5-6 Changing of terminal functions
The programmable input terminals (PSI1 to PSI9) can be arbitrarily assigned to control internal
commands. On the other hand the state of some internal functions can be connected to the
programmable output terminals (RA-RC and PSO1 to PSO5) to lead out the ON/OFF signals.
5-6-1 Sequence input terminal assignment and monitoring
The functions that can be assigned to the terminal block are shown in Fig. 5-3. Each internal function
can be fixed to ON (set value to 16) or OFF (set value to 0). If the function is set for example at "1",
then input PSI1 can switch that function ON/OFF. Fig 5-3 shows the default assignment, where
R.RUN has been assigned to PSI1 input (C03-0=1).
Fig. 5-4 shows monitoring display allowed by parameter D04-0, 1, or 2. Thus the ON state of each
internal signal can be known trough the operation panel display.
Term inal block
O FF
P S I1
P S I2
P S I3
P S I4
P S I5
P S I6
P S I7
P S I8
P S I9
E M S
F.R U N
O N
Fig. 5-3 Assignment of sequence input
5. Control Input / Output
Internal comm and
P S I
0
C 0 3-0 =1
R .R U N
1
C 0 3-1 =2
F.JO G
2
C 0 3-2 =3
R .JO G
3
C 0 3-3
H O L D
4
C 0 3-4
B R A K E
5
C 0 3-5
C O P
6
C 0 3-6
C S E L
7
C 0 3-7
IPA S S
8
C 0 3-8
P ID E N
9
C 0 4-0
C PA S S
1 0
C 0 4-1 =1 6
V F S
11
C 0 4-2
IF S
1 2
C 0 4-3
A U X
1 3
C 0 4-4
P R O G
1 4
C 0 4-5
C S F
1 5
C 0 4-6
S 0
1 6
C 0 4-7
S 1
C 0 4-8
S 2
C 0 4-9
S 3
C 0 5-0
S E
C 0 5-1
FU P
C 0 5-2
FD W
C 0 5-3
B U P
C 0 5-4
B D W
C 0 5-5
IV LM
C 0 5-6
A U X D V
C 0 5-7
P IC K
C 0 5-8
E X C
C 0 5-9
A C R
C 0 6-0
P C T L
C 0 6-1
L IM 1
C 0 6-2
L IM 2
C 0 6-3
M C H
C 0 6-4
R F0
C 0 6-5
D R O O P
C 0 6-6
D E D B
C 0 6-7
TR Q B 1
C 0 6-8
TR Q B 2
Fig. 5-4 Sequence input monitor
5-9
C FS
P R O G
A U X
IF S
V F S
C PA S S
IPA S S
C S E L
E M S
R E S E T
R U N
R E V
JO G
E X C
B R A K E
C O P
D04-0 Display
L IM 2
L IM 1
P C T L
A C R
P IC K
A U X D V
IV LM
B D W
S 0
S 1
S 2
S 3
S E
FU P
FD W
D04-1 Display
B U P
M C H
R F0
D R O O P
D E D B
TR Q B 1
TR Q B 2
D04-2 Display
P ID E N