6-4 Block-C parameters
The Block-C parameters are divided into the basic functions, extended functions and hardware option
functions.
No.
Parameter
C00 – Control methods
0
Run command
method
1
RUN/STOP methods
2
Jog stop method
3
Emergency stop
(EMS) input logic
4
Emergency stop
(EMS) mode
5
Control source
switchover method
(J1 setting)
6
Control source
switchover method
(J2 setting)
7
Run contact output
condition selection
C01 – Start/stop frequency
0
Start frequency
1
Stop frequency
(DC brake start)
6. Control Functions and Parameter Settings
Block-C parameters (Basic function constants) list
Unit
Default
Min.
1.
1.
2.
1.
2.
1.
1.
1.
1.
1.
1.
1.
1.
1.
1.
1.
Hz
1.0
0.1
Hz
1.0
0.1
Max.
Function
3.
Run command method is set.
= 1 : F·RUN, R·RUN
= 2 : RUN, REV
= 3 : Pulse (by Push-buttons)
(Pulse inputs for F·RUN and
R·RUN)
2.
Set the stopping method for RUN
operation.
= 1 : Coast to stop
= 2 : Ramp down to stop
2.
Set the stopping method for JOG
operation.
= 1 : Coast to stop
= 2 : Ramp down to stop
2.
Emergency stop input logic is set.
= 1 : Close to stop
= 2 : Open to stop
3.
Set the stopping method for the
emergency stop.
= 1 : Coast to stop without a fault
output
= 2 : Coast to stop with a fault
output
= 3 : Ramp down to stop
2.
Set whether to validate the remote
operation sequence for the local
operation mode. Fig 5.2
= 1 : Disables
= 2 : Enables
2.
Select the No. of auxiliary operation
sequence input points when the COP
command is ON. Fig 5.2
= 1 : Terminal block input
= 2 : Serial input
2.
The conditions for turning the
sequence RUN output ON are set.
= 1 : ON at pre-excitation
= 2 : OFF at pre-excitation
60.0
60.0
6-20
Application
ST
V/f VEC PM