RECORDS

6.5.4 Data logger

ACTUAL VALUES  RECORDS  DATA LOGGER
 DATA LOGGER
The
OLDEST SAMPLE TIME
full, at which time it starts counting at the defined sampling rate.
The
NEWEST SAMPLE TIME
rate. If the data logger channels are defined, then both values are static.
See the
COMMANDS  CLEAR RECORDS

6.5.5 Breaker maintenance

ACTUAL VALUES  RECORDS  MAINTENANCE  BREAKER 1(2)
 BREAKER 1
6
There is an identical menu for each of the breakers.
The
BKR 1 ACC ARCING AMP
breaker arcing current records.
The
BREAKER OPERATING TIME
All of the values are stored in non-volatile memory and retained with power cycling.
6-26
OLDEST SAMPLE TIME:
2000/01/14 13:45:51
NEWEST SAMPLE TIME:
2000/01/14 15:21:19
represents the time at which the oldest available samples were taken. It is static until the log gets
represents the time the most recent samples were taken. It counts up at the defined sampling
menu for clearing data logger records.
BKR 1 ACC ARCING AMP
φA: 0.00 kA2-cyc
BKR 1 ACC ARCING AMP
φB: 0.00 kA2-cyc
BKR 1 ACC ARCING AMP
φC: 0.00 kA2-cyc
BKR 1 OPERATING TIME
φA:
0 ms
BKR 1 OPERATING TIME
φB:
0 ms
BKR 1 OPERATING TIME
φC:
0 ms
BKR 1 OPERATING
TIME: 0 ms
BKR 1 ARCING AMP φA:
0.00 kA2-cyc
BKR 1 ARCING AMP φB:
0.00 kA2-cyc
BKR 1 ARCING AMP φC:
0.00 kA2-cyc
BKR 1 AMP MAX φA:
0.00 kA
BKR 1 AMP MAX φB:
0.00 kA
BKR 1 AMP MAX φC:
0.00 kA
2
values are in units of kA
-cycles. See the
is defined as the slowest operating time of breaker poles that were initiated to open.
CHAPTER 6: ACTUAL VALUES
COMMANDS  CLEAR RECORDS
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL