Connecting The Battery Or Batteries To The Generating Set; Overvoltage; Installation; Warnings Concerning Commissioning - SDMO R33C3 User And Maintenance Manual

Table of Contents

Advertisement

Connecting the battery or batteries to the generating set

4.2.3.4.
Always ensure that the polarities of the battery and starter motor correspond. Never swap the positive and
negative battery terminals when connecting them. This could cause severe damage to the electrical equipment.
IMPORTANT

4.2.4 Overvoltage

Generating sets are not equipped with devices that protect against voltage surges from atmospheric discharges or due to handling
operations.
The company disclaims all liability for any accidents caused by these phenomena.
However, it is possible to install surge protectors considering that this assembly does not provide complete protection.

5. Installation

5.1. Warnings concerning commissioning

The inspections referred to in this section enable the electrical generator set to operate.
Specific skills are required to carry out these operations.
They must only be entrusted to personnel with the necessary skills.
IMPORTANT
Failure to follow these instructions in any way could result in malfunction or very serious accidents.

5.2. Checking the generating set installation

Check the position of the generating set (stability, mounting, available space, ventilation, exhaust, etc.).
-
Check the electrical connections :
-
earthing;
electrical control connections;
electrical power connections;
starter battery charging system (rating and voltage) if fitted to the generating set.
To connect the battery:
1. Connect the red connecting cable (+) to the positive battery terminal.
2. Then connect the black cable (-) to the negative battery terminal.
To disconnect the battery:
1. First disconnect the black cable (-)
2. Then disconnect the red cable (+).