SMC Networks PSE200 Operation Manual page 36

Multi channel pressure sensor controller
Hide thumbs Also See for PSE200:
Table of Contents

Advertisement

○Error indication function
This function is to display error location and content when a problem or an error occurs.
Error Name
Error Display
OUT1
Over
current
Error
OUT2
Zero-clear Error
Pressurizing Error
System Error
If the error can not be reset after the above measures are taken, then please contact SMC.
Error Type
A load current of switch output is 80 mA
or more.
During zero clear operation, pressure
over ±5%F.S. (±2.5%F.S for compound
pressure) is applied. After 2 s, the mode
will reset to the measurement mode.
Pressure has exceeded the upper limit
of the set pressure range.
A sensor has the possibility of
un-connecting and miswiring.
Pressure has exceeded the lower limit of
the set pressure range.
Displayed in the case of an internal data
error.
-35-
Troubleshooting Method
Turn the power off and remove the
output factor for the over current.
Then turn the power on.
Perform zero clear operation again
after restoring the applied pressure to
an atmospheric pressure condition.
Check connection and wiring of a
sensor. And reset applied pressure to
a level within the set pressure range.
Turn the power off and turn it on again.
If resetting fails, an investigation by
SMC CORPORATION will be
required.
No.PS##-OMH0006-C