section of chap- ter 2 for additional details.
  • Page 405: Real Time Clock Synchronizing

    PTP-— IRIG-B DELTA being received via PTP and that being received via IRIG-B. A positive value indicates that PTP time is fast compared to IRIG-B time. GE Multilin L30 Line Current Differential System...
  • Page 406: Remaining Connection Status

    LAN ID in the frame do not match). is a counter for total messages received with an error on Port B (PRP frame, but port received through MISMATCHES PORT B and LAN ID in the frame do not match). 6-10 L30 Line Current Differential System GE Multilin...
  • Page 407: Metering Conventions

    WATTS = Negative VARS = Positive PF = Lead PF = Lag PF = Lead Current UR RELAY 827239AC.CDR S=VI Generator Figure 6–1: FLOW DIRECTION OF SIGNED VALUES FOR WATTS AND VARS GE Multilin L30 Line Current Differential System 6-11...
  • Page 408 ABC phase rotation: • ACB phase rotation: -- - V -- - V -- - V -- - V -- - V -- - V The above equations apply to currents as well. 6-12 L30 Line Current Differential System GE Multilin...
  • Page 409 The power system voltages are phase-referenced – for simplicity – to VAG and VAB, respectively. This, however, is a relative matter. It is important to remember that the L30 displays are always referenced as specified under SETTINGS ...
  • Page 410: Differential Current

    The metered current values are displayed for all line terminals in fundamental phasor form. All angles are shown with respect to the reference common for all L30 devices; that is, frequency, source currents, and voltages. The metered pri- mary differential and restraint currents are displayed for the local relay.
  • Page 411: Sources

    0.000 0.0° SRC 1 PHASOR Ic: MESSAGE 0.000 0.0° SRC 1 PHASOR In: MESSAGE 0.000 0.0° SRC 1 ZERO SEQ I0: MESSAGE 0.000 0.0° SRC 1 POS SEQ I1: MESSAGE 0.000 0.0° GE Multilin L30 Line Current Differential System 6-15...
  • Page 412 RMS Vca: MESSAGE 0.00 SRC 1 PHASOR Vab: MESSAGE 0.000 0.0° SRC 1 PHASOR Vbc: MESSAGE 0.000 0.0° SRC 1 PHASOR Vca: MESSAGE 0.000 0.0° SRC 1 ZERO SEQ V0: MESSAGE 0.000 0.0° 6-16 L30 Line Current Differential System GE Multilin...
  • Page 413 APPARENT PWR MESSAGE 3φ: 0.000 SRC 1 APPARENT PWR MESSAGE φa: 0.000 SRC 1 APPARENT PWR MESSAGE φb: 0.000 SRC 1 APPARENT PWR MESSAGE φc: 0.000 SRC 1 POWER FACTOR MESSAGE 3φ: 1.000 GE Multilin L30 Line Current Differential System 6-17...
  • Page 414: Synchrocheck

    S = V x Î x Î x Î (EQ 6.1) When VTs are configured in delta, the L30 does not calculate power in each phase and three-phase power is measured as S = V x Î x Î (EQ 6.2)
  • Page 415: Tracking Frequency

    = maximum nominal primary RMS value of the +IN and –IN inputs BASE SYNCHROCHECK = maximum primary RMS value of all the sources related to the +IN and –IN inputs BASE (Max Delta Volts) GE Multilin L30 Line Current Differential System 6-19...
  • Page 416: Iec 61580 Goose Analog Values

    MESSAGE 0.000 The L30 Line Current Differential System is provided with optional IEC 61850 communications capability. This feature is specified as a software option at the time of ordering. Refer to the Ordering section of chap- ter 2 for additional details.
  • Page 417: Pmu Aggregator

    RTD INPUT xx  -50 °C Actual values for each RTD input channel that is enabled are displayed with the top line as the programmed channel ID and the bottom line as the value. GE Multilin L30 Line Current Differential System 6-21...
  • Page 418: Fault Reports

    COMMANDS CLEAR RECORDS Only major output operands generate events, not every operand. Elements that assert output per phase, for example, log operating phase output only without asserting the common three-phase operand event. 6-22 L30 Line Current Differential System GE Multilin...
  • Page 419: Oscillography

     RECORDING The number of triggers applicable to the phasor measurement unit recorder is indicated by the value. NUMBER OF TRIGGERS The status of the phasor measurement unit recorder is indicated as follows: GE Multilin L30 Line Current Differential System 6-23...
  • Page 420: Breaker Maintenance

    BKR 1 ARCING AMP  menu for clearing breaker arcing current records. The COMMANDS CLEAR RECORDS BREAKER OPERATING TIME defined as the slowest operating time of breaker poles that were initiated to open. 6-24 L30 Line Current Differential System GE Multilin...
  • Page 421: Model Information

    6.5PRODUCT INFORMATION 6.5.1 MODEL INFORMATION   PATH: ACTUAL VALUES PRODUCT INFO MODEL INFORMATION Range: standard GE Multilin order code format;  MODEL INFORMATION ORDER CODE LINE 1: example order code shown  L30-E00-HCH-F8F-H6A Range: standard GE Multilin order code format...
  • Page 422 6.5 PRODUCT INFORMATION 6 ACTUAL VALUES The shown data is illustrative only. A modification file number of 0 indicates that, currently, no modifications have been installed. 6-26 L30 Line Current Differential System GE Multilin...
  • Page 423: Virtual Inputs

    The states of up to 64 virtual inputs are changed here. The first line of the display indicates the ID of the virtual input. The second line indicates the current or selected status of the virtual input. This status will be a state off (logic 0) or on (logic 1). GE Multilin L30 Line Current Differential System...
  • Page 424: Clear Records

    The complete date, as a minimum, must be entered to allow execution of this command. The new time (if entered) and date will take effect at the moment the ENTER key is clicked. The timescale of the entered time should be local time, including daylight time where and when applicable. L30 Line Current Differential System GE Multilin...
  • Page 425: Relay Maintenance

    Various self-checking diagnostics are performed in the background while the L30 is running, and diagnostic information is stored on the non-volatile memory from time to time based on the self-checking result. Although the diagnostic information is cleared before the L30 is shipped from the factory, the user may want to clear the diagnostic information for themselves under certain circumstances.
  • Page 426: Phasor Measurement Unit One-Shot

    The high-accuracy high-sampling rate record of the two signals captured by the scope can be processed using digital tools to verify the magnitude and phase angle with respect to the time reference signal. As both the time reference and the mea- L30 Line Current Differential System GE Multilin...
  • Page 427: Security

    Operator Logoff: Selecting ‘Yes’ allows the Supervisor to forcefully logoff an operator session. • Clear Security Data: Selecting ‘Yes’ allows the Supervisor to forcefully clear all the security logs and clears all the operands associated with the self-tests. GE Multilin L30 Line Current Differential System...
  • Page 428: Targets Menu

     MESSAGE Each L30 element with a TARGET setting has a target message that when activated by its element is displayed in sequence with any other currently active target messages in the menu. In the example shown, the Phase TOC4 TARGETS and Digital Element 48 target settings are active and so have their targets displayed.
  • Page 429 Contact Factory (xxx) • Latched target message: Yes. • Description of problem: One or more installed hardware modules is not compatible with the L30 order code. • How often the test is performed: Module dependent. • What to do: Contact the factory and supply the failure code noted in the display. The “xxx” text identifies the failed mod- ule (for example, F8L).
  • Page 430 • What to do: Verify that all the items in the GOOSE data set are supported by the L30. The EnerVista UR Setup soft- ware will list the valid items. An IEC61850 client will also show which nodes are available for the L30.
  • Page 431 How often the test is performed: Upon initiation of a contact output state change. • What to do: Verify the state of the output contact and contact the factory if the problem persists. GE Multilin L30 Line Current Differential System...
  • Page 432 Description of problem: The ambient temperature is greater than the maximum operating temperature (+80°C). • How often the test is performed: Every hour. • What to do: Remove the L30 from service and install in a location that meets operating temperature standards. UNEXPECTED RESTART: Press “RESET” key •...
  • Page 433 If this message appears, contact the factory and supply the failure code noted in the display. Text in the message identifies the failed module (for example, H81). If operated on a Process Card failure, the Module Fail self-test seals-in (latches) till the UR-series device is restarted. GE Multilin L30 Line Current Differential System 7-11...
  • Page 434 Brick output failing to respond to an output command can only be detected while the command is active, and so in this case the target is latched. A latched target can be unlatched by pressing the faceplate reset key if the command has ended, however the output may still be non-functional. 7-12 L30 Line Current Differential System GE Multilin...
  • Page 435: L30 Design

    The second major technical consideration is the restraint characteristic, which is the decision boundary between situations that are declared to be a fault and those that are not. The L30 uses an innovative adaptive decision process based on an on-line computation of the sources of measurement error. In this adaptive approach, the restraint region is an ellipse with variable major axis, minor axis, and orientation.
  • Page 436: Removal Of Decaying Offset

    Since the sampling clocks are synchronized, the time stamp is simply a sequence number. L30 Line Current Differential System GE Multilin...
  • Page 437: Disturbance Detection

    CT saturation is detected (see CT Saturation Detection for details); is an adaptive restraint term (see Online Estimate Of Measurement Error for details) LOC_ADA_A The squared restraining current is calculated as a sum of squared local and all remote restraints: GE Multilin L30 Line Current Differential System...
  • Page 438: Ground Differential Element

    The line ground differential function allows sensitive ground protection for single-line to-ground faults, allowing the phase differential element to be set higher (above load) to provide protection for multi-phase faults. The L30 ground differential function calculates ground differential current from all terminal phase currents. The maximum phase current is used for the restraint.
  • Page 439: Clock Synchronization

    In all cases, an estimate of phase error is computed and used to automatically adapt the restraint region to compensate. Frequency tracking is provided that will accommodate any fre- quency shift normally encountered in power systems. GE Multilin L30 Line Current Differential System...
  • Page 440: Frequency Tracking And Phase Locking

    GPS (Global Positioning System) to compensate for the channel delay asymmetry. This feature requires a GPS receiver to provide a GPS clock signal to the L30. With this option there are two clocks as each terminal: a local sampling clock and a local GPS clock.
  • Page 441: Frequency Detection

    Current measurements can generally provide the most accurate information, but are not always available and may contain large errors during faults or switching transients. Time stamped messages are GE Multilin L30 Line Current Differential System...
  • Page 442 256 to the round trip and add 128 to the phase angle. Also, if the above equations are computed using integer values of time stamps, a conversion to phase angle in radians is required by multiplying by π / 32. L30 Line Current Differential System GE Multilin...
  • Page 443 ( T1 T2 T2 T1 ) i -3, i-2, i -1, δ θ Calculate 1, 1. Speed up Slow down 831729A2.CDR Figure 8–2: ROUND TRIP DELAY AND CLOCK OFFSET COMPUTATION FROM TIME STAMPS GE Multilin L30 Line Current Differential System...
  • Page 444: Phase Locking Filter

    T = the time between execution of the filter algorithm repeat = time constant for the primary phase locked loop phase = time constant for the frequency locked loop frequency 8-10 L30 Line Current Differential System GE Multilin...
  • Page 445: Matching Phaselets

    A 6 Mhz clock with a 16-bit hardware counter is adequate, provided the method is used for achieving the 32-bit resolu- tion that is described in this document. • An 8-bit time stamp is adequate provided time stamp messages are exchanged once per cycle. • A 4-bit message sequence number is adequate. GE Multilin L30 Line Current Differential System 8-11...
  • Page 446: Online Estimate Of Measurement Errors

    1_ADA_A 1_A k ( ) 1_MAG_A Another source of the measurement errors is clock synchronization error, resulting in a clock uncertainty term. The L30 algorithm accounts for two terms of synchronization error corresponding to: • Raw clock deviation computed from time stamps. There are several effects that cause it to not track exactly. First, the ping-pong algorithm inherently produces slightly different estimates of clock deviation at each terminal.
  • Page 447: Ct Saturation Detection

    For short transmission lines the charging current is a small factor and can therefore be treated as an unknown error. In this application the L30 can be deployed with- out voltage sensors and the line charging current is included as a constant term in the total variance, increasing the differ- ential restraint current.
  • Page 448: Differential Element Characteristics

    The L30 incorporates an adaptive differential algorithm based on the traditional percent differential principle. In the tradi- tional percent differential scheme, the operating parameter is based on the phasor sum of currents in the zone and the restraint parameter is based on the scalar (or average scalar) sum of the currents in the protected zone - when the operat- ing parameter divided by the restraint parameter is above the slope setting, the relay will operate.
  • Page 449: Relay Synchronization

    8.1 OVERVIEW The major difference between the L30 differential scheme and a percent differential scheme is the use of an estimate of errors in the input currents to increase the restraint parameter during faults, permitting the use of more sensitive settings than those used in the traditional scheme.
  • Page 450: Description

    8.2OPERATING CONDITION CHARACTERISTICS 8.2.1 DESCRIPTION Characteristics of differential elements can be shown in the complex plane. The operating characteristics of the L30 are fundamentally dependant on the relative ratios of the local and remote current phasor magnitudes and the angles of as shown in the Restraint Characteristics figure.
  • Page 451 8 THEORY OF OPERATION 8.2 OPERATING CONDITION CHARACTERISTICS Figure 8–7: RESTRAINT CHARACTERISTICS GE Multilin L30 Line Current Differential System 8-17...
  • Page 452: Trip Decision Example

    Current differential section of chapter 5. The following figure shows how the L30 settings affect the restraint characteristics. The local and remote currents are 180° apart, which represents an external fault. The breakpoint between the two slopes indicates the point where the restraint area is becoming wider to override uncertainties from CT saturation, fault noise, harmonics, etc.
  • Page 453 8 THEORY OF OPERATION 8.2 OPERATING CONDITION CHARACTERISTICS loc pu OPERATE RESTRAINT BP=8, P=2, S1=30%, S2=50% BP=4, P=1, S1=30%, S2=50% BP=4, P=1, S1=20%, S2=40% OPERATE rem pu 831725A1.CDR Figure 8–8: SETTINGS IMPACT ON RESTRAINT CHARACTERISTIC GE Multilin L30 Line Current Differential System 8-19...
  • Page 454: Description

    Depending on the fault type, appropriate voltage and current signals are selected from the phase quantities before applying the two equations above (the superscripts denote phases, the subscripts denote stations). For AG faults: ⋅ (EQ 8.43) 8-20 L30 Line Current Differential System GE Multilin...
  • Page 455 -- - V (EQ 8.50) – – SYS0 -- - V – – SYS0 where Z is the equivalent zero-sequence impedance behind the relay as entered under the fault report setting menu. SYS0 GE Multilin L30 Line Current Differential System 8-21...
  • Page 456 FAULT FAULT LOCATION 3I_0 LOCATOR 1 FAULT# RECLOSE SHOT VA or VAB VB or VBC VC or VCA Vn or V_0 SHOT # FROM 827094A5.CDR AUTO RECLOSURE Figure 8–10: FAULT LOCATOR SCHEME 8-22 L30 Line Current Differential System GE Multilin...
  • Page 457: Introduction

    Practically, it is difficult to meet this criteria and avoid saturation completely. The L30 provides several means to ensure security during an external fault, including dual-slope restraint characteristics, adaptive restraint, and CT saturation mechanism, allowing the relay to be secure during severe external faults, while maintaining excellent performance for internal faults.
  • Page 458: Ct Saturation Analysis Tool

    9.1.2 CT SATURATION ANALYSIS TOOL The CT saturation analysis tool is an Excel spreadsheet provided for users to analyze the L30 reliability during CT satura- tion caused by an external fault, to investigate the effect of adjusting 87L settings, and to examine the possibility of reducing the CT requirement.
  • Page 459 You are encouraged to test different fault locations and different fault levels and distributions per short circuit studies. Alter- natively, the tool can help to estimate required CT parameters (ratio and knee point voltage), based on some pre-deter- mined criteria. GE Multilin L30 Line Current Differential System...
  • Page 460: Introduction

    9.2CURRENT DIFFERENTIAL (87L) SETTINGS 9.2.1 INTRODUCTION Software is available from the GE Digital Energy website that is helpful in selecting settings for the specific applica- tion. Checking the performance of selected element settings with respect to known power system fault parameters makes it relatively simple to choose the optimum settings for the application.
  • Page 461: Ct Tap

    For relay 1, channel 1 communicates to relay 2 and channel 2 communicates to relay 3 • For relay 2, channel 1 communicates to relay 1 and channel 2 communicates to relay 3 GE Multilin L30 Line Current Differential System...
  • Page 462 This satisfies the equality condition indicated earlier. During on-load tests, the differential current at all terminals should be the same and generally equal to the charging current if the tap and CT ratio settings are chosen correctly. L30 Line Current Differential System GE Multilin...
  • Page 463: Description

    If GPS is enabled at all terminals and the GPS signal is present, the L30 compensates for the channel asymmetry. On the loss of the GPS signal, the L30 stores the last measured value of the channel asymmetry per channel and compensates for the asymmetry until the GPS clock is available.
  • Page 464: Compensation Method 2

    Create FlexLogic similar to that shown below to switch the 87L element to Settings Group 2 (with most sensitive set- tings) if the L30 has a valid GPS time reference. If a GPS or 87L communications failure occurs, the L30 will switch back to Settings Group 1 with less sensitive settings.
  • Page 465 Set the 87L element with different differential settings for Settings Groups 1 and 2 as shown below Enable GPS compensation when the GPS signal is valid and switch to Settings Group 2 (with more sensitive settings) as shown below. GE Multilin L30 Line Current Differential System...
  • Page 466: Instantaneous Element Error During L30 Synchronization

    9.4.1 INSTANTANEOUS ELEMENT ERROR DURING L30 SYNCHRONIZATION As explained in the Theory of Operation chapter, two or three L30 relays are synchronized to each other and to system fre- quency to provide digital differential protection and accurate measurements for other protection and control functions.
  • Page 467: Channel Testing

    G.703, and RS422. The speed is 64 Kbaud in a transparent synchronous mode with automatic synchronous character detection and CRC insertion. The Local Loopback Channel Test verifies the L30 communication modules are working properly. The Remote Loopback –4 Channel Test verifies the communication link between the relays meets requirements (BER less than 10 ).
  • Page 468: Clock Synchronization Tests

    “OK” ACTUAL VALUES STATUS CHANNEL TESTS CHANNEL 1(2) STATUS:    “n/a” ACTUAL VALUES STATUS CHANNEL TESTS REMOTE LOOPBACK STATUS:    “OK” ACTUAL VALUES STATUS CHANNEL TESTS PFLL STATUS: 10-2 L30 Line Current Differential System GE Multilin...
  • Page 469: Current Differential

    Download the UR Test software from the GE Digital Energy website (http://www.gedigitalenergy.com/products/sup- port/ur/l90test.zip) or contact GE Digital Energy for information about the UR current differential test program which allows the user to simulate different operating conditions for verifying correct responses of the relays during com- NOTE missioning activities.
  • Page 470: Local-Remote Relay Tests

    These phasors and differential currents can be monitored at the ACTUAL VAL-   menu where all current magnitudes and angles can be observed and con- METERING 87L DIFFERENTIAL CURRENT clusions of proper relay interconnections can be made. 10-4 L30 Line Current Differential System GE Multilin...
  • Page 471: Replace A Module

    The enhanced faceplate can be opened to the left, once the thumb screw has been removed, as shown below. This allows for easy accessibility of the modules for withdrawal. The new wide-angle hinge assembly in the enhanced front panel opens completely and allows easy access to all modules in the L30. 842812A1.CDR Figure 11–1: UR MODULE WITHDRAWAL AND INSERTION (ENHANCED FACEPLATE)
  • Page 472 When the clips have locked into position, the module will be fully inserted. CPU connections must be individually disconnected from the module before the module can be removed from the chassis. NOTE NOTE 11-2 L30 Line Current Differential System GE Multilin...
  • Page 473: Replace Battery

    10. Reinstall the battery clip and the metal cover, and reinsert the power supply module into the unit. 11. Power on the unit. 12. Dispose of the old battery as outlined in the next section. GE Multilin L30 Line Current Differential System 11-3...
  • Page 474: Dispose Of Battery

    La batterie est marqué de ce symbole, qui comprennent les indications cadmium (Cd), plomb (Pb), ou mercure (Hg). Pour le recyclage, retourner la batterie à votre fournisseur ou à un point de collecte. Pour plus d'informations, voir: www.recyclethis.info. 11-4 L30 Line Current Differential System GE Multilin...
  • Page 475 Baterija je označena s tem simbolom, ki lahko vključuje napise, ki označujejo kadmij (Cd), svinec (Pb) ali živo srebro (Hg). Za ustrezno recikliranje baterijo vrnite dobavitelju ali jo odstranite na določenem zbirališču. Za več informacij obiščite spletno stran: www.recyclethis.info. GE Multilin L30 Line Current Differential System 11-5...
  • Page 476 North America 905-294-6222 Latin America +55 11 3614 1700 Europe, Middle East, Africa +(34) 94 485 88 00 Asia +86-21-2401-3208 India +91 80 41314617 From GE Part Number 1604-0021-A1, GE Publication Number GEK-113574 11-6 L30 Line Current Differential System GE Multilin...
  • Page 477: Uninstall And Clear Files And Data

    Other files can be in standard formats, such as COMTRADE or .csv. You cannot erase directly the flash memory, but all records and settings in that memory can be deleted. Do this using the   command. SETTINGS PRODUCT SETUP CLEAR RELAY RECORDS GE Multilin L30 Line Current Differential System 11-7...
  • Page 478: Repairs

    Customers are responsible for shipping costs to the factory, regardless of whether the unit is under warranty. • Fax a copy of the shipping information to the GE Digital Energy service department in Canada at +1 905 927 5098. Use the detailed return procedure outlined at https://www.gedigitalenergy.com/multilin/support/ret_proc.htm...
  • Page 479: Storage

    Store the unit indoors in a cool, dry place. If possible, store in the original packaging. Follow the storage temperature range outlined in the Specifications. To avoid deterioration of electrolytic capacitors, power up units that are stored in a de-energized state once per year, for one hour continuously. GE Multilin L30 Line Current Differential System 11-9...
  • Page 480: Disposal

    European Union, dispose of the battery as outlined earlier. To prevent non-intended use of the unit, remove the modules as outlined earlier, dismantle the unit, and recycle the metal when possible. 11-10 L30 Line Current Differential System GE Multilin...
  • Page 481: A.1.1 Flexanalog Items

    SRC 1 I_2 Angle Degrees Source 1 negative-sequence current angle 6178 SRC 1 Igd Mag Amps Source 1 differential ground current magnitude 6180 SRC 1 Igd Angle Degrees Source 1 differential ground current angle GE Multilin L30 Line Current Differential System...
  • Page 482 6691 SRC 1 V_0 Mag Volts Source 1 zero-sequence voltage magnitude 6693 SRC 1 V_0 Angle Degrees Source 1 zero-sequence voltage angle 6694 SRC 1 V_1 Mag Volts Source 1 positive-sequence voltage magnitude L30 Line Current Differential System GE Multilin...
  • Page 483 SRC 1 Phase B PF Source 1 phase B power factor 7195 SRC 1 Phase C PF Source 1 phase C power factor 7200 SRC 2 P Watts Source 2 three-phase real power GE Multilin L30 Line Current Differential System...
  • Page 484 Synchrocheck 1 delta voltage 9218 Synchchk 1 Delta F Synchrocheck 1 delta frequency 9219 Synchchk 1 Delta Phs Degrees Synchrocheck 1 delta phase 9220 Synchchk 2 Delta V Volts Synchrocheck 2 delta voltage L30 Line Current Differential System GE Multilin...
  • Page 485 Rest Curr IG Amps Restraint current IG 9400 Local IG Mag Amps Local IG magnitude 9405 Local IG Angle Degrees Local IG angle 9406 Terminal 1 IG Mag Amps Remote 1 IG magnitude GE Multilin L30 Line Current Differential System...
  • Page 486 DCmA input 6 actual value 13516 DCmA Inputs 7 Value DCmA input 7 actual value 13518 DCmA Inputs 8 Value DCmA input 8 actual value 13520 DCmA Inputs 9 Value DCmA input 9 actual value L30 Line Current Differential System GE Multilin...
  • Page 487 RTD input 29 actual value 13581 RTD Inputs 30 Value RTD input 30 actual value 13582 RTD Inputs 31 Value RTD input 31 actual value 13583 RTD Inputs 32 Value RTD input 32 actual value GE Multilin L30 Line Current Differential System...
  • Page 488 45610 GOOSE Analog In 14 IEC 61850 GOOSE analog input 14 45612 GOOSE Analog In 15 IEC 61850 GOOSE analog input 15 45614 GOOSE Analog In 16 IEC 61850 GOOSE analog input 16 L30 Line Current Differential System GE Multilin...
  • Page 489: A.1.2 Flexinteger Items

    IEC61850 GOOSE UInteger input 13 9994 GOOSE UInt Input 14 IEC61850 GOOSE UInteger input 14 9996 GOOSE UInt Input 15 IEC61850 GOOSE UInteger input 15 9998 GOOSE UInt Input 16 IEC61850 GOOSE UInteger input 16 GE Multilin L30 Line Current Differential System...
  • Page 490 A.1 PARAMETER LISTS APPENDIX A A-10 L30 Line Current Differential System GE Multilin...
  • Page 491: B.1.1 Introduction

    See the Supported Function Codes section for details. An exception response from the slave is indicated by set- ting the high order bit of the function code in the response packet. See the Exception Responses section for further details. GE Multilin L30 Line Current Differential System...
  • Page 492: B.1.4 Modbus Rtu Crc-16 Algorithm

    This algorithm requires the characteristic polynomial to be reverse bit ordered. The most significant bit of the characteristic polynomial is dropped, since it does not affect the value of the remainder. A C programming language implementation of the CRC algorithm will be provided upon request. L30 Line Current Differential System GE Multilin...
  • Page 493 No: go to 8; Yes: G (+) A --> A and continue. Is j = 8? No: go to 5; Yes: continue i + 1 --> i Is i = N? No: go to 3; Yes: continue A --> CRC GE Multilin L30 Line Current Differential System...
  • Page 494: B.2.1 Supported Function Codes

    NUMBER OF REGISTERS - low DATA #2 - high CRC - low DATA #2 - low CRC - high DATA #3 - high DATA #3 - low CRC - low CRC - high L30 Line Current Differential System GE Multilin...
  • Page 495: B.2.3 Execute Operation (Function Code 05H)

    DATA STARTING ADDRESS - low DATA STARTING ADDRESS - low DATA - high DATA - high DATA - low DATA - low CRC - low CRC - low CRC - high CRC - high GE Multilin L30 Line Current Differential System...
  • Page 496: B.2.5 Store Multiple Settings (Function Code 10H)

    PACKET FORMAT EXAMPLE (HEX) SLAVE ADDRESS SLAVE ADDRESS FUNCTION CODE FUNCTION CODE CRC - low order byte ERROR CODE CRC - high order byte CRC - low order byte CRC - high order byte L30 Line Current Differential System GE Multilin...
  • Page 497: B.3.1 Obtaining Relay Files Via Modbus

    Familiarity with the data logger feature is required to understand this description. Refer to the Data Logger section of Chap- ter 5 for details. To read the entire data logger in binary COMTRADE format, read the following files. GE Multilin L30 Line Current Differential System...
  • Page 498 “Number of Fault Reports' register. If the value changes, then the master reads all the new files. The contents of the file is in standard HTML notation and can be viewed via any commercial browser. L30 Line Current Differential System GE Multilin...
  • Page 499: B.4.1 Modbus Memory Map

    040E Virtual Input 15 State 0 to 1 F108 0 (Off) 040F Virtual Input 16 State 0 to 1 F108 0 (Off) 0410 Virtual Input 17 State 0 to 1 F108 0 (Off) GE Multilin L30 Line Current Differential System...
  • Page 500 -2147483647 to F004 2147483647 0804 Digital Counter 1 Frozen Time Stamp 0 to 4294967295 F050 0806 Digital Counter 1 Frozen Time Stamp us (microsecond part 0 to 4294967295 F003 of time stamp) B-10 L30 Line Current Differential System GE Multilin...
  • Page 501 0 to 65535 F500 1604 Field Shared Input Channel States 0 to 65535 F500 1605 Field Shared Input Test States 0 to 65535 F500 1606 Field Shared Output Operand States 0 to 65535 F500 GE Multilin L30 Line Current Differential System B-11...
  • Page 502 Source 1 Ground Current RMS 0 to 999999.999 0.001 F060 1816 Source 1 Ground Current Magnitude 0 to 999999.999 0.001 F060 1818 Source 1 Ground Current Angle -359.9 to 0 degrees F002 B-12 L30 Line Current Differential System GE Multilin...
  • Page 503 Source 1 Phase A Reactive Power -1000000000000 to 0.001 F060 1000000000000 1C0C Source 1 Phase B Reactive Power -1000000000000 to 0.001 F060 1000000000000 1C0E Source 1 Phase C Reactive Power -1000000000000 to 0.001 F060 1000000000000 GE Multilin L30 Line Current Differential System B-13...
  • Page 504 Fault 1 Prefault Phase C Voltage Angle -359.9 to 0 degrees F002 2352 Fault 1 Phase A Current Magnitude 0 to 999999.999 0.001 F060 2354 Fault 1 Phase A Current Angle -359.9 to 0 degrees F002 B-14 L30 Line Current Differential System GE Multilin...
  • Page 505 F002 24A0 Terminal 2 IC Angle -359.9 to 0 degrees F002 24A1 Differential Current IA Angle -359.9 to 0 degrees F002 24A2 Differential Current IB Angle -359.9 to 0 degrees F002 GE Multilin L30 Line Current Differential System B-15...
  • Page 506 PMU 1 Negative Sequence Current Angle -180 to 180 ° F002 2567 PMU 1 Zero Sequence Current Magnitude 0 to 999999.999 0.001 F060 2569 PMU 1 Zero Sequence Current Angle -180 to 180 ° F002 B-16 L30 Line Current Differential System GE Multilin...
  • Page 507 0 to 4294967295 F003 270A IEC 61850 Received uinteger 14 0 to 4294967295 F003 270C IEC 61850 Received uinteger 15 0 to 4294967295 F003 270E IEC 61850 Received uinteger 16 0 to 4294967295 F003 GE Multilin L30 Line Current Differential System B-17...
  • Page 508 Security (Read/Write) 328B Administrator Alphanumeric Password Entry F202 (none) Security (Read/Write Setting) 3295 Supervisor Alphanumeric Password Setting F202 (none) Security (Read Only) 329F Supervisor Alphanumeric Password Status 0 to 1 F102 0 (Disabled) B-18 L30 Line Current Differential System GE Multilin...
  • Page 509 Event Recorder (Read Only) 3400 Events Since Last Clear 0 to 4294967295 F003 3402 Number of Available Events 0 to 4294967295 F003 3404 Event Recorder Last Cleared Date 0 to 4294967295 F050 GE Multilin L30 Line Current Differential System B-19...
  • Page 510 °C F002 3507 RTD Input 24 Value -32768 to 32767 °C F002 3508 RTD Input 25 Value -32768 to 32767 °C F002 3509 RTD Input 26 Value -32768 to 32767 °C F002 B-20 L30 Line Current Differential System GE Multilin...
  • Page 511 0 (None) 3760 PTP GrandMaster ID 0 to 100 F073 3764 Real Time Clock Accuracy 0 to 999999999 F003 3766 PTP Port 1 State (3 items) 0 to 4 F625 0 (Disabled) GE Multilin L30 Line Current Differential System B-21...
  • Page 512 Field Contact Input 1 Input 1 to 18 F001 3908 Field Contact Input 1 Failsafe Value 0 to 1 F108 0 (Off) 3909 Field Contact Input 1 Debounce Time 0 to 16 F001 B-22 L30 Line Current Differential System GE Multilin...
  • Page 513 ...Repeated for Field Shared Input 6 3B36 ...Repeated for Field Shared Input 7 3B3F ...Repeated for Field Shared Input 8 3B48 ...Repeated for Field Shared Input 9 3B51 ...Repeated for Field Shared Input 10 GE Multilin L30 Line Current Differential System B-23...
  • Page 514 ...Repeated for Field Shared Output 12 3ECC ...Repeated for Field Shared Output 13 3ED9 ...Repeated for Field Shared Output 14 3EE6 ...Repeated for Field Shared Output 15 3EF3 ...Repeated for Field Shared Output 16 B-24 L30 Line Current Differential System GE Multilin...
  • Page 515 Command Password Access Timeout 5 to 480 F001 402B Setting Password Access Timeout 5 to 480 F001 402C Invalid Password Attempts (before lockout) 2 to 5 F001 402D Password Lockout Duration 5 to 60 F001 GE Multilin L30 Line Current Differential System B-25...
  • Page 516 0 to 3 F601 0 (RS485) 407E COM1 Minimum Response Time 0 to 1000 F001 407F COM2 Minimum Response Time 0 to 1000 F001 4080 Modbus Slave Address 1 to 254 F001 B-26 L30 Line Current Differential System GE Multilin...
  • Page 517 IEC 60870-5-104 Voltage Default Threshold 0 to 100000000 F003 30000 40E8 IEC 60870-5-104 Power Default Threshold 0 to 100000000 F003 30000 40EA IEC 60870-5-104 Energy Default Threshold 0 to 100000000 F003 30000 GE Multilin L30 Line Current Differential System B-27...
  • Page 518 DNP Available TCP/IP Connections 0 to 2 F001 4162 IEC Available TCP/IP Connections 0 to 2 F001 4163 MMS Available TCP/IP Connections 0 to 5 F001 4164 PMU Available TCP/IP Connections 0 to 4 F001 B-28 L30 Line Current Differential System GE Multilin...
  • Page 519 ...Repeated for User-Programmable LED 3 42C9 ...Repeated for User-Programmable LED 4 42CC ...Repeated for User-Programmable LED 5 42CF ...Repeated for User-Programmable LED 6 42D2 ...Repeated for User-Programmable LED 7 42D5 ...Repeated for User-Programmable LED 8 GE Multilin L30 Line Current Differential System B-29...
  • Page 520 4278190080 4374 IPv4 Network Route 1 Gateway 0 to 4294967295 F003 2130706433 4376 ...Repeated for Route 2 437C ...Repeated for Route 3 4382 ...Repeated for Route 4 4388 ...Repeated for Route 5 B-30 L30 Line Current Differential System GE Multilin...
  • Page 521 F001 4601 Phase Rotation 0 to 1 F106 0 (ABC) 4602 Frequency and Phase Reference 0 to 5 F167 0 (SRC 1) 4603 Frequency Tracking Function 0 to 1 F102 1 (Enabled) GE Multilin L30 Line Current Differential System B-31...
  • Page 522 ...Repeated for User-Definable Display 16 Field Unit Raw Data Actuals (Read Only) (8 modules) 4E00 Raw Field Data AC1 Mag 0 to 0.001 0.001 F003 4E02 Raw Field Data AC1 Angle 0 to 0.1 degree F002 B-32 L30 Line Current Differential System GE Multilin...
  • Page 523 ...Repeated for RTD Input 4 5450 ...Repeated for RTD Input 5 5464 ...Repeated for RTD Input 6 5478 ...Repeated for RTD Input 7 548C ...Repeated for RTD Input 8 54A0 ...Repeated for RTD Input 9 GE Multilin L30 Line Current Differential System B-33...
  • Page 524 ...Repeated for FlexLogic Timer 6 5830 ...Repeated for FlexLogic Timer 7 5838 ...Repeated for FlexLogic Timer 8 5840 ...Repeated for FlexLogic Timer 9 5848 ...Repeated for FlexLogic Timer 10 5850 ...Repeated for FlexLogic Timer 11 B-34 L30 Line Current Differential System GE Multilin...
  • Page 525 0 to 1 F122 0 (Phasor) 5B03 Neutral Time Overcurrent 1 Pickup 0 to 30 0.001 F001 1000 5B04 Neutral Time Overcurrent 1 Curve 0 to 16 F103 0 (IEEE Mod Inv) GE Multilin L30 Line Current Differential System B-35...
  • Page 526 CT Fail 1 Current Source 2 0 to 5 F167 1 (SRC 2) 5E72 CT Fail 1 Current Pickup 2 0 to 2 F001 5E73 CT Fail 1 Voltage Source 0 to 5 F167 0 (SRC 1) B-36 L30 Line Current Differential System GE Multilin...
  • Page 527 87L Current Differential External Key DTT 0 to 4294967295 F300 6010 87L Current Differential Target 0 to 2 F109 0 (Self-reset) 6011 87L Current Differential Event 0 to 1 F102 0 (Disabled) GE Multilin L30 Line Current Differential System B-37...
  • Page 528 Negative Sequence Instantaneous Overcurrent 1 Block 0 to 4294967295 F300 63C7 Negative Sequence Instantaneous Overcurrent 1 Target 0 to 2 F109 0 (Self-reset) 63C8 Negative Sequence Instantaneous Overcurrent 1 Events 0 to 1 F102 0 (Disabled) B-38 L30 Line Current Differential System GE Multilin...
  • Page 529 Neutral Directional Overcurrent 1 Function 0 to 1 F102 0 (Disabled) 7231 Neutral Directional Overcurrent 1 Source 0 to 5 F167 0 (SRC 1) 7232 Neutral Directional Overcurrent 1 Polarizing 0 to 2 F230 0 (Voltage) GE Multilin L30 Line Current Differential System B-39...
  • Page 530 ...Repeated for Disconnect Switch 8 Thermal Overload Protection (Read/Write Settings) (2 modules) 7788 Thermal Protection 1 Function 0 to 1 F102 0 (Disabled) 7789 Thermal Protection 1 Source 0 to 5 F167 0 (SRC 1) B-40 L30 Line Current Differential System GE Multilin...
  • Page 531 Phasor Measurement Unit One-shot Command (Read/Write Setting) 788C PMU One-shot Function 0 to 1 F102 0 (Disabled) 788D PMU One-shot Sequence Number 0 to 99 F001 788E PMU One-shot Time 0 to 235959 F050 GE Multilin L30 Line Current Differential System B-41...
  • Page 532 F300 Phasor Measurement Unit Current Trigger (Read/Write Setting) 7980 PMU 1 Current Trigger Function 0 to 1 F102 0 (Disabled) 7981 PMU 1 Current Trigger Pickup 0.1 to 30 0.001 F001 1800 B-42 L30 Line Current Differential System GE Multilin...
  • Page 533 ...Repeated for User Programmable Pushbutton 4 7C20 ...Repeated for User Programmable Pushbutton 5 7C50 ...Repeated for User Programmable Pushbutton 6 7C80 ...Repeated for User Programmable Pushbutton 7 7CB0 ...Repeated for User Programmable Pushbutton 8 GE Multilin L30 Line Current Differential System B-43...
  • Page 534 Breaker Failure 1 Three Pole Initiate 0 to 4294967295 F300 8607 Breaker Failure 1 Block 0 to 4294967295 F300 8609 Breaker Failure 1 Phase Amp Supv Pickup 0.001 to 30 0.001 F001 1050 B-44 L30 Line Current Differential System GE Multilin...
  • Page 535 ...Repeated for Digital Element 11 8AF2 ...Repeated for Digital Element 12 8B08 ...Repeated for Digital Element 13 8B1E ...Repeated for Digital Element 14 8B34 ...Repeated for Digital Element 15 8B4A ...Repeated for Digital Element 16 GE Multilin L30 Line Current Differential System B-45...
  • Page 536 FlexElement 1 Name F206 “FxE 1” 9004 FlexElement 1 InputP 0 to 65535 F600 9005 FlexElement 1 InputM 0 to 65535 F600 9006 FlexElement 1 Compare 0 to 1 F516 0 (LEVEL) B-46 L30 Line Current Differential System GE Multilin...
  • Page 537 ...Repeated for DCmA Output 15 93BA ...Repeated for DCmA Output 16 93C0 ...Repeated for DCmA Output 17 93C6 ...Repeated for DCmA Output 18 93CC ...Repeated for DCmA Output 19 93D2 ...Repeated for DCmA Output 20 GE Multilin L30 Line Current Differential System B-47...
  • Page 538 Selector 1 Bit0 0 to 4294967295 F300 A28A Selector 1 Bit1 0 to 4294967295 F300 A28C Selector 1 Bit2 0 to 4294967295 F300 A28E Selector 1 Bit Mode 0 to 1 F083 0 (Time-out) B-48 L30 Line Current Differential System GE Multilin...
  • Page 539 ...Repeated for Non-Volatile Latch 10 A778 ...Repeated for Non-Volatile Latch 11 A784 ...Repeated for Non-Volatile Latch 12 A790 ...Repeated for Non-Volatile Latch 13 A79C ...Repeated for Non-Volatile Latch 14 A7A8 ...Repeated for Non-Volatile Latch 15 GE Multilin L30 Line Current Differential System B-49...
  • Page 540 IEC 61850 LN Name Prefixes (Read/Write Settings) AB48 IEC 61850 Logical Node LPHD1 Name Prefix 0 to 65534 F206 (none) AB4B IEC 61850 Logical Node PIOCx Name Prefix (72 items) 0 to 65534 F206 (none) B-50 L30 Line Current Differential System GE Multilin...
  • Page 541 ...Repeated for IEC 61850 GGIO4 Analog Input 28 AFD4 ...Repeated for IEC 61850 GGIO4 Analog Input 29 AFDB ...Repeated for IEC 61850 GGIO4 Analog Input 30 AFE2 ...Repeated for IEC 61850 GGIO4 Analog Input 31 GE Multilin L30 Line Current Differential System B-51...
  • Page 542 IEC 61850 MMXU PF.phsB Deadband 1 0.001 to 100 0.001 F003 10000 B0F4 IEC 61850 MMXU PF.phsC Deadband 1 0.001 to 100 0.001 F003 10000 B0F6 ...Repeated for Deadband 2 B12C ...Repeated for Deadband 3 B-52 L30 Line Current Differential System GE Multilin...
  • Page 543 ...Repeated for module number 9 B38B ...Repeated for module number 10 B38E ...Repeated for module number 11 B391 ...Repeated for module number 12 B394 ...Repeated for module number 13 B397 ...Repeated for module number 14 GE Multilin L30 Line Current Differential System B-53...
  • Page 544 ...Repeated for module number 14 BAC0 ...Repeated for module number 15 BAE0 ...Repeated for module number 16 Contact Inputs (Read/Write Setting) (96 modules) BB00 Contact Input 1 Name F205 “Cont Ip 1“ B-54 L30 Line Current Differential System GE Multilin...
  • Page 545 ...Repeated for Contact Input 48 BC80 ...Repeated for Contact Input 49 BC88 ...Repeated for Contact Input 50 BC90 ...Repeated for Contact Input 51 BC98 ...Repeated for Contact Input 52 BCA0 ...Repeated for Contact Input 53 GE Multilin L30 Line Current Differential System B-55...
  • Page 546 Virtual Input 1 Events 0 to 1 F102 0 (Disabled) BE39 Reserved (3 items) F001 BE3C ...Repeated for Virtual Input 2 BE48 ...Repeated for Virtual Input 3 BE54 ...Repeated for Virtual Input 4 B-56 L30 Line Current Differential System GE Multilin...
  • Page 547 ...Repeated for Virtual Input 53 C0AC ...Repeated for Virtual Input 54 C0B8 ...Repeated for Virtual Input 55 C0C4 ...Repeated for Virtual Input 56 C0D0 ...Repeated for Virtual Input 57 C0DC ...Repeated for Virtual Input 58 GE Multilin L30 Line Current Differential System B-57...
  • Page 548 ...Repeated for Virtual Output 40 C270 ...Repeated for Virtual Output 41 C278 ...Repeated for Virtual Output 42 C280 ...Repeated for Virtual Output 43 C288 ...Repeated for Virtual Output 44 C290 ...Repeated for Virtual Output 45 B-58 L30 Line Current Differential System GE Multilin...
  • Page 549 C428 ...Repeated for Virtual Output 96 Mandatory (Read/Write Setting or Command) C430 Test Mode Function 0 to 2 F245 0 (Disabled) C431 Force VFD and LED 0 to 1 F126 0 (No) GE Multilin L30 Line Current Differential System B-59...
  • Page 550 Remote Device 1 in PMU Scheme 0 to 1 F126 0 (No) CB24 Reserved 0 to 3 F626 0 (None) CB25 ...Repeated for Device 2 CB4A ...Repeated for Device 3 CB6F ...Repeated for Device 4 B-60 L30 Line Current Differential System GE Multilin...
  • Page 551 Remote Output DNA 1 Operand 0 to 4294967295 F300 D222 Remote Output DNA 1 Events 0 to 1 F102 0 (Disabled) D223 Reserved 0 to 1 F001 D224 ...Repeated for Remote Output 2 GE Multilin L30 Line Current Differential System B-61...
  • Page 552 ...Repeated for Remote Output 16 D2E0 ...Repeated for Remote Output 17 D2E4 ...Repeated for Remote Output 18 D2E8 ...Repeated for Remote Output 19 D2EC ...Repeated for Remote Output 20 D2F0 ...Repeated for Remote Output 21 B-62 L30 Line Current Differential System GE Multilin...
  • Page 553 IEC 61850 GGIO2.CF.SPCSO39.ctlModel Value 0 to 2 F001 D347 IEC 61850 GGIO2.CF.SPCSO40.ctlModel Value 0 to 2 F001 D348 IEC 61850 GGIO2.CF.SPCSO41.ctlModel Value 0 to 2 F001 D349 IEC 61850 GGIO2.CF.SPCSO42.ctlModel Value 0 to 2 F001 GE Multilin L30 Line Current Differential System B-63...
  • Page 554 PMU 1 PHS-x (14 items) 0 to 14 F543 1 (Va) D43E PMU 1 PHS-x Name (14 items) F203 "GE-UR-PMU- PHS 1 " D4AE PMU 1 A-CH-x (16 items) 0 to 65535 F600 B-64 L30 Line Current Differential System GE Multilin...
  • Page 555 ...Repeated for Contact Output 36 DEAC ...Repeated for Contact Output 37 DEBB ...Repeated for Contact Output 38 DECA ...Repeated for Contact Output 39 DED9 ...Repeated for Contact Output 40 DEE8 ...Repeated for Contact Output 41 GE Multilin L30 Line Current Differential System B-65...
  • Page 556 ...Repeated for DCmA Inputs 19 E1B9 ...Repeated for DCmA Inputs 20 E1CC ...Repeated for DCmA Inputs 21 E1DF ...Repeated for DCmA Inputs 22 E1F2 ...Repeated for DCmA Inputs 23 E205 ...Repeated for DCmA Inputs 24 B-66 L30 Line Current Differential System GE Multilin...
  • Page 557 0 to 2 F109 0 (Self-reset) EC0D Synchrocheck 1 Events 0 to 1 F102 0 (Disabled) EC0E Synchrocheck 1 Block 0 to 4294967295 F300 EC10 Synchrocheck 1 Frequency Hysteresis 0 to 0.1 0.01 F001 GE Multilin L30 Line Current Differential System B-67...
  • Page 558 0 to 4294967295 F050 Settings File Template (Read/Write Setting) ED09 Template Bitmask (750 items) 0 to 65535 F001 Phasor Measurement Unit Records (Read Only) EFFF PMU Recording Number of Triggers 0 to 65535 F001 B-68 L30 Line Current Differential System GE Multilin...
  • Page 559: B.4.2 Data Formats

