Clear Relay Records - GE L60 Instruction Manual

Line phase comparison system
Hide thumbs Also See for L60:
Table of Contents

Advertisement

PRODUCT SETUP
The power cut-off is therefore:
power cut-off= (
= (
× 0.02 pu × 1.0 V × 100 A × 13811.2 V) / 66.4 V
= 720.5 watts
Any calculated power value below this cut-off does not display. As well, the three-phase energy data do not accumulate if
the total power from all three phases does not exceed the power cut-off.
Lower the
VOLTAGE CUT-OFF LEVEL
measurements. Unless dictated otherwise by a specific application, the default settings of "0.02 pu" for
CUT-OFF LEVEL

5.3.3 Clear relay records

SETTINGS  PRODUCT SETUP  CLEAR RELAY RECORDS
 CLEAR RELAY
 RECORDS
5
RESET UNAUTH ACCESS
Selected records can be cleared from user-programmable conditions with FlexLogic operands. Assigning user-
programmable pushbuttons to clear specific records is a typical application for these commands. Since the L60 responds
to rising edges of the configured FlexLogic operands, they must be asserted for at least 50 ms to take effect.
Clearing records with user-programmable operands is not protected by the command password. However, user-
programmable pushbuttons are protected by the command password. Thus, if they are used to clear records, the user-
programmable pushbuttons can provide extra security if required.
For example, to assign user-programmable pushbutton 1 to clear demand records, apply the following settings.
1.
Assign the clear demand function to pushbutton 1 by making the following change in the
 CLEAR RELAY RECORDS
CLEAR DEMAND
2.
Set the properties for user-programmable pushbutton 1 by making the following changes in the
SETUP  USER-PROGRAMMABLE PUSHBUTTONS  USER PUSHBUTTON 1
PUSHBUTTON 1 FUNCTION
PUSHBTN 1 DROP-OUT TIME
5-28
×
CURRENT CUT-OFF LEVEL
OLTAGE CUT-OFF LEVEL
V
and
CURRENT CUT-OFF LEVEL
and "1.0 V" for
VOLTAGE CUT-OFF LEVEL
CLEAR FAULT REPORTS:
Off
CLEAR EVENT RECORDS:
Off
CLEAR OSCILLOGRAPHY:
Off
CLEAR DATA LOGGER:
Off
CLEAR ARC AMPS 1:
Off
CLEAR ARC AMPS 2:
Off
CLEAR DEMAND:
Off
RESET UNAUTH ACCESS:
Off
CLEAR DIR I/O STATS:
Off
— Resets the access restriction counter.
menu:
: "
"
PUSHBUTTON 1 ON
: "Self-reset"
: "0.20 s"
× CT primary × VT primary)/VT secondary
with care as the relay accepts lower signals as valid
are recommended.
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Visible only for units with Direct I/O module
menu:
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
CURRENT
SETTINGS  PRODUCT SETUP
SETTINGS  PRODUCT

Advertisement

Table of Contents
loading

Table of Contents