CHAPTER 5: SETTINGS

5.6.6 Power swing detect (ANSI 68)

SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  POWER SWING DETECT
 POWER SWING
 DETECT
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
Figure 5-114: Ground directional supervision logic
POWER SWING
FUNCTION: Disabled
POWER SWING
SOURCE: SRC 1
POWER SWING
SHAPE: Mho Shape
POWER SWING
MODE: Two Step
POWER SWING
SUPV: 0.600 pu
POWER SW I2 SUPV ENAB:
Off
POWER SWING
I2 SUPV: 0.200 pu
POWER SWING FWD
REACH: 50.00 Ω
POWER SWING QUAD FWD
REACH MID: 60.00 Ω
POWER SWING QUAD FWD
REACH OUT: 70.00 Ω
POWER SWING FWD
RCA: 75°
POWER SWING REV
REACH: 50.00 Ω
POWER SWING QUAD REV
REACH MID: 60.00 Ω
POWER SWING QUAD REV
REACH OUT: 70.00 Ω
POWER SWING REV
RCA: 75°
POWER SWING OUTER
LIMIT ANGLE: 120°
POWER SWING MIDDLE
LIMIT ANGLE: 90°
GROUPED ELEMENTS
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: Mho Shape, Quad Shape
Range: Two Step, Three Step
Range: 0.050 to 30.000 pu in steps of 0.001
Range: FlexLogic operand
Range: 0.050 to 30.000 pu in steps of 0.001
Range: 0.10 to 500.00 ohms in steps of 0.01
Range: 0.10 to 500.00 ohms in steps of 0.01
Range: 0.10 to 500.00 ohms in steps of 0.01
Range: 40 to 90° in steps of 1
Range: 0.10 to 500.00 ohms in steps of 0.01
Range: 0.10 to 500.00 ohms in steps of 0.01
Range: 0.10 to 500.00 ohms in steps of 0.01
Range: 40 to 90° in steps of 1
Range: 40 to 140° in steps of 1
Range: 40 to 140° in steps of 1
5