    0 = Disabled, 1 = Enabled UR_UINT32 TIME in SR format (alternate format for F050) First 16 bits are Hours/Minutes (HH:MM:xx.xxx). Hours: 0=12am, 1=1am,...,12=12pm,...23=11pm; Minutes: 0 to 59 in steps of 1 GE Multilin L30 Line Current Differential System B-69...
  • Page 560 ENUMERATION: ELEMENT INPUT SIGNAL TYPE F113 0 = Phasor, 1 = RMS ENUMERATION: PARITY 0 = None, 1 = Odd, 2 = Even F123 ENUMERATION: CT SECONDARY 0 = 1 A, 1 = 5 A B-70 L30 Line Current Differential System GE Multilin...
  • Page 561 Non-volatile Latch 7 87L Current Differential Non-volatile Latch 8 50DD Disturbance Detector Non-volatile Latch 9 87L Trip (Current Differential Trip) Non-volatile Latch 10 Stub Bus Non-volatile Latch 11 CT Fail1 Non-volatile Latch 12 GE Multilin L30 Line Current Differential System B-71...
  • Page 562 RTD Input 29 Digital Element 37 RTD Input 30 Digital Element 38 RTD Input 31 Digital Element 39 RTD Input 32 Digital Element 40 RTD Input 33 Digital Element 41 RTD Input 34 B-72 L30 Line Current Differential System GE Multilin...
  • Page 563 Broken conductor detection 2 Port 3 Offline Port 4 Offline F126 Port 5 Offline ENUMERATION: NO/YES CHOICE Port 6 Offline RRTD Communications Failure 0 = No, 1 = Yes Voltage Monitor FlexLogic Error Token GE Multilin L30 Line Current Differential System B-73...
  • Page 564 FGM Failure Temperature Warning On FGM Failure Temperature Warning Off FGM Failure Unauthorized Access FGM Failure System Integrity Recovery FGM Failure System Integrity Recovery 06 FGM Error System Integrity Recovery 07 Maintenance Alert B-74 L30 Line Current Differential System GE Multilin...
  • Page 565 UserSt-23 ENUMERATION: TRANSDUCER RTD INPUT TYPE DNA-21 UserSt-24 0 = 100 Ohm Platinum, 1 = 120 Ohm Nickel, DNA-22 UserSt-25 2 = 100 Ohm Nickel, 3 = 10 Ohm Copper DNA-23 UserSt-26 GE Multilin L30 Line Current Differential System B-75...
  • Page 566 20 registers, 16 Bits: 1st Char MSB, 2nd Char LSB GooseIn 16 F202 F186 TEXT20: 20-CHARACTER ASCII TEXT ENUMERATION: MEASUREMENT MODE 10 registers, 16 Bits: 1st Char MSB, 2nd Char LSB 0 = Phase to Ground, 1 = Phase to Phase B-76 L30 Line Current Differential System GE Multilin...
  • Page 567 0 = Voltage, 1 = Current, 2 = Dual, 3 = Dual-V, 4 = Dual-I MMXU1.MX.VAr.phsB.cVal.mag.f MMXU1.MX.VAr.phsC.cVal.mag.f MMXU1.MX.VA.phsA.cVal.mag.f F231 MMXU1.MX.VA.phsB.cVal.mag.f ENUMERATION: POLARIZING VOLTAGE MMXU1.MX.VA.phsC.cVal.mag.f 0 = Calculated V0, 1 = Measured VX MMXU1.MX.PF.phsA.cVal.mag.f MMXU1.MX.PF.phsB.cVal.mag.f MMXU1.MX.PF.phsC.cVal.mag.f MMXU2.MX.TotW.mag.f MMXU2.MX.TotVAr.mag.f MMXU2.MX.TotVA.mag.f MMXU2.MX.TotPF.mag.f GE Multilin L30 Line Current Differential System B-77...
  • Page 568 MMXU3.MX.Hz.mag.f MMXU4.MX.A.phsB.cVal.ang.f MMXU3.MX.PPV.phsAB.cVal.mag.f MMXU4.MX.A.phsC.cVal.mag.f MMXU3.MX.PPV.phsAB.cVal.ang.f MMXU4.MX.A.phsC.cVal.ang.f MMXU3.MX.PPV.phsBC.cVal.mag.f MMXU4.MX.A.neut.cVal.mag.f MMXU3.MX.PPV.phsBC.cVal.ang.f MMXU4.MX.A.neut.cVal.ang.f MMXU3.MX.PPV.phsCA.cVal.mag.f MMXU4.MX.W.phsA.cVal.mag.f MMXU3.MX.PPV.phsCA.cVal.ang.f MMXU4.MX.W.phsB.cVal.mag.f MMXU3.MX.PhV.phsA.cVal.mag.f MMXU4.MX.W.phsC.cVal.mag.f MMXU3.MX.PhV.phsA.cVal.ang.f MMXU4.MX.VAr.phsA.cVal.mag.f MMXU3.MX.PhV.phsB.cVal.mag.f MMXU4.MX.VAr.phsB.cVal.mag.f MMXU3.MX.PhV.phsB.cVal.ang.f MMXU4.MX.VAr.phsC.cVal.mag.f MMXU3.MX.PhV.phsC.cVal.mag.f MMXU4.MX.VA.phsA.cVal.mag.f MMXU3.MX.PhV.phsC.cVal.ang.f MMXU4.MX.VA.phsB.cVal.mag.f MMXU3.MX.A.phsA.cVal.mag.f MMXU4.MX.VA.phsC.cVal.mag.f MMXU3.MX.A.phsA.cVal.ang.f MMXU4.MX.PF.phsA.cVal.mag.f MMXU3.MX.A.phsB.cVal.mag.f MMXU4.MX.PF.phsB.cVal.mag.f B-78 L30 Line Current Differential System GE Multilin...
  • Page 569 MMXU5.MX.PF.phsC.cVal.mag.f GGIO4.MX.AnIn16.mag.f MMXU6.MX.TotW.mag.f GGIO4.MX.AnIn17.mag.f MMXU6.MX.TotVAr.mag.f GGIO4.MX.AnIn18.mag.f MMXU6.MX.TotVA.mag.f GGIO4.MX.AnIn19.mag.f MMXU6.MX.TotPF.mag.f GGIO4.MX.AnIn20.mag.f MMXU6.MX.Hz.mag.f GGIO4.MX.AnIn21.mag.f MMXU6.MX.PPV.phsAB.cVal.mag.f GGIO4.MX.AnIn22.mag.f MMXU6.MX.PPV.phsAB.cVal.ang.f GGIO4.MX.AnIn23.mag.f MMXU6.MX.PPV.phsBC.cVal.mag.f GGIO4.MX.AnIn24.mag.f MMXU6.MX.PPV.phsBC.cVal.ang.f GGIO4.MX.AnIn25.mag.f MMXU6.MX.PPV.phsCA.cVal.mag.f GGIO4.MX.AnIn26.mag.f MMXU6.MX.PPV.phsCA.cVal.ang.f GGIO4.MX.AnIn27.mag.f MMXU6.MX.PhV.phsA.cVal.mag.f GGIO4.MX.AnIn28.mag.f MMXU6.MX.PhV.phsA.cVal.ang.f GGIO4.MX.AnIn29.mag.f MMXU6.MX.PhV.phsB.cVal.mag.f GGIO4.MX.AnIn30.mag.f MMXU6.MX.PhV.phsB.cVal.ang.f GGIO4.MX.AnIn31.mag.f GE Multilin L30 Line Current Differential System B-79...
  • Page 570 IEC 61850 GOOSE Rx dataset item GGIO3.ST.UIntIn4.q None GGIO3.ST.UIntIn4.stVal GGIO3.ST.Ind1.q GGIO3.ST.UIntIn5.q GGIO3.ST.Ind1.stVal GGIO3.ST.UIntIn5.stVal GGIO3.ST.Ind2.q GGIO3.ST.UIntIn6.q GGIO3.ST.Ind2.stVal GGIO3.ST.UIntIn6.stVal ↓ ↓ GGIO3.ST.UIntIn7.q GGIO1.ST.Ind64q GGIO3.ST.UIntIn7.stVal GGIO1.ST.Ind64.stVal GGIO3.ST.UIntIn8.q GGIO3.MX.AnIn1.mag.f GGIO3.ST.UIntIn8.stVal GGIO3.MX.AnIn2.mag.f GGIO3.ST.UIntIn9.q GGIO3.MX.AnIn3.mag.f GGIO3.ST.UIntIn9.stVal GGIO3.MX.AnIn4.mag.f GGIO3.ST.UIntIn10.q GGIO3.MX.AnIn5.mag.f GGIO3.ST.UIntIn10.stVal B-80 L30 Line Current Differential System GE Multilin...
  • Page 571 Wednesday None Thursday U1/AC1..3 Friday U1/AC5..7 Saturday U2/AC1..3 U2/AC5..7 F239 U3/AC1..3 ENUMERATION: REAL TIME CLOCK DAYLIGHT SAVINGS U3/AC5..7 TIME START DAY INSTANCE U4/AC1..3 U4/AC5..7 Value Instance U5/AC1..3 First U5/AC5..7 Second U6/AC1..3 Third GE Multilin L30 Line Current Differential System B-81...
  • Page 572 [11] CONTACT OUTPUTS VOLTAGE OFF DETECTED (1 to 64) [12] CONTACT OUTPUTS CURRENT DETECTED (1 to 64) [13] CONTACT OUTPUTS CURRENT OFF DETECTED (1 to 64) [14] REMOTE INPUTS (1 to 32) B-82 L30 Line Current Differential System GE Multilin...
  • Page 573 0 to 15 corresponding to input/output state 49 to 64 (if required). The number of registers required is determined by the specific data item. A bit value of 0 = Off and 1 = On. GE Multilin L30 Line Current Differential System B-83...
  • Page 574 0 = NONE, 1 = 37.118, 2 = 61850-90-5 ENUMERATION: LANGUAGE 0 = English, 1 = French, 2 = Chinese, 3 = Russian, 4 = Turkish F549 ENUMERATION: PMU PERFORMANCE CLASS 0 = None, 1 = M-CLASS, 2 = P-CLASS B-84 L30 Line Current Differential System GE Multilin...
  • Page 575 Only certain values can be used as FlexAn- PDIF1.ST.Str.general alogs (basically all metering quantities used in protection). PDIF1.ST.Op.general PDIF2.ST.Str.general F601 PDIF2.ST.Op.general ENUMERATION: COM2 PORT USAGE PDIF3.ST.Str.general PDIF3.ST.Op.general Enumeration COM2 port usage PDIF4.ST.Str.general RS485 PDIF4.ST.Op.general RRTD GE Multilin L30 Line Current Differential System B-85...
