Run Delay Timer; Setting Start/Stop Function; Start Interlock - GE VAT2000 Instruction Manual

Ac speed control equipment
Hide thumbs Also See for VAT2000:
Table of Contents

Advertisement

C20-0
Start/stop frequencies (speeds)
C20-1
Start/stop frequency (speed) hysteresis
C20-2
Interlock frequency (speed)
C20-3

Run delay timer

The following types of interlock can be obtained for the run RUN and R·RUN commands.
R U N
R .R U N
Fre q ue ncy settin g
(spe ed )

(1) Setting start/stop function

The motor will run when the frequency (speed) setting is higher than the C20-0 setting
value, and will stop when lower.
Starting and stopping with the setter is possible with this function.

(2) Start interlock

If the frequency (speed) setting value is larger than C20-2 when the run command
(RUN X) is ON, the motor will not start.
(Note) The setting start/stop and start interlock functions cannot be used
(3) Run delay timer
The motor will be delayed from the run command (RUN X) by the time set in C20-3.
This is used for synchronisation with peripheral machines such as mechanical brakes.
The run delay timer will not function in the jogging or local modes.
(Note 1)
(Note 2)
(Note 3)
(Note 4)
6. Control Functions and Parameter Settings
3
R U N X
O N d elay tim er
1
H ystere sis C o m p arato r
C 2 0-0
H ystere sis
C 2 0-1
R U N X
2
C 2 0-2
simultaneously. Thus, set C20-0 or C20-2 to 0.
O N
F ·R U N
R U N Y
Set the parameter setting values to 0 when not using (1),, (2) or (3).
The (1), (2) and (3) functions will not function during jogging run.
The (3) function will not function during the local mode.
When interlock is applied on (1), (2) or (3), the FWD or REV LED will flicker.
C 2 0-3
O N
tD LY
C 2 0-3
6-64
R U N Y