Pattern Run Function - GE VAT2000 Instruction Manual

Ac speed control equipment
Hide thumbs Also See for VAT2000:
Table of Contents

Advertisement

B50-0~0

Pattern run function

to B59-3
The frequency (speed), run direction and operation time can be controlled automatically with
the pattern run function
R U N
(1) A max. of ten patterns can be set. Program in the B50-B59 blocks as shown below.
The remote setting input point is selected with C02-0 = 4
n is the step No. from 0 to 9.
B5n-0: Run mode
B5n-1: Run frequency or speed (%)
B5n-2: Run time (sec)
B5n-3: Return destination step
6. Control Functions and Parameter Settings
B 5 1-1
B 5 0-1
S tep -0
S tep -1
B 5 0-2
B 5 1-2
= 0: Stop
= 1: Forward run
= 2: Reverse run
= 3: Final step (set when repeating before B59)
= 0 to 8
(Set the No. of the step to be executed next when B5n-0=3.)
B 5 2-1
S tep -2
B 5 2-2
6-54
B 5 4-1
B 5 3-1
S tep -3
S tep -4
B 5 3-2
B 5 4-2
tim e