  • Page 576 PIOC9.ST.Op.general PIOC36.ST.Str.general PIOC10.ST.Str.general PIOC36.ST.Op.general PIOC10.ST.Op.general PIOC37.ST.Str.general PIOC11.ST.Str.general PIOC37.ST.Op.general PIOC11.ST.Op.general PIOC38.ST.Str.general PIOC12.ST.Str.general PIOC38.ST.Op.general PIOC12.ST.Op.general PIOC39.ST.Str.general PIOC13.ST.Str.general PIOC39.ST.Op.general PIOC13.ST.Op.general PIOC40.ST.Str.general PIOC14.ST.Str.general PIOC40.ST.Op.general PIOC14.ST.Op.general PIOC41.ST.Str.general PIOC15.ST.Str.general PIOC41.ST.Op.general PIOC15.ST.Op.general PIOC42.ST.Str.general PIOC16.ST.Str.general PIOC42.ST.Op.general PIOC16.ST.Op.general PIOC43.ST.Str.general PIOC17.ST.Str.general PIOC43.ST.Op.general B-86 L30 Line Current Differential System GE Multilin...
  • Page 577 PIOC62.ST.Op.general PTOC17.ST.Str.general PIOC63.ST.Str.general PTOC17.ST.Op.general PIOC63.ST.Op.general PTOC18.ST.Str.general PIOC64.ST.Str.general PTOC18.ST.Op.general PIOC64.ST.Op.general PTOC19.ST.Str.general PIOC65.ST.Str.general PTOC19.ST.Op.general PIOC65.ST.Op.general PTOC20.ST.Str.general PIOC66.ST.Str.general PTOC20.ST.Op.general PIOC66.ST.Op.general PTOC21.ST.Str.general PIOC67.ST.Str.general PTOC21.ST.Op.general PIOC67.ST.Op.general PTOC22.ST.Str.general PIOC68.ST.Str.general PTOC22.ST.Op.general PIOC68.ST.Op.general PTOC23.ST.Str.general PIOC69.ST.Str.general PTOC23.ST.Op.general PIOC69.ST.Op.general PTOC24.ST.Str.general PIOC70.ST.Str.general PTOC24.ST.Op.general GE Multilin L30 Line Current Differential System B-87...
  • Page 578 PTUV3.ST.Op.general RBRF17.ST.OpEx.general PTUV4.ST.Str.general RBRF17.ST.OpIn.general PTUV4.ST.Op.general RBRF18.ST.OpEx.general PTUV5.ST.Str.general RBRF18.ST.OpIn.general PTUV5.ST.Op.general RBRF19.ST.OpEx.general PTUV6.ST.Str.general RBRF19.ST.OpIn.general PTUV6.ST.Op.general RBRF20.ST.OpEx.general PTUV7.ST.Str.general RBRF20.ST.OpIn.general PTUV7.ST.Op.general RBRF21.ST.OpEx.general PTUV8.ST.Str.general RBRF21.ST.OpIn.general PTUV8.ST.Op.general RBRF22.ST.OpEx.general PTUV9.ST.Str.general RBRF22.ST.OpIn.general PTUV9.ST.Op.general RBRF23.ST.OpEx.general PTUV10.ST.Str.general RBRF23.ST.OpIn.general PTUV10.ST.Op.general RBRF24.ST.OpEx.general PTUV11.ST.Str.general RBRF24.ST.OpIn.general B-88 L30 Line Current Differential System GE Multilin...
  • Page 579 CSWI9.ST.Pos.stVal GGIO1.ST.Ind11.stVal CSWI10.ST.Loc.stVal GGIO1.ST.Ind12.stVal CSWI10.ST.Pos.stVal GGIO1.ST.Ind13.stVal CSWI11.ST.Loc.stVal GGIO1.ST.Ind14.stVal CSWI11.ST.Pos.stVal GGIO1.ST.Ind15.stVal CSWI12.ST.Loc.stVal GGIO1.ST.Ind16.stVal CSWI12.ST.Pos.stVal GGIO1.ST.Ind17.stVal CSWI13.ST.Loc.stVal GGIO1.ST.Ind18.stVal CSWI13.ST.Pos.stVal GGIO1.ST.Ind19.stVal CSWI14.ST.Loc.stVal GGIO1.ST.Ind20.stVal CSWI14.ST.Pos.stVal GGIO1.ST.Ind21.stVal CSWI15.ST.Loc.stVal GGIO1.ST.Ind22.stVal CSWI15.ST.Pos.stVal GGIO1.ST.Ind23.stVal CSWI16.ST.Loc.stVal GGIO1.ST.Ind24.stVal CSWI16.ST.Pos.stVal GGIO1.ST.Ind25.stVal CSWI17.ST.Loc.stVal GGIO1.ST.Ind26.stVal GE Multilin L30 Line Current Differential System B-89...
  • Page 580 GGIO1.ST.Ind64.stVal GGIO1.ST.Ind117.stVal GGIO1.ST.Ind65.stVal GGIO1.ST.Ind118.stVal GGIO1.ST.Ind66.stVal GGIO1.ST.Ind119.stVal GGIO1.ST.Ind67.stVal GGIO1.ST.Ind120.stVal GGIO1.ST.Ind68.stVal GGIO1.ST.Ind121.stVal GGIO1.ST.Ind69.stVal GGIO1.ST.Ind122.stVal GGIO1.ST.Ind70.stVal GGIO1.ST.Ind123.stVal GGIO1.ST.Ind71.stVal GGIO1.ST.Ind124.stVal GGIO1.ST.Ind72.stVal GGIO1.ST.Ind125.stVal GGIO1.ST.Ind73.stVal GGIO1.ST.Ind126.stVal GGIO1.ST.Ind74.stVal GGIO1.ST.Ind127.stVal GGIO1.ST.Ind75.stVal GGIO1.ST.Ind128.stVal GGIO1.ST.Ind76.stVal MMXU1.MX.TotW.mag.f GGIO1.ST.Ind77.stVal MMXU1.MX.TotVAr.mag.f GGIO1.ST.Ind78.stVal MMXU1.MX.TotVA.mag.f GGIO1.ST.Ind79.stVal MMXU1.MX.TotPF.mag.f B-90 L30 Line Current Differential System GE Multilin...
  • Page 581 MMXU2.MX.Hz.mag.f MMXU3.MX.A.phsB.cVal.ang.f MMXU2.MX.PPV.phsAB.cVal.mag.f MMXU3.MX.A.phsC.cVal.mag.f MMXU2.MX.PPV.phsAB.cVal.ang.f MMXU3.MX.A.phsC.cVal.ang.f MMXU2.MX.PPV.phsBC.cVal.mag.f MMXU3.MX.A.neut.cVal.mag.f MMXU2.MX.PPV.phsBC.cVal.ang.f MMXU3.MX.A.neut.cVal.ang.f MMXU2.MX.PPV.phsCA.cVal.mag.f MMXU3.MX.W.phsA.cVal.mag.f MMXU2.MX.PPV.phsCA.cVal.ang.f MMXU3.MX.W.phsB.cVal.mag.f MMXU2.MX.PhV.phsA.cVal.mag.f MMXU3.MX.W.phsC.cVal.mag.f MMXU2.MX.PhV.phsA.cVal.ang.f MMXU3.MX.VAr.phsA.cVal.mag.f MMXU2.MX.PhV.phsB.cVal.mag.f MMXU3.MX.VAr.phsB.cVal.mag.f MMXU2.MX.PhV.phsB.cVal.ang.f MMXU3.MX.VAr.phsC.cVal.mag.f MMXU2.MX.PhV.phsC.cVal.mag.f MMXU3.MX.VA.phsA.cVal.mag.f MMXU2.MX.PhV.phsC.cVal.ang.f MMXU3.MX.VA.phsB.cVal.mag.f MMXU2.MX.A.phsA.cVal.mag.f MMXU3.MX.VA.phsC.cVal.mag.f MMXU2.MX.A.phsA.cVal.ang.f MMXU3.MX.PF.phsA.cVal.mag.f MMXU2.MX.A.phsB.cVal.mag.f MMXU3.MX.PF.phsB.cVal.mag.f GE Multilin L30 Line Current Differential System B-91...
  • Page 582 MMXU4.MX.PF.phsC.cVal.mag.f MMXU6.MX.PhV.phsC.cVal.mag.f MMXU5.MX.TotW.mag.f MMXU6.MX.PhV.phsC.cVal.ang.f MMXU5.MX.TotVAr.mag.f MMXU6.MX.A.phsA.cVal.mag.f MMXU5.MX.TotVA.mag.f MMXU6.MX.A.phsA.cVal.ang.f MMXU5.MX.TotPF.mag.f MMXU6.MX.A.phsB.cVal.mag.f MMXU5.MX.Hz.mag.f MMXU6.MX.A.phsB.cVal.ang.f MMXU5.MX.PPV.phsAB.cVal.mag.f MMXU6.MX.A.phsC.cVal.mag.f MMXU5.MX.PPV.phsAB.cVal.ang.f MMXU6.MX.A.phsC.cVal.ang.f MMXU5.MX.PPV.phsBC.cVal.mag.f MMXU6.MX.A.neut.cVal.mag.f MMXU5.MX.PPV.phsBC.cVal.ang.f MMXU6.MX.A.neut.cVal.ang.f MMXU5.MX.PPV.phsCA.cVal.mag.f MMXU6.MX.W.phsA.cVal.mag.f MMXU5.MX.PPV.phsCA.cVal.ang.f MMXU6.MX.W.phsB.cVal.mag.f MMXU5.MX.PhV.phsA.cVal.mag.f MMXU6.MX.W.phsC.cVal.mag.f MMXU5.MX.PhV.phsA.cVal.ang.f MMXU6.MX.VAr.phsA.cVal.mag.f MMXU5.MX.PhV.phsB.cVal.mag.f MMXU6.MX.VAr.phsB.cVal.mag.f MMXU5.MX.PhV.phsB.cVal.ang.f MMXU6.MX.VAr.phsC.cVal.mag.f B-92 L30 Line Current Differential System GE Multilin...
  • Page 583 GGIO4.MX.AnIn28.mag.f XCBR1.ST.Loc.stVal GGIO4.MX.AnIn29.mag.f XCBR1.ST.Pos.stVal GGIO4.MX.AnIn30.mag.f XCBR2.ST.Loc.stVal GGIO4.MX.AnIn31.mag.f XCBR2.ST.Pos.stVal GGIO4.MX.AnIn32.mag.f XCBR3.ST.Loc.stVal XSWI1.ST.Loc.stVal XCBR3.ST.Pos.stVal XSWI1.ST.Pos.stVal XCBR4.ST.Loc.stVal XSWI2.ST.Loc.stVal XCBR4.ST.Pos.stVal XSWI2.ST.Pos.stVal XCBR5.ST.Loc.stVal XSWI3.ST.Loc.stVal XCBR5.ST.Pos.stVal XSWI3.ST.Pos.stVal XCBR6.ST.Loc.stVal XSWI4.ST.Loc.stVal XCBR6.ST.Pos.stVal XSWI4.ST.Pos.stVal XSWI5.ST.Loc.stVal XSWI5.ST.Pos.stVal XSWI6.ST.Loc.stVal XSWI6.ST.Pos.stVal XSWI7.ST.Loc.stVal XSWI7.ST.Pos.stVal XSWI8.ST.Loc.stVal GE Multilin L30 Line Current Differential System B-93...
  • Page 584 GGIO1.ST.Ind17.q GGIO1.ST.Ind43.stVal GGIO1.ST.Ind17.stVal GGIO1.ST.Ind44.q GGIO1.ST.Ind18.q GGIO1.ST.Ind44.stVal GGIO1.ST.Ind18.stVal GGIO1.ST.Ind45.q GGIO1.ST.Ind19.q GGIO1.ST.Ind45.stVal GGIO1.ST.Ind19.stVal GGIO1.ST.Ind46.q GGIO1.ST.Ind20.q GGIO1.ST.Ind46.stVal GGIO1.ST.Ind20.stVal GGIO1.ST.Ind47.q GGIO1.ST.Ind21.q GGIO1.ST.Ind47.stVal GGIO1.ST.Ind21.stVal GGIO1.ST.Ind48.q GGIO1.ST.Ind22.q GGIO1.ST.Ind48.stVal GGIO1.ST.Ind22.stVal GGIO1.ST.Ind49.q GGIO1.ST.Ind23.q GGIO1.ST.Ind49.stVal GGIO1.ST.Ind23.stVal GGIO1.ST.Ind50.q GGIO1.ST.Ind24.q GGIO1.ST.Ind50.stVal GGIO1.ST.Ind24.stVal GGIO1.ST.Ind51.q B-94 L30 Line Current Differential System GE Multilin...
