GE L60 Instruction Manual page 207

Line phase comparison system
Hide thumbs Also See for L60:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
The
menu allows selection of one of the following protocols: DNP 3.0, IEC60870-104, or IEC60870-103.
PROTOCOL
— This setting selects the SCADA protocol on which the unit communicates, among DNP3.0, IEC 60870-
SCADA PROTOCOL
104, and IEC 60870-103, with DNP being the default. Options depend on order code. For any change to take effect, restart
the unit.
— This setting specifies a time delay for the detection of network TCP connection lost. If there is
MMS CONNECTION TIMEOUT
no data traffic on the TCP connection for greater than the time specified by this setting, the connection is aborted. This
frees up the connection to be re-used by a client. For any change to take effect, restart the unit.
The table shows which of DNP 3.0, IEC 60870-5-104, IEC 60870-5-103, and IEC 61850 protocols are operational on the
RS232, RS485, and Ethernet ports. It shows all possible combinations of the
Table 5-10: Port and protocol combinations
PROTOCOL
DNP CHANNEL 1(2) PORT
setting
settings
DNP
Channel 1: Eth TCP
Channel 2: Eth TCP
Channel 1: Eth TCP
Channel 2: none
Channel 1: none
Channel 2: Eth TCP
Channel 1: Eth UDP
Channel 2: none
Channel 1: Eth TCP
Channel 2: RS485
Channel 1: Eth TCP
Channel 2: RS232
Channel 1: Eth UDP
Channel 2: RS485
Channel 1: Eth UDP
Channel 2: RS232
Channel 1: RS485
Channel 2: Eth TCP
Channel 1: RS232
Channel 2: Eth TCP
Channel 1: RS485
Channel 2: RS232
Channel 1: RS232
Channel 2: RS485
Channel 1: RS485
Channel 2: none
IEC 104
IEC 103
5.3.4.10 DNP protocol
SETTINGS  PRODUCT SETUP  COMMUNICATIONS  DNP PROTOCOL
 DNP PROTOCOL
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
MMS CONNECTION
TIMEOUT: 120 s
RS232
RS485
Modbus
Modbus
Modbus
Modbus
Modbus
Modbus
Modbus
Modbus
Modbus
DNP
DNP
Modbus
Modbus
DNP
DNP
Modbus
Modbus
DNP
DNP
Modbus
DNP
DNP
DNP
DNP
Modbus
DNP
Modbus
Modbus
Modbus
IEC 103
 DNP CHANNELS
DNP ADDRESS:
1
 DNP NETWORK
 CLIENT ADDRESSES
Range: 10 to 7200 in steps of 10
and
PROTOCOL
DNP CHANNEL 1(2) PORT
Ethernet
DNP, Modbus, IEC 61850
DNP, Modbus, IEC 61850
DNP, Modbus, IEC 61850
DNP, Modbus, IEC 61850
DNP, Modbus, IEC 61850
DNP, Modbus, IEC 61850
DNP, Modbus, IEC 61850
DNP, Modbus, IEC 61850
DNP, Modbus, IEC 61850
DNP, Modbus, IEC 61850
Modbus, IEC 61850
Modbus, IEC 61850
Modbus, IEC 61850
IEC 104, Modbus, IEC 61850
Modbus, IEC 61850
See below
Range: 0 to 65535 in steps of 1
See below
PRODUCT SETUP
settings.
5