B10-0
Acceleration ramp time –2
B10-1
Deceleration ramp time –2
B10-2

Acceleration ramp time for jogging

B10-3

Deceleration ramp time for jogging

The ramp up/down time can be switched by turning the sequence command CSEL to ON.
Set the CSEL command input terminal with C03-6 parameter.
The ramp time for jogging can be set independently with B10-2 and -3.
F.JO G
F.R U N
E M S -C S E L
(C 0 3-6 =1 4)
The above run example shows the case when the sequence command CSEL is connected
to the EMS terminal (C03-6=14), and the run is decelerated with ramp down time −2 during
emergency stop.
(Note)
6. Control Functions and Parameter Settings
B 1 0-2
B 1 0-3
The acceleration or deceleration ramp time set, is the time to reach maximum
frequency (B00-4) or maximum speed (B01-4) from zero, or the opposite.
C S E L = O FF
C S E L = O N
A ccelera tio n 1
D e ce le ratio n 2
(A 0 1-0)
(B 1 0-1)
6-40
C S E L = O FF
D e ce le ratio n 1
(A 0 1-1)
Tim e