C15-0

Attainment (ATN) detection width

The attained output ATN operation width is
set.
C15-1

Current (IDET) detection level

The current detection (IDET) operation level
is set. Set with a percentage of the rated
current (B00-6, B01-6).
A 5% hysteresis is fixed for the IDET
operation.
Speed detection (SPD 1) level − 1
C15-2
Speed detection (SPD 2) level − 2
C15-3
The speed detection SPD 1 and 2 operation
level is set.
Set with a percentage to the max. frequency
(B00-4) or max. speed (B01-4).
The output frequency or the motor speed will
be the comparison target.
A 1% hysteresis is fixed for SPD1 and SPD2
operation.
C15-4

Zero speed detection (ZSP) level

The zero speed detection ZSP operation
level is set.
Set with a percentage to the max. frequency
(B00-4) or max. speed (B01-4).
The output frequency or the motor speed will
be the comparison target.
6. Control Functions and Parameter Settings
6-63
C15-0
O N
ATN
O utput current
C15-1
O N
IDE T
O utput frequency
C15-2
C15-3
SPD 1
SPD 2
O utput frequency
(M otor Speed)
C15-4
O N
ZS P
O utput
frequency
Time
O N
5%
1%
1%
Time
1%
Time