5.6.4 Line pickup

SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  LINE PICKUP
 LINE PICKUP
5-188
Figure 5-93: Open breaker echo logic
LINE PICKUP
FUNCTION: Disabled
LINE PICKUP SIGNAL
SOURCE: SRC 1
PHASE IOC LINE
PICKUP: 1.000 pu
LINE PICKUP UV PKP:
0.700 pu
LINE END OPEN PICKUP
DELAY: 0.150 s
LINE END OPEN RESET
DELAY: 0.090 s
LINE PICKUP OV PKP
DELAY: 0.040 s
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: 0.020 to 30.000 pu in steps of 0.001
Range: 0.004 to 3.000 pu in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001