  • Page 585 GGIO1.ST.Ind70.q GGIO1.ST.Ind96.stVal GGIO1.ST.Ind70.stVal GGIO1.ST.Ind97.q GGIO1.ST.Ind71.q GGIO1.ST.Ind97.stVal GGIO1.ST.Ind71.stVal GGIO1.ST.Ind98.q GGIO1.ST.Ind72.q GGIO1.ST.Ind98.stVal GGIO1.ST.Ind72.stVal GGIO1.ST.Ind99.q GGIO1.ST.Ind73.q GGIO1.ST.Ind99.stVal GGIO1.ST.Ind73.stVal GGIO1.ST.Ind100.q GGIO1.ST.Ind74.q GGIO1.ST.Ind100.stVal GGIO1.ST.Ind74.stVal GGIO1.ST.Ind101.q GGIO1.ST.Ind75.q GGIO1.ST.Ind101.stVal GGIO1.ST.Ind75.stVal GGIO1.ST.Ind102.q GGIO1.ST.Ind76.q GGIO1.ST.Ind102.stVal GGIO1.ST.Ind76.stVal GGIO1.ST.Ind103.q GGIO1.ST.Ind77.q GGIO1.ST.Ind103.stVal GGIO1.ST.Ind77.stVal GGIO1.ST.Ind104.q GE Multilin L30 Line Current Differential System B-95...
  • Page 586 GGIO1.ST.Ind123.q MMXU2.MX.Hz.mag.f GGIO1.ST.Ind123.stVal MMXU2.MX.PPV.phsAB.cVal.mag.f GGIO1.ST.Ind124.q MMXU2.MX.PPV.phsAB.cVal.ang.f GGIO1.ST.Ind124.stVal MMXU2.MX.PPV.phsBC.cVal.mag.f GGIO1.ST.Ind125.q MMXU2.MX.PPV.phsBC.cVal.ang.f GGIO1.ST.Ind125.stVal MMXU2.MX.PPV.phsCA.cVal.mag.f GGIO1.ST.Ind126.q MMXU2.MX.PPV.phsCA.cVal.ang.f GGIO1.ST.Ind126.stVal MMXU2.MX.PhV.phsA.cVal.mag.f GGIO1.ST.Ind127.q MMXU2.MX.PhV.phsA.cVal.ang.f GGIO1.ST.Ind127.stVal MMXU2.MX.PhV.phsB.cVal.mag.f GGIO1.ST.Ind128.q MMXU2.MX.PhV.phsB.cVal.ang.f GGIO1.ST.Ind128.stVal MMXU2.MX.PhV.phsC.cVal.mag.f MMXU1.MX.TotW.mag.f MMXU2.MX.PhV.phsC.cVal.ang.f MMXU1.MX.TotVAr.mag.f MMXU2.MX.A.phsA.cVal.mag.f MMXU1.MX.TotVA.mag.f MMXU2.MX.A.phsA.cVal.ang.f MMXU1.MX.TotPF.mag.f MMXU2.MX.A.phsB.cVal.mag.f B-96 L30 Line Current Differential System GE Multilin...
  • Page 587 MMXU3.MX.A.phsB.cVal.ang.f MMXU4.MX.PF.phsC.cVal.mag.f MMXU3.MX.A.phsC.cVal.mag.f MMXU5.MX.TotW.mag.f MMXU3.MX.A.phsC.cVal.ang.f MMXU5.MX.TotVAr.mag.f MMXU3.MX.A.neut.cVal.mag.f MMXU5.MX.TotVA.mag.f MMXU3.MX.A.neut.cVal.ang.f MMXU5.MX.TotPF.mag.f MMXU3.MX.W.phsA.cVal.mag.f MMXU5.MX.Hz.mag.f MMXU3.MX.W.phsB.cVal.mag.f MMXU5.MX.PPV.phsAB.cVal.mag.f MMXU3.MX.W.phsC.cVal.mag.f MMXU5.MX.PPV.phsAB.cVal.ang.f MMXU3.MX.VAr.phsA.cVal.mag.f MMXU5.MX.PPV.phsBC.cVal.mag.f MMXU3.MX.VAr.phsB.cVal.mag.f MMXU5.MX.PPV.phsBC.cVal.ang.f MMXU3.MX.VAr.phsC.cVal.mag.f MMXU5.MX.PPV.phsCA.cVal.mag.f MMXU3.MX.VA.phsA.cVal.mag.f MMXU5.MX.PPV.phsCA.cVal.ang.f MMXU3.MX.VA.phsB.cVal.mag.f MMXU5.MX.PhV.phsA.cVal.mag.f MMXU3.MX.VA.phsC.cVal.mag.f MMXU5.MX.PhV.phsA.cVal.ang.f MMXU3.MX.PF.phsA.cVal.mag.f MMXU5.MX.PhV.phsB.cVal.mag.f MMXU3.MX.PF.phsB.cVal.mag.f MMXU5.MX.PhV.phsB.cVal.ang.f GE Multilin L30 Line Current Differential System B-97...
  • Page 588 MMXU6.MX.PhV.phsC.cVal.mag.f GGIO4.MX.AnIn32.mag.f MMXU6.MX.PhV.phsC.cVal.ang.f GGIO5.ST.UIntIn1.q MMXU6.MX.A.phsA.cVal.mag.f GGIO5.ST.UIntIn1.stVal MMXU6.MX.A.phsA.cVal.ang.f GGIO5.ST.UIntIn2.q MMXU6.MX.A.phsB.cVal.mag.f GGIO5.ST.UIntIn2.stVal MMXU6.MX.A.phsB.cVal.ang.f GGIO5.ST.UIntIn3.q MMXU6.MX.A.phsC.cVal.mag.f GGIO5.ST.UIntIn3.stVal MMXU6.MX.A.phsC.cVal.ang.f GGIO5.ST.UIntIn4.q MMXU6.MX.A.neut.cVal.mag.f GGIO5.ST.UIntIn4.stVal MMXU6.MX.A.neut.cVal.ang.f GGIO5.ST.UIntIn5.q MMXU6.MX.W.phsA.cVal.mag.f GGIO5.ST.UIntIn5.stVal MMXU6.MX.W.phsB.cVal.mag.f GGIO5.ST.UIntIn6.q MMXU6.MX.W.phsC.cVal.mag.f GGIO5.ST.UIntIn6.stVal MMXU6.MX.VAr.phsA.cVal.mag.f GGIO5.ST.UIntIn7.q MMXU6.MX.VAr.phsB.cVal.mag.f GGIO5.ST.UIntIn7.stVal MMXU6.MX.VAr.phsC.cVal.mag.f GGIO5.ST.UIntIn8.q B-98 L30 Line Current Differential System GE Multilin...
  • Page 589 PDIS7.ST.Str.general PIOC23.ST.Op.general PDIS7.ST.Op.general PIOC24.ST.Str.general PDIS8.ST.Str.general PIOC24.ST.Op.general PDIS8.ST.Op.general PIOC25.ST.Str.general PDIS9.ST.Str.general PIOC25.ST.Op.general PDIS9.ST.Op.general PIOC26.ST.Str.general PDIS10.ST.Str.general PIOC26.ST.Op.general PDIS10.ST.Op.general PIOC27.ST.Str.general PIOC1.ST.Str.general PIOC27.ST.Op.general PIOC1.ST.Op.general PIOC28.ST.Str.general PIOC2.ST.Str.general PIOC28.ST.Op.general PIOC2.ST.Op.general PIOC29.ST.Str.general PIOC3.ST.Str.general PIOC29.ST.Op.general PIOC3.ST.Op.general PIOC30.ST.Str.general PIOC4.ST.Str.general PIOC30.ST.Op.general PIOC4.ST.Op.general PIOC31.ST.Str.general GE Multilin L30 Line Current Differential System B-99...
  • Page 590 PIOC50.ST.Str.general PTOC4.ST.Op.general PIOC50.ST.Op.general PTOC5.ST.Str.general PIOC51.ST.Str.general PTOC5.ST.Op.general PIOC51.ST.Op.general PTOC6.ST.Str.general PIOC52.ST.Str.general PTOC6.ST.Op.general PIOC52.ST.Op.general PTOC7.ST.Str.general PIOC53.ST.Str.general PTOC7.ST.Op.general PIOC53.ST.Op.general PTOC8.ST.Str.general PIOC54.ST.Str.general PTOC8.ST.Op.general PIOC54.ST.Op.general PTOC9.ST.Str.general PIOC55.ST.Str.general PTOC9.ST.Op.general PIOC55.ST.Op.general PTOC10.ST.Str.general PIOC56.ST.Str.general PTOC10.ST.Op.general PIOC56.ST.Op.general PTOC11.ST.Str.general PIOC57.ST.Str.general PTOC11.ST.Op.general PIOC57.ST.Op.general PTOC12.ST.Str.general B-100 L30 Line Current Differential System GE Multilin...
  • Page 591 PTOV7.ST.Str.general RBRF4.ST.OpIn.general PTOV7.ST.Op.general RBRF5.ST.OpEx.general PTOV8.ST.Str.general RBRF5.ST.OpIn.general PTOV8.ST.Op.general RBRF6.ST.OpEx.general PTOV9.ST.Str.general RBRF6.ST.OpIn.general PTOV9.ST.Op.general RBRF7.ST.OpEx.general PTOV10.ST.Str.general RBRF7.ST.OpIn.general PTOV10.ST.Op.general RBRF8.ST.OpEx.general PTRC1.ST.Tr.general RBRF8.ST.OpIn.general PTRC1.ST.Op.general RBRF9.ST.OpEx.general PTRC2.ST.Tr.general RBRF9.ST.OpIn.general PTRC2.ST.Op.general RBRF10.ST.OpEx.general PTRC3.ST.Tr.general RBRF10.ST.OpIn.general PTRC3.ST.Op.general RBRF11.ST.OpEx.general PTRC4.ST.Tr.general RBRF11.ST.OpIn.general PTRC4.ST.Op.general RBRF12.ST.OpEx.general GE Multilin L30 Line Current Differential System B-101...
  • Page 592 RREC3.ST.Op.general CSWI23.ST.Pos.stVal RREC3.ST.AutoRecSt.stVal CSWI24.ST.Loc.stVal RREC4.ST.Op.general CSWI24.ST.Pos.stVal RREC4.ST.AutoRecSt.stVal CSWI25.ST.Loc.stVal RREC5.ST.Op.general CSWI25.ST.Pos.stVal RREC5.ST.AutoRecSt.stVal CSWI26.ST.Loc.stVal RREC6.ST.Op.general CSWI26.ST.Pos.stVal RREC6.ST.AutoRecSt.stVal CSWI27.ST.Loc.stVal CSWI1.ST.Loc.stVal CSWI27.ST.Pos.stVal CSWI1.ST.Pos.stVal CSWI28.ST.Loc.stVal CSWI2.ST.Loc.stVal CSWI28.ST.Pos.stVal CSWI2.ST.Pos.stVal CSWI29.ST.Loc.stVal CSWI3.ST.Loc.stVal CSWI29.ST.Pos.stVal CSWI3.ST.Pos.stVal CSWI30.ST.Loc.stVal CSWI4.ST.Loc.stVal CSWI30.ST.Pos.stVal CSWI4.ST.Pos.stVal XSWI1.ST.Loc.stVal B-102 L30 Line Current Differential System GE Multilin...
  • Page 593 Administrator XSWI20.ST.Loc.stVal Supervisor XSWI20.ST.Pos.stVal Engineer XSWI21.ST.Loc.stVal Operator XSWI21.ST.Pos.stVal XSWI22.ST.Loc.stVal XSWI22.ST.Pos.stVal F621 XSWI23.ST.Loc.stVal ENUMERATION: MODBUS LOGIN ROLES XSWI23.ST.Pos.stVal Enumeration Role XSWI24.ST.Loc.stVal None XSWI24.ST.Pos.stVal Administrator XCBR1.ST.Loc.stVal Supervisor XCBR1.ST.Pos.stVal Engineer XCBR2.ST.Loc.stVal Operator 1000 XCBR2.ST.Pos.stVal Observer GE Multilin L30 Line Current Differential System B-103...
  • Page 594 Disables security on local access, remote access, or both. SNTP Enumeration Item F625 Disabled ENUMERATION: PTP STATE Local and Remote Local Enumeration Item Remote Disabled No Signal Calibrating Synchronized Synchronized (No PDelay) B-104 L30 Line Current Differential System GE Multilin...
  • Page 595: C.1.1 Introduction

