Fault Codes - GE VAT2000 Instruction Manual

Ac speed control equipment
Hide thumbs Also See for VAT2000:
Table of Contents

Advertisement

Appendix 3 Fault Codes
Code
Display
0
— — —
1
(EmS)
2
(PM-n)
3
(OC-n)
4
(OV-n)
5
(UV-n)
6
Not defined
7
8
9
Not defined
A
(ATT-n)
B
(OL-n)
C
(GRD. n) Ground
Appendix
Fault
No fault
No fault recorded.
Emergency
Indicates that sequence signal EMS has been input in C00-4 = 2 (fault
stop
output at emergency stop) mode.
Power
Power module fault
Module
n: sub-code
Over
The output has risen to or beyond 300%.
current
n: sub-code
The DC voltage has risen to or beyond the preset level. (Vdc ≥ 800 or
Over
voltage
400V)
n: sub-code
Under
While the drive is running, the DC voltage has lowered to or beyond the
voltage
preset level (65% of the rating).
n: sub-code
At C08-0 = 2, 3 (automatic start), only the symbol displays, so the FLT
LED and terminal block FA, FB and FC contacts will not operate. EC0 to
3 will operate.
Overheat
The heatsink temperature has risen to or beyond 95°C.
Overspeed
Indicates that the motor speed exceeded the overspeed setting value
(C24-0).
Automatic
This indicates that the automatic tuning did not complete normally.
tuning
n: Automatic tuning step No. (when interrupted)
abnormal
(1)
ACR simple setting
completion
(2)
Single-phase AC measurement
(3)
ACR adjustment
(9)
Excitation inductance measurement
(A)
Secondary resistance measurement
(B)
Max. torque boost adjustment
(C)
Excitation inductance fluctuation table adjustment
Overload
Indicate that the output current exceeded the thermal operation time
having inverse time characteristics. The standard characteristics are
150% for one minute in respect to the motor rated current. At 155% or
more in respect to the inverter rated current, this will be 170% for 2.5
seconds.
n: Sub-code 1: Drive output overload
The Drive has sensed a grounded conditions on the output.
n: sub-code
Description
1: during stop
3: during acceleration
5: during braking
7: during pre-extension
1: during stop
3: during acceleration
5: during braking
7: during pre-extension
1: during stop
3: during acceleration
5: during braking
7: during pre-extension
1: during stop
3: during acceleration
5: during braking
7: during pre-extension
1: during stop
3: during acceleration
5: during braking
7: during pre-extension
A-9
2: during operation at
the set speed
4: during deceleration
6: during ACR
9: during automatic tuning
2: during operation at
the set speed
4: during deceleration
6: during ACR
9: during automatic tuning
2: during operation at
the set speed
4: during deceleration
6: during ACR
9: during automatic tuning
2: during operation at
the set speed
4: during deceleration
6: during ACR
9: during automatic tuning
2: during operation at
the set speed
4: during deceleration
6: during ACR
9: during automatic tuning
Retry
×
×



×

×
×



Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents