Inputs - GE L60 Instruction Manual

Line phase comparison system
Hide thumbs Also See for L60:
Table of Contents

Advertisement

CHAPTER 2: PRODUCT DESCRIPTION
Parameters:
Update rate:
VAR-HOURS (POSITIVE AND NEGATIVE)
Accuracy:
Range:
Parameters:
Update rate:
FREQUENCY
Accuracy at
V = 0.8 to 1.2 pu:
I = 0.1 to 0.25 pu:
I > 0.25 pu:
DEMAND
Measurements:
Accuracy:

2.5.5 Inputs

AC CURRENT
CT rated primary:
CT rated secondary:
Relay burden:
Conversion range:
Standard CT:
Sensitive Ground CT module:
Current withstand:
Short circuit rating:
AC VOLTAGE
VT rated secondary:
VT ratio:
Relay burden:
Conversion range:
Voltage withstand:
FREQUENCY
Nominal frequency setting:
Sampling frequency:
Tracking frequency range:
CONTACT INPUTS
Dry contacts:
Wet contacts:
Selectable thresholds:
Tolerance:
Contacts per common return:
Recognition time:
Debounce time:
Continuous current draw:
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
three-phase only
50 ms
±2.0% of reading
6
±0 to 1 × 10
Mvarh
three-phase only
50 ms
±0.001 Hz (when voltage signal is used for frequency measurement)
±0.005 Hz
±0.02 Hz (when current signal is used for frequency measurement)
Phases A, B, and C present and maximum measured currents
3-Phase Power (P, Q, and S) present and maximum measured currents
±2.0%
1 to 50000 A
1 A or 5 A by connection
< 0.2 VA at rated secondary
0.02 to 46 × CT rating RMS symmetrical
0.002 to 4.6 × CT rating RMS symmetrical
20 ms at 250 times rated
1 sec at 100 times rated
continuous 4xInom
150000 RMS symmetrical amperes, 250 V maximum (primary current to external CT)
50.0 to 240.0 V
1.00 to 24000.00
< 0.25 VA at 120 V
1 to 275 V
continuous at 260 V to neutral
1 min/hr at 420 V to neutral
25 to 60 Hz
64 samples per power cycle
20 to 70 Hz
1000 Ω maximum
300 V DC maximum
17 V, 33 V, 84 V, 166 V
±10%
4
< 1 ms
0.0 to 16.0 ms in steps of 0.5
4 mA (when energized)
SPECIFICATIONS
2
2-27

Advertisement

Table of Contents
loading

Table of Contents