    LAN environment. Actual MMS protocol services are mapped to IEC 61850 abstract ser- vices in IEC 61850-8-1. The L30 relay supports IEC 61850 server services over TCP/IP. The TCP/IP profile requires the L30 to have an IP address to establish communications. These addresses are located in the ...
  • Page 596: C.1.3 File Transfer By Iec 61850

    APPENDIX C C.1.3 FILE TRANSFER BY IEC 61850 The L30 supports file transfer by IEC 61850. The approach is as follows, using the SISCO AX-S4 61850 client software as an example. In the AX-S4 61850 Explorer window, click the Tools menu and access the SISCO File Transfer Utility.
  • Page 597: C.2.1 Overview

    C.2.2 GGIO1: DIGITAL STATUS VALUES The GGIO1 logical node is available in the L30 to provide access to as many 128 digital status points and associated time- stamps and quality flags. The data content must be configured before the data can be used. GGIO1 provides digital status points for access by clients.
  • Page 598: C.2.6 Mmxu: Analog Measured Values

    A limited number of measured analog values are available through the MMXU logical nodes. Each MMXU logical node provides data from a L30 current and voltage source. There is one MMXU available for each con- figurable source (programmed in the ...
  • Page 599 The protection elements listed above contain start (pickup) and operate flags. For example, the start flag for PIOC1 is PIOC1.ST.Str.general. The operate flag for PIOC1 is PIOC1.ST.Op.general. For the L30 protection elements, these flags take their values from the pickup and operate FlexLogic operands for the corresponding element.
  • Page 600: C.3.1 Buffered/Unbuffered Reporting

    C.3.4 LOGICAL DEVICE NAME The logical device name is used to identify the IEC 61850 logical device that exists within the L30. This name is composed of two parts: the IED name setting and the logical device instance. The complete logical device name is the combination of the two character strings programmed in the settings.
  • Page 601: C.3.6 Logical Node Name Prefixes

    A built-in TCP/IP connection timeout of two minutes is employed by the L30 to detect ‘dead’ connections. If there is no data traffic on a TCP connection for greater than two minutes, the connection will be aborted by the L30. This frees up the con- nection to be used by other clients.
  • Page 602: C.4.1 Overview

    MAC address for GSSE messages. If GSSE DESTINATION MAC ADDRESS a valid multicast Ethernet MAC address is not entered (for example, 00 00 00 00 00 00), the L30 will use the source Ether- net MAC address as the destination, with the multicast bit set.
  • Page 603 The L30 has the ability of detecting if a data item in one of the GOOSE datasets is erroneously oscillating. This can be caused by events such as errors in logic programming, inputs improperly being asserted and de-asserted, or failed station components.
  • Page 604 REMOTE IN 1 ITEM item to remote input 1. Remote input 1 can now be used in FlexLogic equations or other settings. The L30 must be rebooted (control power removed and re-applied) before these settings take effect. The value of remote input 1 (Boolean on or off) in the receiving device will be determined by the GGIO1.ST.Ind1.stVal value in the sending device.
  • Page 605: C.4.5 Ethernet Mac Address For Gsse/Goose

    GSSE and GOOSE messages must have multicast destination MAC addresses. By default, the L30 is configured to use an automated multicast MAC scheme. If the L30 destination MAC address setting is not a valid multicast address (that is, the least significant bit of the first byte is not set), the address used as the destina- tion MAC will be the same as the local MAC address, but with the multicast bit set.
  • Page 606: C.5.1 Overview

    An ICD file is generated for the L30 by the EnerVista UR Setup software that describe the capabilities of the IED. The ICD file is then imported into a system configurator along with other ICD files for other IEDs (from GE or other ven- dors) for system configuration.
  • Page 607: C.5.2 Configuring Iec 61850 Settings

    Transmission GOOSE dataset may be added or deleted, or prefixes of some logical nodes may be changed. While all new configurations will be mapped to the L30 settings file when importing an SCD file, all unchanged settings will preserve the same values in the new settings file.
  • Page 608: C.5.3 About Icd Files

    Although configurable transmission GOOSE can also be created and altered by some third-party system con- figurators, we recommend configuring transmission GOOSE for GE Multilin IEDs before creating the ICD, and strictly within EnerVista UR Setup software or the front panel display (access through the Settings > Product Setup > Com- munications >...
  • Page 609 Furthermore, it defines the capabilities of an IED in terms of communication services offered and, together with its LNType, instantiated data (DO) and its default or configuration values. There should be only one IED section in an ICD since it only describes one IED. GE Multilin L30 Line Current Differential System C-15...
  • Page 610 Other ReportControl elements DOI (name) SDI (name) DAI (name) Text Other DOI elements SDI (name) DAI (name) Text Other LN elements Other LDevice elements 842797A1.CDR Figure C–4: ICD FILE STRUCTURE, IED NODE C-16 L30 Line Current Differential System GE Multilin...
  • Page 611 BDA (name, bType, type) Other BDA elements Other BDA elements Other DAType elements Other DAType elements EnumType (id) Text EnumVal (ord) Other EnumVal elements Other EnumType elements 842798A1.CDR Figure C–5: ICD FILE STRUCTURE, DATATYPETEMPLATES NODE GE Multilin L30 Line Current Differential System C-17...
  • Page 612: C.5.4 Creating An Icd File With Enervista Ur Setup

    The EnerVista UR Setup will prompt to save the file. Select the file path and enter the name for the ICD file, then click OK to generate the file. The time to create an ICD file from the offline L30 settings file is typically much quicker than create an ICD file directly from the relay.
  • Page 613 Like ICD files, the Header node identifies the SCD file and its version, and specifies options for the mapping of names to signals. The Substation node describes the substation parameters: Substation PowerSystemResource EquipmentContainer Power Transformer GeneralEquipment EquipmentContainer VoltageLevel Voltage PowerSystemResource Function SubFunction GeneralEquipment 842792A1.CDR Figure C–7: SCD FILE STRUCTURE, SUBSTATION NODE GE Multilin L30 Line Current Differential System C-19...
  • Page 614 IdInst is the instance identification of the logical device within the IED on which the control block is located, and cbName is the name of the control block. C-20 L30 Line Current Differential System GE Multilin...
  • Page 615: C.5.6 Importing An Scd File With Enervista Ur Setup

    Figure C–9: SCD FILE STRUCTURE, IED NODE C.5.6 IMPORTING AN SCD FILE WITH ENERVISTA UR SETUP The following procedure describes how to update the L30 with the new configuration from an SCD file with the EnerVista UR Setup software. Right-click anywhere in the files panel and select the Import Contents From SCD File item.
  • Page 616 The software will open the SCD file and then prompt the user to save a UR-series settings file. Select a location and name for the URS (UR-series relay settings) file. If there is more than one GE Multilin IED defined in the SCD file, the software prompt the user to save a UR-series set- tings file for each IED.
  • Page 617: C.6.1 Acsi Basic Conformance Statement

    REPORTING Buffered report control M7-1 sequence-number M7-2 report-time-stamp M7-3 reason-for-inclusion M7-4 data-set-name M7-5 data-reference M7-6 buffer-overflow M7-7 entryID M7-8 BufTm M7-9 IntgPd M7-10 Unbuffered report control M8-1 sequence-number M8-2 report-time-stamp M8-3 reason-for-inclusion GE Multilin L30 Line Current Differential System C-23...
  • Page 618: C.6.3 Acsi Services Conformance Statement

    UR FAMILY PUBLISHER SERVER (CLAUSE 7) ServerDirectory APPLICATION ASSOCIATION (CLAUSE 8) Associate Abort Release LOGICAL DEVICE (CLAUSE 9) LogicalDeviceDirectory LOGICAL NODE (CLAUSE 10) LogicalNodeDirectory GetAllDataValues DATA (CLAUSE 11) GetDataValues SetDataValues GetDataDirectory GetDataDefinition C-24 L30 Line Current Differential System GE Multilin...
  • Page 619 LOG CONTROL BLOCK GetLCBValues SetLCBValues QueryLogByTime QueryLogByEntry GetLogStatusValues GENERIC SUBSTATION EVENT MODEL (GSE) (CLAUSE 18, ANNEX C) GOOSE-CONTROL-BLOCK (CLAUSE 18) SendGOOSEMessage GetReference GetGOOSEElementNumber GetGoCBValues SetGoCBValues GSSE-CONTROL-BLOCK (ANNEX C) SendGSSEMessage GetReference GetGSSEElementNumber GetGsCBValues GE Multilin L30 Line Current Differential System C-25...
  • Page 620 (SendGOOSEMessage or SendGSSEMessage) NOTE c9: shall declare support if TP association is available c10: shall declare support for at least one (SendMSVMessage or SendUSVMessage) C-26 L30 Line Current Differential System GE Multilin...
  • Page 621: C.7.1 Logical Nodes Table

    GGIO: Generic process I/O GLOG: Generic log GSAL: Generic security application I: LOGICAL NODES FOR INTERFACING AND ARCHIVING IARC: Archiving IHMI: Human machine interface ISAF: Safety alarm function ITCI: Telecontrol interface ITMI: Telemonitoring interface GE Multilin L30 Line Current Differential System C-27...
  • Page 622 PSCH: Protection scheme PSDE: Sensitive directional earth fault PTEF: Transient earth fault PTOC: Time overcurrent PTOF: Overfrequency PTOV: Overvoltage PTRC: Protection trip conditioning PTTR: Thermal overload PTUC: Undercurrent PTUF: Underfrequency PTUV: Undervoltage C-28 L30 Line Current Differential System GE Multilin...
  • Page 623 T: LOGICAL NODES FOR INSTRUMENT TRANSFORMERS TANG: Angle TAXD: Axial displacement TCTR: Current transformer TDST: Distance TFLW: Liquid flow TFRQ: Frequency TGSN: Generic sensor THUM: Humidity TLVL: Media level TMGF: Magnetic field TMVM: Movement sensor GE Multilin L30 Line Current Differential System C-29...
  • Page 624 ZLIN: Power overhead line ZMOT: Motor ZREA: Reactor ZRES: Resistor ZRRC: Rotating reactive component ZSAR: Surge arrestor ZSCR: Semi-conductor controlled rectifier ZSMC: Synchronous machine ZTCF: Thyristor controlled frequency converter ZTRC: Thyristor controlled reactive component C-30 L30 Line Current Differential System GE Multilin...
  • Page 625: D.1.1 Interoperability Document

