User-Programmable Self-Tests - GE L60 Instruction Manual

Line phase comparison system
Hide thumbs Also See for L60:
Table of Contents

Advertisement

PRODUCT SETUP
Table 5-16: Recommended settings for user-programmable LEDs
Setting
LED 1 operand
LED 2 operand
LED 3 operand
LED 4 operand
LED 5 operand
LED 6 operand
LED 7 operand
LED 8 operand
LED 9 operand
LED 10 operand
LED 11 operand
LED 12 operand
See the figure in the Setting Groups section of the Control Elements section later in this chapter for an example of group
activation.

5.3.12 User-programmable self-tests

SETTINGS  PRODUCT SETUP  USER-PROGRAMMALBE SELF TESTS
 USER-PROGRAMMABLE
5
 SELF TESTS
All major self-test alarms are reported automatically with their corresponding FlexLogic operands, events, and targets.
Most of the minor alarms can be disabled if so wanted.
When in the Disabled mode, minor alarms do not assert a FlexLogic operand, write to the event recorder, or display target
messages. Moreover, they do not trigger the ANY MINOR ALARM or ANY SELF-TEST messages. When in Enabled mode,
minor alarms continue to function along with other major and minor alarms. See the Relay Self-tests section in chapter 7
for information on major and minor self-test alarms.
5-108
Parameter
SETTING GROUP ACT 1
SETTING GROUP ACT 2
SETTING GROUP ACT 3
SETTING GROUP ACT 4
SETTING GROUP ACT 5
SETTING GROUP ACT 6
Off
Off
BREAKER 1 OPEN
BREAKER 1 CLOSED
BREAKER 1 TROUBLE
Off
DIRECT RING BREAK
FUNCTION: Enabled
DIRECT DEVICE OFF
FUNCTION: Enabled
RxGOOSE OFF
FUNCTION: Enabled
FIRST ETHERNET FAIL
FUNCTION: Disabled
SEC. ETHERNET FAIL
FUNCTION: Disabled
THIRD ETHERNET FAIL
FUNCTION: Disabled
SFP MODULE FAIL
FUNCTION: Disabled
BATTERY FAIL
FUNCTION: Enabled
SNTP FAIL
FUNCTION: Enabled
IRIG-B FAIL
FUNCTION: Enabled
PTP FAIL
FUNCTION: Enabled
Setting
Parameter
LED 13 operand
Off
LED 14 operand
BREAKER 2 OPEN
LED 15 operand
BREAKER 2 CLOSED
LED 16 operand
BREAKER 2 TROUBLE
LED 17 operand
SYNC 1 SYNC OP
LED 18 operand
SYNC 2 SYNC OP
LED 19 operand
Off
LED 20 operand
Off
LED 21 operand
AR ENABLED
LED 22 operand
AR DISABLED
LED 23 operand
AR RIP
LED 24 operand
AR LO
Range: Disabled, Enabled. Valid for units equipped
with Direct Input/Output module.
Range: Disabled, Enabled. Valid for units equipped
with Direct Input/Output module.
Range: Disabled, Enabled
Range: Disabled, Enabled
Range: Disabled, Enabled
Range: Disabled, Enabled
Range: Disabled, Enabled
Range: Disabled, Enabled
Range: Disabled, Enabled
Range: Disabled, Enabled
Range: Disabled, Enabled
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS