R438 A.v.r; Characteristics; Frequency Compared With Voltage (Without Lam); Lam (Load Acceptance Module) Characteristics - SDMO R33C3 User And Maintenance Manual

Table of Contents

Advertisement

LEROY-SOMER

2 - R438 A.V.R.

2.1 - Characteristics

- Storage : -55°C ; +85°C
- Operation : -40°C ; +70°C
- Standard power supply: AREP or PMG.
- Rated overload current: 8 A - 10 s
- Electronic protection (overload, short-cir-
cuit on opening of voltage sensing circuit):
excitation overload current for 10 seconds
then return to approximately 1A. The alter-
nator must be stopped (or the power
switched off) in order to reset the protection.
- Fuse : F1 on X1, X2. 8A ; slow - 250V
- Voltage sensing : 5 VA isolated via trans-
former ;
• 0-110 V terminals = 95 to 140 V,
• 0-220 V terminals = 170 to 260 V,
• 0-380 V terminals = 340 to 520 V.
- Voltage regulation ± 1%.
- Normal or rapid response time via ST2
jumper (see below).
- Voltage adjustment via potentiometer P2.
other voltages via adapter transformer
- Current sensing (parallel operation): C.T.
2.5 VA cl1, secondary 1 A (optional).
- Quadrature droop adjustment via potentio-
meter P1.
- Max. excitation current adjustment via P5
(see below).
Configuration jumpers function
2.1.1 -
Delivrery
config.
Pot.
Position
Open
Closed
ST1
3-ph.
Mono
ST2
Fast
Normal
ST3
50 ou 60 Hz Frequency selection
External
ST4
potentio-
Without
meter
ST5 Without
With
Others
ST9
AREP
(PMG...)
ST10
13% or 25%
48 or
ST11
65 Hz
58 Hz
6
Installation and maintenance
R438
A.V.R.
Function
Open for module
installation tri detection
Response time
Potentiometer
LAM
Supply
LAM voltage drop
amplitude
U/f function bend
position
232/242
Setting potentiometers
2.1.2 -
function
Delivrery
Pot.
position
0
P1
Quadrature droop ; // operation with C.T.
400V
P2
Voltage
Centre
P3
Stability
Maxi
P5
Excitation current ceiling
2.2 - Frequency compared with
voltage (without LAM)
Voltage
Bend
48 Hz
100 %
U/U
50 Hz
N
2.3 - LAM (Load Acceptance
Module) characteristics
2.3.1 - Voltage drop
The LAM system is integrated in the R 438
AVR as standard.
Role of the «LAM» (Load Adjustment Mo-
dule) :
On application of a load, the rotation speed
of the generator set decreases. When it
passes below the preset frequency thres-
hold, the LAM causes the voltage to drop by
approximately 13% or 25% and conse-
quently the amount of active load applied is
reduced by approximately 25% to 50%, until
the speed reaches its rated value again.
Hence the LAM can be used either to reduce
the speed variation (frequency) and its dura-
tion for a given applied load, or to increase
the applied load possible for one speed va-
riation (turbo-charged engine).
To avoid voltage oscillations, the trip thres-
hold for the LAM function should be set ap-
proximately 2 Hz below the lowest frequen-
cy in steady state.
3971 en -
2010.11 / f
Function
57.5 Hz
60 Hz
Frequency
Hz
50 Hz
60 Hz