    Balanced Transmission Not Present (Balanced Transmission Only)   Unbalanced Transmission One Octet  Two Octets  Structured  Unstructured Frame Length (maximum length, number of octets): Not selectable in companion IEC 60870-5-104 standard GE Multilin L30 Line Current Differential System...
  • Page 626  <18> := Packed start events of protection equipment with time tag M_EP_TB_1  <19> := Packed output circuit information of protection equipment with time tag M_EP_TC_1  <20> := Packed single-point information with status change detection M_SP_NA_1 L30 Line Current Differential System GE Multilin...
  • Page 627  <103> := Clock synchronization command (see Clause 7.6 in standard) C_CS_NA_1  <104> := Test command C_TS_NA_1  <105> := Reset process command C_RP_NA_1  <106> := Delay acquisition command C_CD_NA_1  <107> := Test command with time tag CP56Time2a C_TS_TA_1 GE Multilin L30 Line Current Differential System...
  • Page 628 •Blank boxes indicate functions or ASDU not used. •‘X’ if only used in the standard direction TYPE IDENTIFICATION CAUSE OF TRANSMISSION MNEMONIC <1> M_SP_NA_1 <2> M_SP_TA_1 <3> M_DP_NA_1 <4> M_DP_TA_1 <5> M_ST_NA_1 <6> M_ST_TA_1 <7> M_BO_NA_1 <8> M_BO_TA_1 <9> M_ME_NA_1 L30 Line Current Differential System GE Multilin...
  • Page 629 M_ME_TD_1 <35> M_ME_TE_1 <36> M_ME_TF_1 <37> M_IT_TB_1 <38> M_EP_TD_1 <39> M_EP_TE_1 <40> M_EP_TF_1 <45> C_SC_NA_1 <46> C_DC_NA_1 <47> C_RC_NA_1 <48> C_SE_NA_1 <49> C_SE_NB_1 <50> C_SE_NC_1 <51> C_BO_NA_1 <58> C_SC_TA_1 <59> C_DC_TA_1 <60> C_RC_TA_1 GE Multilin L30 Line Current Differential System...
  • Page 630 F_FR_NA_1 <121> F_SR_NA_1 <122> F_SC_NA_1 <123> F_LS_NA_1 <124> F_AF_NA_1 <125> F_SG_NA_1 <126> F_DR_TA_1*) BASIC APPLICATION FUNCTIONS Station Initialization:  Remote initialization Cyclic Data Transmission:  Cyclic data transmission Read Procedure:  Read procedure L30 Line Current Differential System GE Multilin...
  • Page 631  Mode B: Local freeze with counter interrogation  Mode C: Freeze and transmit by counter-interrogation commands  Mode D: Freeze by counter-interrogation command, frozen values reported simultaneously  Counter read  Counter freeze without reset GE Multilin L30 Line Current Differential System...
  • Page 632 Maximum number of outstanding I-format APDUs k and latest acknowledge APDUs (w): PARAMETER DEFAULT REMARKS SELECTED VALUE VALUE 12 APDUs Maximum difference receive sequence number to send state variable 12 APDUs 8 APDUs 8 APDUs Latest acknowledge after receiving I-format APDUs L30 Line Current Differential System GE Multilin...
  • Page 633: D.1.2 Point List

    The IEC 60870-5-104 data points are configured through the    SETTINGS PRODUCT SETUP COMMUNICATIONS DNP / menu. Refer to the Communications section of Chapter 5 for additional details. IEC104 POINT LISTS GE Multilin L30 Line Current Differential System...
  • Page 634 D.1 IEC 60870-5-104 APPENDIX D D-10 L30 Line Current Differential System GE Multilin...
  • Page 635: E.1.1 Dnp V3.00 Device Profile

    Maximum Data Link Re-tries: Maximum Application Layer Re-tries:  None  None  Fixed at 3  Configurable  Configurable Requires Data Link Layer Confirmation:  Never  Always  Sometimes  Configurable GE Multilin L30 Line Current Differential System...
  • Page 636 FlexLogic. The On/Off times and Count value are ignored. “Pulse Off” and “Latch Off” operations put the appropriate Virtual Input into the “Off” state. “Trip” and “Close” operations both put the appropriate Virtual Input into the “On” state. L30 Line Current Differential System GE Multilin...
  • Page 637  16 Bits (Counter 8) Default Variation: 1  32 Bits (Counters 0 to 7, 9)  Point-by-point list attached  Other Value: _____  Point-by-point list attached Sends Multi-Fragment Responses:  Yes  No GE Multilin L30 Line Current Differential System...
  • Page 638: E.1.2 Implementation Table

    Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the L30 is not restarted, but the DNP process is restarted. L30 Line Current Differential System GE Multilin...
  • Page 639 Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the L30 is not restarted, but the DNP process is restarted. GE Multilin L30 Line Current Differential System...
  • Page 640 Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the L30 is not restarted, but the DNP process is restarted. L30 Line Current Differential System GE Multilin...
  • Page 641 Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the L30 is not restarted, but the DNP process is restarted. GE Multilin L30 Line Current Differential System...
  • Page 642: E.2.1 Binary Input Points

    Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time), Configurable Change Event Scan Rate: 8 times per power system cycle Change Event Buffer Size: 500 Default Class for All Points: 1 L30 Line Current Differential System GE Multilin...
  • Page 643: E.2.2 Binary And Control Relay Output

    Virtual Input 59 Virtual Input 28 Virtual Input 60 Virtual Input 29 Virtual Input 61 Virtual Input 30 Virtual Input 62 Virtual Input 31 Virtual Input 63 Virtual Input 32 Virtual Input 64 GE Multilin L30 Line Current Differential System...
  • Page 644: E.2.3 Counters

    Events Since Last Clear A counter freeze command has no meaning for counters 8 and 9. L30 Digital Counter values are represented as 32-bit inte- gers. The DNP 3.0 protocol defines counters to be unsigned integers. Care should be taken when interpreting negative counter values.
  • Page 645: E.2.4 Analog Inputs

    Change Event Variation reported when variation 0 requested: 1 (Analog Change Event without Time) Change Event Scan Rate: defaults to 500 ms Change Event Buffer Size: 256 Default Class for all Points: 2 GE Multilin L30 Line Current Differential System E-11...
  • Page 646 E.2 DNP POINT LISTS APPENDIX E E-12 L30 Line Current Differential System GE Multilin...
  • Page 647: F.1.1 Radius Server Configuration

    UR device for successful authentication, and the shortname is a short, optional alias that can be used in place of the IP address. client 10.0.0.2/24 { secret = testing123 shortname = private-network-1 In the <Path_to_Radius>\etc\raddb folder, create a file called dictionary.ge and add the following content. # ########################################################## GE VSAs ############################################################ VENDOR...
  • Page 648 Access Settings > Product Setup > Security. Configure the IP address and ports for the RADIUS server. Leave the GE vendor ID field at the default of 2910. Update the RADIUS shared secret as specified in the clients.conf file. Verify operation. Log in to the UR software as follows. In the login window, select Server as the Authentication Type, enter the user name entered (for example user name Tester and password "testpw").
  • Page 649: G.1.1 Revision History

    Update Updated FlexAnalog table Update Updated Modbus memory map and F codes Update Updated product warranty from 24 months to 10 years Table G–3: MAJOR UPDATES FOR L30 MANUAL REVISION Z2 (Sheet 1 of 2) PAGE PAGE CHANGE DESCRIPTION (Z1)
  • Page 650 G.1 CHANGE NOTES APPENDIX G Table G–3: MAJOR UPDATES FOR L30 MANUAL REVISION Z2 (Sheet 2 of 2) PAGE PAGE CHANGE DESCRIPTION (Z1) (Z2) Added Maintenance chapter, moving module replacement content from chapter 3, adding battery replacement instructions, and moving battery disposal instructions from beginning of manual Added appendix on RADIUS server configuration Table G–4: MAJOR UPDATES FOR L30 MANUAL REVISION Z1...
  • Page 651 APPENDIX G G.1 CHANGE NOTES Table G–7: MAJOR UPDATES FOR L30 MANUAL REVISION Y1 (Sheet 2 of 3) PAGE PAGE CHANGE DESCRIPTION (X2) (Y1) 2-10 2-10 Delete Deleted 9S, 2S, 2T from replacement module order code Tables 2-7 and 2-8...
  • Page 652 G.1 CHANGE NOTES APPENDIX G Table G–7: MAJOR UPDATES FOR L30 MANUAL REVISION Y1 (Sheet 3 of 3) PAGE PAGE CHANGE DESCRIPTION (X2) (Y1) 5-220 5-220 Delete Deleted section 5.8.5d Remote Devices: ID of Device for Receiving GSSE/GOOSE Messages, meaning the Settings > Input/Outputs > Remote Devices settings...
  • Page 653: G.2.1 Standard Abbreviations

    MRT ....Minimum Response Time MSG....Message F ..... Field MTA ....Maximum Torque Angle FAIL....Failure MTR ....Motor FD ....Fault Detector MVA ....MegaVolt-Ampere (total 3-phase) FDH....Fault Detector high-set MVA_A....MegaVolt-Ampere (phase A) FDL ....Fault Detector low-set GE Multilin L30 Line Current Differential System...
  • Page 654 WRT....With Respect To RST ....Reset RSTR ..... Restrained X ....Reactance RTD ....Resistance Temperature Detector XDUCER..Transducer RTU ....Remote Terminal Unit XFMR..... Transformer RX (Rx) ..Receive, Receiver Z..... Impedance, Zone L30 Line Current Differential System GE Multilin...
  • Page 655 G.3.1 GE MULTILIN WARRANTY For products shipped as of 1 October 2013, GE Digital Energy warrants most of its GE manufactured products for 10 years. For warranty details including any limitations and disclaimers, see the GE Digital Energy Terms and Conditions at https://www.gedigitalenergy.com/multilin/warranty.htm...
  • Page 656 G.3 WARRANTY APPENDIX G L30 Line Current Differential System GE Multilin...
  • Page 657 AUXILIARY UNDERVOLTAGE CHANNEL COMMUNICATION .......... 3-27 FlexLogic operands ............. 5-133 CHANNEL MONITOR ............2-18 logic ................5-194 CHANNEL STATUS Modbus registers ............B-44 Modbus registers ..........B-12, B-26 settings ............... 5-193 specifications ..............2-23 GE Multilin L30 Line Current Differential System...
  • Page 658 ..............6-4 DATE ................7-2 FlexLogic operands ............5-138 DCMA INPUTS ..............6-21 Modbus registers .........B-11, B-18, B-65 Modbus registers ..........B-20, B-66 settings ............... 5-237 settings ................ 5-249 CONTROL ELEMENTS ........... 5-197 specifications ..............2-27 L30 Line Current Differential System GE Multilin...
  • Page 659 ................5-101 Modbus registers ..........B-19, B-20 settings ................. 5-99 specifications ..............2-25 DISPLAY ............1-18, 4-22, 5-24 via EnerVista software ............. 4-2 DISPOSAL ..............11-10 EVENTS SETTING ............. 5-5 EXCEPTION RESPONSES ..........B-6 GE Multilin L30 Line Current Differential System...
  • Page 660 ..............5-149 G.703 ............ 3-30, 3-31, 3-32, 3-36 FlexLogic operands ............5-134 G.703 WIRE SIZE .............3-30 hysteresis ..............5-149 GE TYPE IAC CURVES ..........5-162 pickup ................. 5-149 GROUND CURRENT METERING ........6-16 scheme logic ............... 5-148 GROUND IOC settings ..........5-147, 5-148, 5-150 FlexLogic™...
  • Page 661 PHASE, GROUND, and NEUTRAL IOC entries description ..............2-20 INTER-RELAY COMMUNICATIONS ......2-17, 2-29 frequency ..............2-26 INTRODUCTION ..............1-3 power ................2-26 INVERSE TIME UNDERVOLTAGE ........5-190 voltage ................2-26 IN-ZONE TRANSFORMER ..........5-94 METERING CONVENTIONS ..........6-12 GE Multilin L30 Line Current Differential System...
  • Page 662 OVERCURRENT CURVE TYPES ........5-159 settings ............... 5-179 OVERCURRENT CURVES specifications..............2-22 definite time ..............5-163 NEUTRAL DIRECTIONAL OC FlexCurves ..............5-163 Modbus registers ............B-39 I2T ................5-163 IAC ................5-162 IEC ................5-161 IEEE ................5-159 L30 Line Current Differential System GE Multilin...
  • Page 663 PHASE ROTATION ............5-85 RELAY ACTIVATION ............4-26 PHASE TIME OVERCURRENT RELAY ARCHITECTURE ..........5-131 see entry for PHASE TOC RELAY MAINTENANCE ............7-3 RELAY NAME ..............5-82 RELAY NOT PROGRAMMED ..........1-19 GE Multilin L30 Line Current Differential System...
  • Page 664 SCAN OPERATION ............1-4 STUB BUS SECURITY FlexLogic operands ............5-137 delete files and records ..........11-7 logic ................5-158 SELECT BEFORE OPERATE ..........5-54 Modbus registers ............B-37 settings ................ 5-157 viii L30 Line Current Differential System GE Multilin...
  • Page 665 ..............2-24 TIMERS ................. 5-146 USER-PROGRAMMABLE PUSHBUTTONS FlexLogic operands ............5-139 ground ................ 5-177 Modbus registers ..........B-32, B-43 neutral ................ 5-170 settings ................. 5-74 phase ................5-164 specifications ..............2-25 specifications ..............2-22 GE Multilin L30 Line Current Differential System...
  • Page 666 WIRING DIAGRAM ............3-8 VOLTAGE ELEMENTS ........... 5-189 WITHDRAWAL FROM OPERATION ........11-7 VOLTAGE METERING specifications ..............2-26 values ................6-16 VOLTAGE RESTRAINT CHARACTERISTIC ....5-164 ZERO SEQUENCE CORE BALANCE .........3-11 ZERO-SEQUENCE CURRENT REMOVAL ......5-91 L30 Line Current Differential System GE Multilin...

Table of Contents