Faults
All faults will cause:
the generating set to stop: immediate or gradual stop (coolant temperature and overload or short circuit)
the red LED to flash "General fault".
In conjunction with this LED:
a flashing pictogram appears on the LCD screen
representing the circuit affected by the fault and the
associated indicator, if present
(example)
Faults have priority over alarms. Faults are displayed in the descending order of their appearance (from the most recent to the oldest).

Activation of an alarm or fault

6.3.4.2.
The appearance of an alarm or a fault causes the corresponding screen to be displayed (examples below)
FAULT
ALARM
Low coolant Level
06/10/06
OK=HELP
Press OK (on the scrolling and selection wheel) to access the help message if it is available (example below)
HELP
Check the level
fuel
Esc=EXIT
If the alarm is no longer active, it is reset automatically (cause disappears).
Press Esc to reset a fault:
reset acknowledged if the cause of the fault has been removed
-
reset not performed if the cause of the fault is still present.
-
10:30
message on graphic display (example)
FAULT
FAULT
Oil Pressure
25/12/05
OK=HELP
FAULT
FAULT
Emergency Stop
06/10/06 15:30
Esc=RESET
78/242
15:30
OK=HELP